| Date |
Text |
| 2007-01-30 17:59:07 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | |
| | FROM PREVIOUS REVIEW: |
| | FROM PREVIOUS REVIEW: |
| | |
| | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI |
| | REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF |
| | REGULATOR. |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED |
| | |
| | F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT |
| | DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000 |
| | BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS |
| | QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT |
| | 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2" |
| | PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA |
| | DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS |
| | APPROXAMATLY 180'. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE |
| | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. |
| | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE |
| | MODEL NUMBER. LISTING INFORMATION REQUIRED. |
| | |
| | H. NA |
| | I.NA |
| | |