| Date |
Text |
| 2006-12-25 20:33:37 | ** UNSAT 2ND REVIEW ** |
| | |
| | |
| | **** CITY CENTER ******* |
| | |
| | FOURTH REVIEW, 2ND UNDER PERMIT APPLICATION. |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A "NO" IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN "OK" WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A "NO/OK" MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE THREE SETS OF ALL ARE REQUIRED. |
| | PLEASE SEE MISSING A THIRD SET OF ELECTRICAL SUBMITTALS |
| | FOR GENERATOR, ATS, MTS ETC. |
| | PLEASE ALSO SEE OTHER NOTES FOR MISSING THE LIGHTING |
| | SPEC BOOKS AND ENGINEERING CALCULATIONS WHICH WERE |
| | PREVIOUSLY SUBMITTED. |
| | ENGINEERING FOR SELECTIVE COORDINATION PREVIOUSLY |
| | SUBMITTED ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW WHEN SUBMITTING FOR FINAL PERMITTING AND |
| | STAMPING, A THIRD SET OF SIGNED, DATED AND SEALED PLANS |
| | WILL BE REQUIRED. |
| | PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR |
| | THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL |
| | DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: NO, PLEASE SEE SYMBOL LEGEND ONLY HAD CHANGES |
| | TO TWO OF THE DEVICES. PLEASE SEE ALL SWITCH/OVER RIDE |
| | TYPE DEVICES INCLUDING THE OC SENSOR SHOULD INDICATE ON |
| | THE SYMBOL LEGEND ITS DESIGNATION AND TIMES ON OVER |
| | RIDES. THIS WOULD INCLUDE S3, ST, OC ETC. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13. PLEASE SEE 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE |
| | DEVICE SYMBOL LEGEND. |
| | PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF |
| | TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30 |
| | MINS MAX). |
| | PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM |
| | BEING PROPOSED. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK/NO, PLEASE SEE THESE WERE NOW SUBMITTED |
| | HOWEVER PLEASE SEE NEW NOTES AT THE END OF THESE |
| | COMMENTS AS THESE ARE NOW BEING SUBMITTED AND REVIEWED |
| | FOR THE FIRST TIME AND THERE ARE COMMENTS ON DOCUMENTS |
| | SUBMITTED. |
| | PLEASE ALSO SEE NEW NOTES PERTAINING TO THE SIGNATURE |
| | OF THE MECHANICAL ENGINEER OF RECORD ON SAID |
| | DOCUMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS FOR THE |
| | ENTIRE BUILDING FOR REVIEW OF ALL TRADES. PLEASE KNOW |
| | AS NONE WERE SUBMITTED AT THIS TIME THERE ARE MANY |
| | ITEMS WHICH CAN NOT BE VERIFIED WITH THE PLANS, |
| | EQUIPMENT AND LIGHTING. |
| | PLEASE SEE 13-415.1.AB.1. |
| | |
| | 5) NOTE: OK/NO, PLEASE SEE THESE WERE SUBMITTED AND |
| | SEEM TO BE OK, HOWEVER AS NOTED IN NOTE #4 ABOVE THERE |
| | ARE NEW NOTES BASED ON THE COORDINATION OF THESE |
| | DOCUMENTS WITH THE ENERGY CALCULATIONS SUBMITTED. |
| | PLEASE SEE THE TOTALS ON THE WATTAGE DO NOT SEEM TO |
| | CORRELATE WITH THE ENERGY CALCULATIONS AS SUBMITTED. |
| | PLEASE ALSO SEE NEW NOTES. |
| | PLEASE KNOW THE THREE SETS OF LIGHTING POWER DENSITIES |
| | SHALL CONTAIN TITLE BLOCKS FOR THE ENGINEER AND/OR FIRM |
| | OF RECORD. THIS MAY BE RE-DONE ON NEW SHEETS WHICH |
| | CONTAIN THESE TITLE BLOCKS, STAMPED ON EACH SHEET WHICH |
| | IS SIGNED AND SEALED BY THE ENGINEER OR HANDWRITTEN. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM AND |
| | MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE |
| | CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER |
| | DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS |
| | WHICH DO NOT CORRELATE WITH SAID PLANS. |
| | PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS |
| | WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE |
| | ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON |
| | PLANS. |
| | PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM |
| | TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS |
| | NOTED AND SHOWN. |
| | PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE. |
| | PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS |
| | SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS |
| | MAY SHOW 10.5 ETC. |
| | PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND |
| | NEEDED. |
| | |
| | 6) NOTE: NO, UNABLE TO VERIFY AT THIS TIME DUE TO THE |
| | CONFLICTS BETWEEN THE ENERGY CALCULATIONS FOR EXTERIOR |
| | LIGHTING AND THE ALLOWANCE LEVELS NOT BEING SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR LIGHTING |
| | ALLOWANCES, INCLUDING THAT WHICH IS DECORATIVE. PLEASE |
| | SEE THERE ARE EXCEPTIONS FOR SOME AREAS; HOWEVER THESE |
| | AREAS AS LISTED WOULD BE REQUIRED BY SECTIONS AS |
| | LISTED. PLEASE SEE 13-415.0(3) (EXCEPTS). |
| | |
| | 7) NOTE: OK/NO, PLEASE SEE THE PLANS NOW SEEM TO |
| | INDICATE THE EQUIPMENT MORE IN DETAIL, HOWEVER AS NOTED |
| | IN NOTE #1, THE MANUFACTURES SPECS/CUT SHEETS WERE NOT |
| | SUBMITTED BACK. THIS REVIEWER ONLY HAS THE ONE BOOK |
| | WHICH WAS RETAINED BY THIS OFFICE. |
| | WHEN SUBMITTING BOOKS/SPECS, PLEASE BE SURE TO HIGH |
| | LIGHT AND COORDINATE WITH THE PLANS SUBMITTED FOR THE |
| | EQUIPMENT AND DEVICES BEING INSTALLED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS SHALL INDICATE THE ACTUAL PANEL BEING |
| | USED FOR LIGHTING CONTROLS. PLEASE SEE THERE ARE |
| | SEVERAL PANELS INDICATE IN THE MANUFACTURE SPECS/CUT |
| | SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO BE |
| | HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED TO |
| | PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING |
| | CONTROL PANEL. (LCP) |
| | ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS |
| | IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE |
| | SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK, |
| | HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON |
| | CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED |
| | ON EACH LCP. |
| | |
| | 8) NOTE: OK/NO, PLEASE KNOW MOST OF THE SYSTEM IS |
| | UNDERSTOOD HOWEVER THERE ARE AREAS IN WHICH A SWITCH |
| | TYPE DEVICE (SENTRY) IS BEING INSTALLED ALONG WITH AN |
| | OC (OCCUPANCY SENSOR) TYPE DEVICE. THE DETAIL WAS |
| | LOCATED ON 7-2.0 HOWEVER THIS WOULD STILL PERMIT THE |
| | TURNING OFF LIGHTS IN AN UNWANTED FASHION.PLEASE SEE |
| | EGRESS STAIRS FOR MEZZANINE AREA WHICH COULD BE TURNED |
| | OFF, YET OF AN OCCUPANT WAS STILL LOCATED ON THE UPPER |
| | LEVEL THEY WOULD HAVE NO CONTROL OF LIGHTING AS SHOWN. |
| | |
| | PLEASE SEE ROOF TOP AREA ON E1-6.1 WHICH LOCATES A |
| | SWITCH ON WHAT APPEARS TO BE AN OUTSIDE WALL TO CONTROL |
| | LIGHTING IN ELEVATOR EQUIPMENT ROOM AS WELL AS OTHER |
| | LIGHTING AS REQUIRED FOR LIFE SAFETY. |
| | PLEASE SEE OTHER AREAS WHICH CONTAIN BOTH. |
| | PLEASE ALSO SEE AS NO SPECS WERE SUBMITTED BACK, COULD |
| | NOT LOCATE A LETTER FROM THE LUTRON MANUFACTURE WHICH |
| | PERMITS THE USE OF THE SENTRY SWITCH IN THEIR SYSTEM. |
| | PLEASE SEE AREAS OF MEETINGS ROOMS AND COMMISSION |
| | CHAMBERS AREA WHICH DO NOT PROVIDE ENOUGH INFORMATION |
| | FOR HOW THESE WILL BE CONTROLLED. PLEASE SEE THAT THE |
| | NOTE ON THE PLANS FOR THIS TO BE PROVIDED BY LIGHTING |
| | TECHNICAL NEEDS TO BE REPLACED WITH ACTUAL DETAILS ON |
| | HOW THESE WILL BE ADDRESSED TO COMPLY WITH CHAPTER 13 |
| | AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF SYSTEM |
| | BEING PROPOSED AND CONTROLS OF SAID SYSTEM. PLANS CALL |
| | FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT OF NORMAL |
| | BUSINESS HOURS AND THIS WILL TURN OFF ANY AND ALL |
| | DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO OVER |
| | RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE |
| | CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS |
| | BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF |
| | THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL |
| | CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE |
| | SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN |
| | OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS. |
| | (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE |
| | LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR |
| | POLICE, AND OTHER AREAS. |
| | PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS |
| | WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE |
| | ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL |
| | ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS |
| | WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS |
| | SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET |
| | BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE |
| | "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES |
| | HAVE PASSED. |
| | PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE |
| | ARE FAR TOO NUMEROUS ROOMS TO LIST. |
| | PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO |
| | INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL |
| | ON THE LIGHTING CONTROL RISER HOW THESE WILL BE |
| | CONNECTED OR TIED IN. |
| | PLEASE SEE BATHROOMS ETC. |
| | PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS |
| | IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL |
| | NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE |
| | KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS |
| | WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO |
| | OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE |
| | WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE |
| | LUTRON GRAFIK PANEL. |
| | 110.3, 90.7 NEC. |
| | |
| | 9) NOTE: OK/NO, PLEASE SEE COORDINATION OF NUMERICAL |
| | IDENTIFICATION SEEMS TO BE BETTER; HOWEVER PLEASE SEE |
| | SEVERAL AREAS AND ROOM HAVE THEIR DESIGNATION COVERED |
| | BY A DEVICE, FIXTURE OR SOME OTHER ITEM. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL |
| | DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED |
| | ON PLANS. PLEASE SEE GARAGE PLANS. |
| | PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE |
| | HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT |
| | BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE |
| | FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR |
| | VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO |
| | THE OVER LAY OF THE NUMERICAL DESIGNATION. |
| | PLEASE COORDINATE. A1-116-2-1.610 ETC |
| | FBC ADMIN SECTION 106.1.2, 106.1.3 |
| | |
| | 10) NOTE: OK, HOWEVER PLEASE KNOW BASED ON FURTHER |
| | COMMENTS, ADJUSTMENTS IN FIXTURE TYPES AND DESIGNATIONS |
| | WILL BE NEEDED. |
| | |
| | 11) NOTE:NO, PLEASE SEE THERE ARE SEVERAL ROOMS WHICH |
| | STILL DO NOT INDICATE A BATTERY BACK UP FIXTURE OF SOME |
| | SORT WHICH WILL BE REQUIRED. |
| | FIRE PUMP ROOMS, MAIN ELECTRICAL ROOM, MAIN MECHANICAL |
| | ROOM, THE MAIN MECHANICAL ROOM ELECTRICAL ROOM, |
| | ELEVATOR EQUIPMENT ROOM. ETC. |
| | PLEASE ALSO SEE NEW NOTES FOR ROOF TOP/ELEVATOR |
| | EQUIPMENT ROOM AND OUTSIDE AREA TO STAIR TWO. PLEASE |
| | ALSO SEE GARAGE STAIR TOWERS WILL ALSO BE REQUIRED TO |
| | CONTAIN MINIMUM BATTERY BACK UP FOR FIXTURES AS OTHER |
| | STAIR TOWERS IN MAIN BUILDING ARE DONE. |
| | ** PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT BATTERY BACK UP FIXTURES OF SOME TYPE |
| | WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS. SOME ARE |
| | SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN ELECTRICAL |
| | ROOM, THE FIRE COMMAND CENTER, BOTH FIRE PUMP ROOMS, |
| | ELEVATOR EQUIPMENT ROOM, AND AT THE LOCATION OF THE |
| | ROOF TOP GENERATOR WILL ALL REQUIRE THIS. PLEASE SEE |
| | THAT ALL STAIR TOWERS AND EGRESS PATHS SHALL ALSO |
| | INCLUDE SOME SORT OF BATTERY BACK UP FIXTURE. THERE ARE |
| | MANY LOCATIONS WHICH INCLUDE THIS; HOWEVER AS SOME OF |
| | THE FIXTURE INFORMATION IS NOT CLEAR AT THIS TIME THIS |
| | CAN NOT BE VERIFIED. THIS BUILDING IS EXPECTED TO BE |
| | OCCUPIED IN THE TIME OF POWER OUTAGES AND IN THE EVENT |
| | OF THE TRIPPING OF A SINGLE MEANS OF OVER CURRENT |
| | PROTECTION (EMSB1) OR GEN MAIN, THIS WILL PLACE MANY |
| | AREAS IN COMPLETE DARKNESS WHICH IS NOT PERMITTED. NEC |
| | 700.12E, 700.16, LS 101 7.9. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: NO, PLEASE SEE COMMENTS WITH RESPECT TO STAIR |
| | TOWERS IN GARAGE AND OTHER ROOMS WITH THESE |
| | DESIGNATIONS WHICH MAY BE CHANGED OR ADJUSTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS TO BE |
| | BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS |
| | PROVIDED. PLEASE SEE FIXTURES, Z,ETC. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: NO, PLEASE SEE RESPONSE LETTER MENTIONS THIS |
| | IS TO BE DONE BY THE STRUCTURAL ENGINEER/DESIGNER OF |
| | RECORD HOWEVER COULD NOT LOCATED ANY DETAIL FOR THIS ON |
| | THE S SHEETS. PLEASE SEE THE SAME DETAIL FOR GROUND |
| | LEVEL POLES IS BEING USED FOR ROOF TOP MOUNTING? PLEASE |
| | SEE NEW NOTES WITH RESPECT TO THE S SHEETS AND TITLE |
| | BLOCKS MISSING AND OTHER NOT CONTAIN ANY CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS REQUIRED. SEE NEW ELECTRICAL |
| | NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE |
| | LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE |
| | ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL |
| | BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE |
| | DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE |
| | REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH |
| | (3SEC GUST) 120MPH SUSTAINED. |
| | THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE |
| | BUILDING PLAN REVIEWER. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE: OK. |
| | |
| | 19) NOTE:NO, THIS IS STILL UNCLEAR HOW THE SHORTER |
| | LENGTHS OF CONDUCTORS OUT TO FIXTURES ACTUALLY CONTAIN |
| | A HIGHER VOLTAGE DROP. |
| | PLEASE SEE OTHER COMMENTS ON THE FOLLOWING NOTE #20. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME CIRCUIT AS |
| | NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE SA |
| | INDICATE #8'S, AND YET SB WHICH CONTAIN A LONGER RUN |
| | AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE |
| | SEE FBC 13-413.1.ABC.1.2. |
| | |
| | 20) NOTE:NO, COULD NOT LOCATE ANY FOR BRANCH |
| | CIRCUITING. ONLY LOCATED THE FEEDERS ON RISER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER AND BRANCH |
| | CIRCUIT. |
| | 13-413.1ABC.1. |
| | IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD % |
| | IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE |
| | THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC |
| | 106.1.2. |
| | |
| | 21) NOTE: NO, SAME NOTE. PLEASE SEE THE FS SHEETS STILL |
| | INDICATE ELECTRICAL FIRE PUMPS ALONG WITH DIFFERENT |
| | SIZES OF EQUIPMENT THAN THAT SUBMITTED IN THE |
| | ELECTRICAL SUBMITTAL BOOKS. PLEASE SEE DIFFERENT |
| | MANUFACTURE, ETC. |
| | PLEASE SEE THAT BASED ON THE COMMENTARY PROVIDED FOR |
| | FUEL USAGE, THE FUEL FOR ONE APPEARS TO BE OK, HOWEVER |
| | THE OTHER (110HP) DOES NOT MEET THE MINIMUM LEVEL OF |
| | FUEL REQUIRED. PLEASE SEE AS TWO DIFFERENT SIZE PUMPS |
| | ARE SUBMITTED, I AM UNABLE TO REVIEW WHICH THE ONE FOR |
| | INSTALLATION AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE 100% FIRE SPRINKLER PLANS SUBMITTED DO |
| | NOT CORRELATE WITH THE FA OR ELECTRICAL PLANS SUBMITTED |
| | WITH RESPECT TO THE FIRE PUMPS. PLEASE SEE THE FS |
| | SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/ DIESEL AND |
| | DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND THE |
| | MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY INDICATE |
| | DIESEL. |
| | PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE |
| | SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF |
| | ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN |
| | EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE |
| | BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER |
| | LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES |
| | REQUIRED. |
| | PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE |
| | CODE: |
| | 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT |
| | TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 |
| | PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE |
| | SUPPLY REQUIRED FOR OTHER DEMANDS. |
| | PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME |
| | AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER |
| | HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE |
| | THE FOLLOWING THE CODE. |
| | 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT |
| | LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5 |
| | PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR |
| | SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3 |
| | THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT |
| | TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8 |
| | HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS |
| | UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG |
| | WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE: OK/NO, PLEASE SEE AS SOME AREAS ARE NOT CLEAR |
| | UNABLE TO VERIFY ANY GFI NOTATION. PLEASE SEE SOME ARE |
| | SHOWN WITH THE GFI IDENTIFICATION AND IF THE SYMBOLS |
| | WERE A LITTLE MORE CLEAR THE SYMBOL LEGEND ON E0.10 MAY |
| | BE IF USE. |
| | PLEASE ALSO SEE SHEET E1.-1.2 WHICH SHOULD BE A SECTION |
| | OF THE BUILDING WHICH WOULD BE LARGER IN SIZE. IT SEEMS |
| | SOMETHING WITH THE PRINTING OF SHEET CAUSED SHEET TO BE |
| | MUCH SMALLER. PLEASE SEE KITCHEN AREAS WHICH ARE |
| | LOCATED ON THIS SHEET COULD NOT BE VERIFIED AT THIS |
| | TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN KITCHENS |
| | IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS WOULD BE |
| | REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN ON |
| | PLANS. |
| | |
| | 24) NOTE: OK. |
| | |
| | 25) NOTE: NO, PLEASE SEE PHOTO-METRICS ARE CONFUSING. |
| | PLEASE SEE THE GARAGE STAIRS SEEM TO NOW BE SHOWN, |
| | HOWEVER THERE IS NO SPECIFIED UNDER NORMAL OR UNDER |
| | EMERGENCY. PLEASE SEE DESIGNATIONS ON ALL OTHER STAIRS |
| | AND LABELING OF AREAS DOES NOT CORRELATE WITH ACTUAL |
| | PLANS AND STAIR TOWERS AS SHOWN. PLEASE KNOW THIS |
| | COMMENT IS NOT JUST FOR GARAGE STAIRS AS PREVIOUS |
| | COMMENT WAS TO ADDRESS ALL PHOTO-METRICS. PLEASE SEE |
| | MISSING STAIR 13, MEZZ STAIRS, PLEASE SEE OTHER STAIR |
| | DESIGNATIONS NOT LABELED ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING THE PHOTO-METRICS FOR THE GARAGE |
| | STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS SUBMITTED |
| | ARE A LITTLE CONFUSING. PLEASE PREVIOUS COMMENTS ONLY |
| | REQUESTED EGRESS PATHS OF LEVELS SURFACES/ CORRIDORS |
| | AND EGRESS PATHS THAT OF THE STAIR TOWERS. PLEASE SEE |
| | THERE MUCH INFORMATION SUBMITTED GIVING FIXTURE |
| | DESIGNATIONS AND ROOM BY ROOM LEVELS? PLEASE PROVIDE |
| | THE EGRESS PATHS INFORMATION INDICATING THE CLEAR |
| | NORMAL AND EMERGENCY LEVELS AS NEEDED AND REQUIRED BY |
| | CODE. |
| | PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY |
| | AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS |
| | SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE |
| | INFORMATION AS NEEDED. |
| | PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK, |
| | EMERGENCY/ NORMAL? |
| | |
| | 26) NOTE: OK. |
| | |
| | 27) NOTE: NO, PLEASE SEE SOME ARE STILL SHOWING THIS |
| | DESIGNATION. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS "ON" NEXT |
| | TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS IS UNCLEAR |
| | AT THIS TIME WHAT IS MEANT BY THIS. |
| | FBC 106.1.2 ADMIN SECTION |
| | |
| | 28) NOTE: OK. |
| | |
| | 29) NOTE: OK. |
| | |
| | 30) NOTE: OK/NO, PLEASE SEE ROOM LAYOUT DESIGNATION ON |
| | SHEET E1-1.3 INDICATES SHEET E4-1.0, WHEN IT SHOULD BE |
| | E- 1.1 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING THE ELECTRICAL ROOM FOR 1HMGB AND |
| | 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL ROOMS. PLEASE |
| | PROVIDE. 106.1.2, |
| | NEC 110.26 |
| | |
| | 31) NOTE: NO/OK, PLEASE SEE THE DOOR SWINGS SEEM TO BE |
| | OK, HOWEVER PLEASE SEE NO NOTE FOR PANIC HARDWARE AS |
| | REQUIRED COULD BE LOCATED ON PLANS. THIS WILL BE |
| | REQUIRED FOR MAIN ELECTRICAL ROOM AND MAIN ELECTRICAL |
| | EQUIPMENT FOR MECHANICAL MAIN ELECTRICAL EQUIPMENT |
| | ROOMS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MAIN ELECTRICAL ROOM AND THE MISSING |
| | ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS STILL |
| | INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT |
| | PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH |
| | RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS |
| | REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM |
| | NOTED ON NOTE #30). |
| | PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE |
| | REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE |
| | GO OVER ALL PLANS AND DOORS. |
| | |
| | 32) NOTE: NO, PLEASE SEE SEVERAL OF THESE UNITS ARE |
| | BEING SHOWN ON PLANS AT JANITOR CLOSET LOCATIONS, |
| | HOWEVER NOT ALL OF THESE ROOMS CONTAIN THESE. PLEASE |
| | ALSO SEE SEVERAL KITENETTE AREA WHICH ALSO INCLUDES |
| | THESE HOWEVER MANY DO NOT? IN EITHER CASE PLEASE SEE NO |
| | SPECS WERE SUBMITTED AND NO DISCONNECTING MEANS FOR ALL |
| | UNITS COULD BE LOCATED ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR AL |
| | THE TANK-LESS WATER HEATER UNITS. THESE MAY ALSO BE |
| | LABELED AS INSTA-HOTS. PLEASE SEE MISSING DISCONNECTS |
| | AS REQUIRED ON THESE UNITS. THESE COULD NOT BE LOCATED |
| | ON PLANS. |
| | PLEASE SEE SIZING OF THE OVER CURRENT DEVICES, |
| | DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE |
| | SEE 422.31, 110.3, AND 90.7. |
| | |
| | 33) NOTE:NO, SAME NOTE. PLEASE VERIFY ALL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON PLANS ARE |
| | MISSING THE REQUIRED CIRCUITING. CAN NOT REVIEW FOR |
| | COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC AT THIS |
| | TIME. |
| | PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2 |
| | |
| | 34) NOTE: OK. |
| | |
| | 35) NOTE: OK. |
| | |
| | 36) NOTE: OK |
| | |
| | 37) NOTE: OK. |
| | |
| | 38) NOTE: OK. |
| | |
| | 39) NOTE: OK. |
| | |
| | 40) NOTE: OK. |
| | |
| | 41) NOTE: OK, HOWEVER SEE NOTE FOR CORRELATION OF ROOM |
| | A5.107 |
| | |
| | 42) NOTE: OK. |
| | |
| | 43) NOTE: NO? SAME AS SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL PLANS |
| | E-1.1.4, PLEASE CLARIFY |
| | 106.1.2 FBC ADMIN SECTION. |
| | |
| | 44) NOTE: OK. |
| | |
| | 45) NOTE: OK. |
| | |
| | 45) NOTE: NO/OK, PLEASE SEE WALL AS LOCATED, HOWEVER |
| | SEPARATE LIGHTING CONTROLS FOR SEPARATE SPACES AS |
| | REQUIRED COULD NOT BE LOCATED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE WHAT APPEARS TO BE MISSING WALLS, DOORS |
| | SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE SHOW |
| | AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT VERIFIED FOR |
| | CONTROL OF LIGHTING. LIGHTING OF SOME TYPE INCLUDING |
| | EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN SPACE, EVEN |
| | IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101 7.8, 7.9 AND |
| | POSSIBLE COMMENTS FROM FIRE MARSHAL?S OFFICE. |
| | 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3 |
| | |
| | 46) NOTE: OK. |
| | |
| | 47) NOTE: NO/OK, SOME OF THESE WERE DONE BY THE CHANGES |
| | IN THE UNDER GROUND TO OTHER SECTIONS OF BUILDING, |
| | HOWEVER NOT DETAIL FOR THE ENCASED FEEDERS FROM |
| | GENERATOR COULD BE LOCATED. PLANS MENTIONS TO SEE |
| | ARCHITECTURAL PLANS; HOWEVER NO INFORMATION FOR WHICH |
| | SHEET OR DETAIL THIS IS COULD BE FOUND. PLEASE PROVIDE |
| | THE DETAIL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL ELECTRICAL |
| | CONDUITS BEING RUN FROM GARAGE TO THE MAIN BUILDING. |
| | THIS BUILDING IS BEING CONSIDERED "ATTACHED" AND ONE " |
| | BUILDING" BY DEFINITION, HOWEVER DUE THE UNDERSTANDING |
| | OF MANY OF THE CONDUITS ARE NOW BEING INSTALLED IN THE |
| | SLAB OR UNDER GROUND AND THE AMOUNT OF OTHER CONDUITS, |
| | PIPING, BEING INSTALLED IN THIS SAME AREA, IT IS OF |
| | CONCERN FOR THE SPACE REQUIREMENTS FOR BUNDLING OF |
| | CONDUITS, DE-RATING OF CONDUCTOR AMPACITIES. ETC. (THIS |
| | CAN BE A DETAIL LIKE A DUCT-BANK DETAIL) |
| | FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15, |
| | 310.16, 300.17 ETC. |
| | THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED. |
| | PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS |
| | OF EMERGENCY FEEDERS ETC. |
| | |
| | 48) NOTE: OK, HOWEVER SEE NEW NOTES DUE TOP HAND DRAWN |
| | CHANGES MADE TO PLANS. |
| | |
| | 49) NOTE: NO, PLEASE SEE THE RATING OF THIS ROOM IS |
| | STILL REQUIRED. THIS COMMENT WILL BE IN REVIEWS FROM |
| | MULTIPLE REVIEWERS AND AS THIS WILL CHANGE THE BACK |
| | GROUND OF WALL DETAIL PLEASE ADDRESS AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM EQUIPMENT |
| | IS BEING SUBMITTED WITH THIS RECORD SET OF PLANS, |
| | PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER PLANS |
| | THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER EQUIPMENT |
| | ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE PERMIT, |
| | PLANS, AND FEES BASED ON THE EQUIPMENT BEING INSTALLED |
| | IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR THIS ROOM |
| | CAN NOT BE COMPLETED AT THIS TIME. THE REQUIREMENTS FOR |
| | THE CONSTRUCTION OF THIS ROOM IS REQUIRED AT THIS TIME, |
| | INCLUDING THE MINIMUM 1HR RATING, THE FIRE DAMPERS ETC |
| | (IF APPLICABLE) AND THE SHUT DOWN OF AN AND ALL A/C |
| | EQUIPMENT. |
| | NEC 645, NFPA-75 |
| | |
| | 50) NOTE: OK. |
| | |
| | 51) NOTE: OK. |
| | |
| | 52) NOTE: OK. |
| | |
| | 53) NOTE:OK/NO, THIS NOTE WILL REMAIN AS IT IS THIS |
| | REVIEWERS UNDERSTANDING THAT THERE WILL BE COMMENTS |
| | FROM OTHER TRADES WHICH WILL SUBSTANTIALLY AFFECT |
| | BACKGROUNDS AND LAYOUTS OF SAID PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS FOR |
| | ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL |
| | OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100% |
| | PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND |
| | EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR |
| | BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER |
| | TRADES. |
| | REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE |
| | DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES |
| | WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT |
| | BE PERMITTED. |
| | 110.26, 240.24 NEC. |
| | FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR |
| | COMMERCIAL PLANS. |
| | |
| | 54) NOTE:NO, SAME NOTE. PLEASE SEE PLANS IN SEVERAL |
| | LOCATIONS 6-1.0,1-6.3,5-1.1 ETC INDICATE 800KW AND |
| | SUBMITTALS ARE 900KW. |
| | PLEASE ALSO SEE SHEET WHICH STILL INDICATES ONLY 5 |
| | GALLON SPILL CONTAINMENT. THIS MAY BE PART OF THE FIRE |
| | OR MECHANICAL REVIEW NOTES, IF NOT PLEASE SEE THIS |
| | NEEDS TO BE VERIFIED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE THE PLANS WITH THE MANUFACTURE |
| | SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS BEING |
| | SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS SHOWN ON |
| | PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND THE FUEL |
| | LINE SUPPLY FOR THE PROPOSED NATURAL GAS LINE. 90.7, |
| | 110.3, |
| | FBC 106.1.2 |
| | |
| | 55) NOTE: OK. |
| | |
| | 56) NOTE: OK. |
| | |
| | 57) NOTE:OK/NO, PLEASE SEE PREVIOUS COMMENT WITH |
| | RESPECT TO HOW THIS WILL ACTUALLY BE DESIGNED AND |
| | INSTALLED. THIS COMMENT WILL REMAIN AT THIS TIME AS A |
| | REMINDER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS AND MANY |
| | DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER COMMENTS |
| | FOR TYPE OF DEVICES WHICH WILL BE REQUIRED. |
| | 13-415.1.ABC.1.2 |
| | |
| | 58) NOTE: NO, PLEASE SEE MOST WERE DONE, HOWEVER PLEASE |
| | SEE 2-2.2, 2-3.1,2-4.2 AND ANY OTHER LARGER BATHROOMS |
| | OTHER THAN A SINGLE POINT OF USE OCCUPIED ROOM. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW SOME SORT OF BATTERY BACK UP FIXTURE WILL |
| | BE REQUIRED IN THE LARGER BATHROOMS (ROOM OTHER THAN |
| | SINGLE POINT OF USE). |
| | PLEASE SEE LS 101 7.8., 7.9 |
| | THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL |
| | BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S |
| | OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS |
| | REFLECT. |
| | |
| | 59) NOTE: OK. |
| | |
| | 60) NOTE: OK. |
| | |
| | 61) NOTE: NO, PLEASE SEE RESPONSE MENTIONS MINIMUM |
| | LIGHTING REQUIRED FOR EGRESS, HOWEVER PLEASE KNOW THE |
| | AREA OF THE LOBBY AFTER HOURS WOULD REQUIRE OVER RIDE |
| | FOR NORMAL LIGHTING. ONLY WOULD THEY NEED THESE |
| | FIXTURES TO BE BATTERY BACK UP FOR AN EMERGENCY. THIS |
| | WAS DISCUSSED WITH THE DESIGNER, HOWEVER THE NUMBER OF |
| | FIXTURES EXCEED ANY REASONABLE AMOUNT PERMITTED TO BE |
| | LEFT ON FOR THE EXCEPTIONS AS PERMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS WHICH ARE |
| | SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A PERMANENT |
| | ON SCENARIO; HOWEVER THE NUMBERS OF FIXTURES BEING |
| | PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER WHAT IS |
| | BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS CAN BE |
| | GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE THERE |
| | ARE 10-20PLUS LIGHTS BEING LEFT ON. |
| | THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE |
| | SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE |
| | SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA. |
| | |
| | 62) NOTE:NO/OK, PROJECT MANUALS ARE TO BE REVIEWED |
| | FOR ALL OF THESE ITEMS AND DOCUMENTATION WILL BE |
| | REQUIRED BEFORE FINAL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND FLORIDA |
| | FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER REQUIREMENTS |
| | FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE LOCATED. |
| | PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE |
| | GALVANIZED STEEL OR COPPER. |
| | PLEASE KNOW AS PART OF THE COMPLETED TESTING AND |
| | ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR |
| | TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO |
| | THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1 |
| | ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND |
| | RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL |
| | RUNNING TEMPERATURE. |
| | |
| | 63) NOTE:NO, RESPONSE MENTIONS INFORMATION GIVEN TO |
| | ARCHITECT AND STRUCTURAL ENGINNER WHICH IS OK, HOWEVER |
| | COULD NOT LOCATE ANY INFORMATION OR DETAIL FOR THIS. |
| | THIS UNIT AND ITS SIZE IS BEING PLACED ON THE ROOF OF |
| | THE GARAGE AND IT IS OF THE UTMOST IMPORTANCE THAT THE |
| | INFORMATION IS PROVIDED A THIS TIME AS IT MAY AFFECT |
| | PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NFPA-110 CHAPTER 7 FOR THE INSTALLATION OF |
| | THE GENERATOR. PLEASE SEE 7.4 AND 7.5, PROVIDE DETAIL |
| | FOR MOUNTING OF UNIT TO ALLEVIATE ANY INTEGRITY |
| | INTERFERENCE OF THE STRUCTURE. |
| | |
| | 64) NOTE: NO, PLEASE SEE THE SAME SPECS WHICH CONTAIN |
| | HAND WRITTEN INFORMATION WAS SUBMITTED BACK FOR REVIEW. |
| | PLEASE KNOW, THIS SYSTEM AS SUBMITTED IS NOT ACCEPTABLE |
| | TO THIS AHJ WITHOUT THE FAIL SAFE OPERATION TO |
| | COMPLETELY PREVENT INADVERTENT SIMULTANEOUS OPERATION. |
| | PLEASE KNOW THERE ARE NUMEROUS OF THE TYPES OF SYSTEMS |
| | ON THE MARKET WHICH WILL PERMIT BOTH SIDE BEING ON AT |
| | THE SAME TIME. PLEASE KNOW AS PER KNOWLEDGE OF THIS |
| | REVIEWER MR. MARK ODE FROM UL WAS IN DISCUSSION WITH |
| | SAID COMPANY TO START WITH THE PROCEEDINGS TO HAVE |
| | THEIR EQUIPMENT LISTED AS TRANSFER EQUIPMENT PER UL |
| | 1081. PLEASE KNOW AT THIS TIME, EITHER PROVIDE THE |
| | NEEDED INFORMATION OR CHANGE EQUIPMENT TO AN ACCEPT |
| | UNIT WHICH IS LISTED BY A NRTL. (NATIONALLY RECOGNIZED |
| | TESTING LABORATORY). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE PROPOSED MTS. |
| | THE "KIRK KEY" AS SHOWN AND HAND WRITTEN ON SPECS IS |
| | NOT ACCEPTED AT THIS TIME. THERE ARE MANY OF THESE |
| | SYSTEMS ON THE MARKET WHICH WILL PERMIT THE POWER FROM |
| | TWO SOURCES AT ONCE WHICH IS STRICTLY PROHIBITED. |
| | PLEASE SEE 700.6, 701.7, 110.3, AND 90.7 CAN NOT VERIFY |
| | AT THIS TIME. PLEASE ALSO SEE THE FOLLOWING COMMENT. |
| | |
| | 65) NOTE: NO/OK, PLEASE SEE SPECS SUBMITTED INDICATE |
| | 4-POLE UNITS, HOWEVER EACH ATS ON RISER WHEN SUBMITTED |
| | FOR THE 90% REVIEW CONTAINED DESIGNATION NEXT TO EACH |
| | UNIT TO BE 4-POLE. PLEASE PLACE THIS MEANS OF |
| | IDENTIFICATION/DESIGNATION ON RISER AT THIS TIME TO |
| | AVOID ANY CONFUSION OF WHAT TYPE OF UNITS ARE TO BE |
| | INSTALLED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER AND PLANS WERE REVISED FROM THE 50% |
| | AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE UNITS. |
| | PLEASE SEE ALTHOUGH GF PROTECTION IS NOT REQUIRED ON |
| | THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM AND LEGALLY |
| | REQUIRED SYSTEMS, PROPER GROUND FAULT SENSING IS |
| | REQUIRED. PLEASE KNOW DOCUMENTATION FROM MORE THAN ONE |
| | MANUFACTURE WAS SENT TO THE ENGINEER PRIOR TO THE |
| | REVIEW WHEN THE PLANS WERE SUBMITTED ON THE 7TH OF NOV. |
| | PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL |
| | CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING |
| | CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND |
| | THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO" |
| | WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED |
| | BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, |
| | SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT |
| | SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE |
| | SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND |
| | FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE |
| | DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND |
| | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT |
| | WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE |
| | MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT |
| | DISCONNECT THE ARCING FAULT FROM THE GENERATOR. |
| | COORDINATION IS THUS LOST." |
| | PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL |
| | MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED. |
| | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE |
| | REQUIRED TO BE REVISED. |
| | PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH |
| | WOULD NOT BE LARGE ENOUGH. |
| | PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95, |
| | 700.7D, 700.26 |
| | PLEASE SEE THE MTS. |
| | |
| | 66) NOTE: OK, HOWEVER PLEASE SEE SOME OF THESE ARE |
| | BEING SHOWN ATTACHED DIRECTLY TO CIRCUITS WHICH SEEMED |
| | TO BE CONTROLLED BY LIGHTING CONTROL SYSTEM OR DEVICES. |
| | THE NOTES ON PLANS MENTION TO BE SURE TO CONNECT AHEAD |
| | OF ANY CONTROL OR SWITCHING DEVICES HOWEVER PLEASE |
| | VERIFY THIS ON THE PLANS AT THIS TIME AS SHOWN. PLEASE |
| | SEE THERE ARE STILL SOME EXIT LIGHT FIXTURES ON PLANS |
| | WHICH STILL DO NOT SHOW ANY CONNECTION TO LOCAL |
| | CIRCUITS E2-3.2,E2-4.2 |
| | |
| | PLEASE SEE THERE ARE MANY EXIT/EMERGENCY LIGHTS WHICH |
| | DO NOT SHOW ANY CONNECTION TO ANY LOCAL CIRCUIT IN |
| | ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN THIS WAY, |
| | HOWEVER NOT ALL. PLEASE GO THROUGH PLANS. PLEASE SEE |
| | 700.12E WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 67) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH SEEM TO BE |
| | SHOWING LIGHTING OF SOME KIND ON GARAGE PLANS? PLEASE |
| | ALSO SEE E2-4.0 |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 68) NOTE: NO, PLEASE SEE THE LOCATION AS SHOWN WOULD |
| | NOT BE AN ACCEPTABLE LOCATION. PLEASE THE RUNNING OF |
| | CABLES IN THE EGRESS PATH IS NOT PERMITTED IN FRONT OF |
| | DOOR WAYS AND ANY OTHER EGRESS PATHS. PERHAPS CONDUITS |
| | TO A J-BOX OF SOME TYPE TO THE OUTSIDE WALL ON THE |
| | NORTH SIDE OF BUILDING. PLEASE KNOW TRIPPING HAZARDS |
| | UNDER THE REQUIREMENTS IN THE CODE FOR TEMPORARY |
| | INSTALLATIONS IS STILL NOT PERMITTED. PLEASE SECTIONS |
| | AS PREVIOUSLY GIVEN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO THE MTS |
| | WHICH IS TO PROVIDE FUTURE PROVISIONS FOR POSSIBLE |
| | PORTABLE GENERATOR TO RUN THE EMERGENCY SYSTEMS, PLEASE |
| | KNOW A DETAIL TO A LOCATION AND HOW THIS CONNECTION |
| | WILL BE MADE IS REQUIRED.THE RUNNING OF CORDS, |
| | CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL THROUGH THE |
| | ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR ANY |
| | LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT SECURING |
| | LIVE PARTS ETC. |
| | PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL |
| | BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF |
| | BUILDING ETC. |
| | 110.26, 110.27, NEC 527. |
| | |
| | 69) NOTE: OK. |
| | |
| | 70) NOTE: OK. |
| | |
| | 71) NOTE: OK, PLEASE KNOW ALL LOW VOLTAGE WILL NOT BE |
| | INCLUDED IN THIS PERMIT. NOTE WILL REMAIN ONLY AS |
| | INFORMATION AS TO WHAT WILL BE REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW IF IT IS THE INTENT TO UTILIZE THESE PLANS |
| | FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS OF PHONE, |
| | DATE DROP ETC, PLEASE COMPLETE PLANS AS SUBMITTED |
| | SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE MANY AREAS |
| | WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE REQUIRED OR |
| | INSTALLED, HOWEVER THESE LOCATIONS ARE NOT BEING SHOWN |
| | AT THIS TIME. |
| | IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS |
| | SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE |
| | PERMIT PLANS AND FEES. |
| | |
| | 72) NOTE: OK. |
| | |
| | 73) NOTE:OK/NO, PLEASE SEE PREVIOUS NOTE #47, WHERE |
| | THE DETAIL FOR THE FEEDERS IN GARAGE WAS NOT PROVIDED. |
| | THE DETAIL FOR UNDERGROUND IS OK. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 700.9D FOR THE FEEDERS FROM THE GENERATOR TO |
| | THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS WHICH MAY BE |
| | CONSIDERED INSIDE THE BUILDING. PLEASE SEE THE CODE AS |
| | THERE ARE WAYS TO MEET THE INSTALLATION OF THESE |
| | FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL BE |
| | USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF CONCRETE, |
| | FULLY SPRINKLED ETC) |
| | PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS |
| | OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS. |
| | THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D |
| | FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING |
| | THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR |
| | ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005 |
| | NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE |
| | FURTHER EXPLANATION IS PROVIDED. |
| | |
| | 74) NOTE: OK. |
| | |
| | 75) NOTE: OK.. |
| | |
| | 76) NOTE: NO, COULD NOT LOCATE. RESPONSE MENTIONS TO |
| | SEE SHEETS; HOWEVER THIS WAS REQUESTED FOR RISER TO |
| | SHOW THIS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON THE |
| | GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE THE |
| | GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER |
| | PLEASE SEE E5-2.0. |
| | 250.50, 250.58 |
| | |
| | 77) NOTE: NO, PLEASE SEE RESPONSE MENTIONS ALL |
| | TERMINATE IN OCP. YES, THIS IS TRUE, HOWEVER AS STATED |
| | IN PREVIOUS REVIEW PER 240.21C THE OCP SHALL LIMIT THE |
| | LOAD ON CONDUCTORS. |
| | PLEASE SEE E5-1.0 WHICH SHOWS A 45KVA TRANSFORMER, WHEN |
| | E6-1.0 SHOWS 1/0'S FOR THE TYPICAL 45 KVA TRANSFORMER |
| | ON THE SECONDARY SIDE, THIS WOULD MEAN THE OCP WOULD BE |
| | LIMITED TO 150A?S. PLEASE SEE 6-1.0 FOR 1LD2 WHICH |
| | INDICATES 225A OCP AS THE SECONDARY MCB. PLEASE SEE |
| | 6-7.0 1HD WHICH SHOWS 1/0'S ON THE SECONDARY SIDE OF |
| | THE FEEDERS. |
| | PLEASE ADJUST. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE SECONDARY |
| | SIDE OF ANY TRANSFORMER SHALL BE SIZED AND TERMINATE IN |
| | OVER-CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE |
| | CONDUCTORS. PLEASE SEE 240.21C, 310.16. PLEASE SEE |
| | 1LD2 |
| | |
| | 78) NOTE: OK. |
| | |
| | 79) NOTE: NO, PLEASE CLARIFY WHERE CONTINUOUS LOADS AND |
| | LARGEST MOTOR LOADS ARE SHOWN AT 125%. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT LOAD CALCULATIONS. PLEASE INDICATE AND |
| | SHOW ALL CONTINUOUS LOADS AND LARGEST MOTOR LOADS AT |
| | 125%. |
| | 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC |
| | |
| | 80) NOTE: OK. |
| | |
| | 81) NOTE:NO, PLEASE KNOW BASED ON THE PREVIOUS NOTES |
| | ABOVE WITH RESPECT TO PHOTO-METRICS, THIS COMMENT WILL |
| | REMAIN DUE TO POSSIBLE CHANGES IN PLANS. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PREVIOUS NOTES WITH RESPECT TO MINIMUM FOOT |
| | CANDLES REQUIRED. PLEASE SEE GARAGE SHALL CONTAIN |
| | EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON SOME |
| | AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR THIS |
| | IS MET. |
| | PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3, |
| | 7.9.2.2 |
| | |
| | 82) NOTE: OK. |
| | |
| | 83) NOTE:NO/OK, PLEASE SEE MOST WERE DONE, HOWEVER |
| | PLEASE SEE ROOM A1.507 WHICH SHOWS 75K ON RISER AND 45K |
| | ON ROOM PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE CORRELATE THE TRANSFORMERS ON THE ELECTRICAL |
| | ROOM LAYOUTS AND THE ELECTRICAL RISER. PLEASE SEE THERE |
| | ARE MANY WHICH ARE SHOWN AS 15KVA ON ONE SHEET AND |
| | 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND 75KAV ON |
| | ANOTHER. PLEASE ALSO SEE RISER. |
| | PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND |
| | IS IN NO WAY ALL POSSIBLE. |
| | 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB, |
| | 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA, |
| | 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC |
| | |
| | 84) NOTE: OK, |
| | |
| | 85) NOTE: NO, PLEASE SEE NOTE NOTES COULD BE LOCATED ON |
| | FA SHEETS, IN FACT SHEETS STILL ONLY NOTE NFPA72 FOR |
| | LEVELS. |
| | PLEASE ADJUST ALL SHEETS AND NOTES ACCORDINGLY AS |
| | PREVIOUSLY REQUESTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 CHAPTER 11 FOR REQUIREMENTS FOR ADA |
| | WITH RESPECT TO HORNS, AND STROBES. THE AUDIBLE LEVELS |
| | SHALL BE PER BOTH FBC CHAPTER 11 AND NFPA-72 AS NOTED, |
| | HOWEVER THE MORE STRINGENT SHALL APPLY. |
| | PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4). |
| | PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS. |
| | PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN |
| | THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE |
| | MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE |
| | ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL |
| | FA SHEETS WHICH ONLY INDICATE NFPA-72. |
| | |
| | |
| | 86) NOTE:OK, PLEASE DO THE SAME. NOTE WILL REMAIN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW A RESPONSE LETTER/NOTES WERE PROVIDED, |
| | HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW FOR CODE |
| | COMPLIANCE, A MORE DETAILED RESPONSE WOULD GREATLY HELP |
| | IN THE REVIEW PROCESS. THIS RESPONSE COULD INDICATE THE |
| | SHEETS/LOCATIONS OF CHANGES, CORRECTIONS OR ANY |
| | COMMENTS RELATED TO AND RESPECT TO THIS REVIEWERS |
| | NOTES. |
| | |
| | ********** NEW NOTES FOR THIS REVIEW************ |
| | |
| | 87) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO |
| | THE ENGINEER OF RECORD SIGNING AND SEALING DOCUMENTS IN |
| | 471.025. PLEASE SEE SHEETS SIGNED OTHER THAN MR. MINDUR |
| | CONTAINS WHAT APPEARS TO BE MORE THAN ONE SIGNATURE FOR |
| | THE SAME ENGINEER. PLEASE KNOW AS STATED BY THE |
| | PLUMBING REVIEWER FOR PLUMBING SHEETS, THE SAME APPLIES |
| | TO FS SHEETS AND OTHER DOCUMENTS SIGNED AND SEALED. |
| | PLEASE KNOW UNTIL LEGAL SIGNATURE VERIFICATION CAN BE |
| | DONE, THE ENERGY CALCULATIONS WHICH ARE SIGNED AND |
| | SEALED ALSO BY OTHER THAN MR. MINDUR CAN NOT BE |
| | ACCEPTED AT THIS TIME. |
| | FAC 61G15-23.002 |
| | PLEASE BE SURE LETTER FOR LEGAL SIGNATURE VERIFICATION |
| | FOR MR. WU IS CORRECTLY NOTARIZED PER FLORIDA STATUTES |
| | 117.05. |
| | |
| | 88) NOTE: PLEASE KNOW AS COMMENTS FROM ELECTRICAL |
| | ENGINEER MENTIONED TO SEE S SHEETS FOR INFORMATION, |
| | UPON REVIEW OF SAID SHEETS THIS REVIEW NOTICE MANY |
| | SHEETS WHICH WERE DATED IN DECEMBER NOT CONTAINING ANY |
| | TITLE BLOCKS FOR THE ENGINEERING FIRM OF RECORD. PLEASE |
| | SEE SOME SHEETS WHICH WERE DATED FROM OCTOBER WHICH DO |
| | CONTAIN THE TITLE BLOCKS FOR FIRM DO NOT CONTAIN THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER |
| | FS 471.023 AND FAC 61G15-23.002. THIS IS REQUIRED FOR S |
| | SHEETS WHETHEROR NOT COMMENT IS MADE BY ANY OTHER |
| | TRADE. |
| | |
| | 89) NOTE: PLEASE SEE ENERGY CALCULATIONS WHICH ARE NOW |
| | SUBMITTED ONLY INDICATE 3 FIXTURES FOR EXTERIOR |
| | LIGHTING? HOW IS THIS POSSIBLE? PLEASE CORRELATE WITH |
| | PLANS AND FIXTURES AS SHOWN ON PLANS. |
| | PLEASE ALSO CORRELATE WITH THE WATTAGES AS SHOWN ON |
| | LIGHTING POWER DENSITIES AND PLANS. |
| | PLEASE CLARIFY ZONES IN ENERGY CALCULATIONS AS SHOWN. |
| | PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 |
| | |
| | 90) NOTE: PLEASE SEE NOTES ON LIGHTING SEQUENCE OF |
| | OPERATION SHEETS. PLEASE SEE NOTE #11 ON E5-3.0 WHICH |
| | MENTIONS PHOTO-CELL FOR CONTROL OF ROOMS? PLEASE SEE |
| | THE SAME ROOMS AND NOTE #3 ON 5-3.1 WHICH MENTIONS |
| | DIFFERENT CONTROLS. |
| | |
| | 91) NOTE: PLEASE SEE WATER COOLERS LOCATIONS OF |
| | RECEPTACLES. PLEASE SEE MANY INDICATE THE RECEPT TO BE |
| | LOCATED AT THE CEILING LEVEL AND MANY INDICATE AT WC |
| | LEVEL. PLEASE EXPLAIN THE INDICATION FOR DEVICE AT |
| | CEILING. PLEASE ALSO SEE AREAS WHERE MORE THAN TWO |
| | WATER COOLERS ARE BEING SHOWN HOWEVER ONLY ONE DUPLEX |
| | RECEPT IS BEING SHOWN. PLEASE ADJUST TO QUAD AND PLEASE |
| | VERIFY LOAD ON THESE UNITS WHICH ARE NOT TO EXCEED |
| | RATING OF DEVICE AND CIRCUIT. THIS WAS NOT COMMENTED ON |
| | THE PREVIOUS REVIEW. |
| | 240.4, 310.16, 210.25, 2210.21B2 ETC. |
| | |
| | 92) NOTE: PLEASE PLACE NOTE ON E0-2.1 FOR SECTIONS OF |
| | 314PART IV , SECTIONS 314.50-314.59 TO BE MET. |
| | NOT ON PREVIOUS REVIEW. |
| | |
| | 93) NOTE: PLEASE SEE UPON REVIEW OF PROJECT MANUAL, |
| | PLEASE SEE COLOR CODING SHALL BE BROWN, PURPLE, YELLOW |
| | FOR 277/480V SYSTEMS. PLEASE SEE THE CODE DOES NOT |
| | PROVIDE COLOR CODING FOR MOST SYSTEMS, HOWEVER ORANGE |
| | AS BEING NOTED FOR THIS IS FOR A HIGH-LEG SYSTEM WHICH |
| | IS NOT WHAT IS BEING INSTALLED. PLEASE KNOW AS PER |
| | LOCAL AMENDMENTS FOR 3 DECADES OR SO UNDER THE 2004 FBC |
| | THE CITY OF WEST PALM BEACH ALONG WITH PALM BEACH |
| | COUNTY HAD THIS COLOR SCENARIO FOR 277/480V SYSTEMS AND |
| | WILL BE REQUIRED TO REMAIN THE SAME FOR ALL OTHER |
| | BUILDING BEING PROPOSED. PLEASE PLACE A NOTE ON RISER |
| | FOR COLOR CODING. |
| | 90.4., FBC ADMIN SECTION 104.6 |
| | |
| | 94) NOTE:PLEASE SEE BUILDING REVIEW NOTES AND |
| | CLARIFY THE TWO PULL BOXES BEING SHOWN ON E0-2.1 WHICH |
| | SEEM TO BE DIRECTLY LOCATED IN THE WALL OR FOOTER. |
| | PLEASE CLARIFY THESE AT THE LOCATIONS AS SHOWN AND |
| | PLEASE ADJUST PLANS AS NEEDED. PLEASE SEE CODE FOR |
| | ACCESSIBILITY. |
| | 110.26 |
| | |
| | 95) NOTE: PLEASE CLARIFY THE FUEL TANK ROOM AS BEING |
| | SHOWN ON THE GARAGE PLANS NEXT TO THE FIRE PUMP ROOM. |
| | PLEASE KNOW IT WAS BEING ASSUMED THIS WAS THE LOCATION |
| | OF THE TANK FOR THE FIRE PUMP; HOWEVER IT HAS COME TO |
| | OUR ATTENTION THAT THIS IS NOT THE CASE. PLEASE PROVIDE |
| | INFORMATION FOR THIS FOR MECHANICAL AND FIRE REVIEW AS |
| | WELL AS ELECTRICAL REVIEW. PLEASE SEE NEC 500. SPECIFIC |
| | SECTIONS CAN NOT BE GIVEN AT THIS TIME, AS THE USE AND |
| | RATING OF ROOM ETC IS NOT KNOWN AT THIS TIME. |
| | FBC ADMIN SECTION 106.1.2 (MORE INFORMATION). NFPA-70, |
| | 72, 30? ETC. |
| | |
| | 96) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOM |
| | DISCONNECTS ARE BEING SHOWN WITH 3-WAY SWITCH NOTATIONS |
| | INSTEAD OF DISCONNECTS OR MOTOR RATED SYMBOL. |
| | NOT ON PREVIOUS REVIEW. |
| | PLEASE ADJUST. 620.51, 620.61, 620.62 ETC |
| | FBC 106.1.2, |
| | |
| | 97) NOTE: PLEASE SEE ANY HAND DRAWN CHANGES WHICH MAY |
| | HAVE BEEN DONE BY THE ENGINEER AFTER PLANS WERE SIGNED, |
| | DATED AND SEALED, SHOULD BE REVISED AT THIS TIME. ONLY |
| | THE ENGINEER OF RECORD MAY MAKE CHANGES TO SAID PLANS |
| | WHICH ARE SIGNED AND SEALED. FS 471.025 PLEASE KNOW AS |
| | PLANS ARE SEALED, MANY OF THE SEALS ARE NOT CLEAR AND |
| | VISIBLE WITH INFORMATION ON SAID SEAL. PLEASE BE SURE |
| | PLANS ARE SEALED TO SEE INFORMATION. FS 471.025 |
| | |
| | |
| | IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION |
| | OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET |
| | SUBMITTED PLEASE BE SURE TO GO OVER ALL. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE |
| | ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-12-25 08:06:40 | 2006-12-25 08:06:40 |
| | IN PROGRESS |
| 2006-12-24 20:14:29 | 2006-12-24 20:14:29 |
| | REVIEW STOPPED. TO CONTINUE ON 12/25 |
| 2006-12-24 18:11:34 | 2006-12-24 18:11:34 |
| | ONE ROLL OF MEP'S IN ELECTRIC FOR REVIEW ALONG WITH ONE |
| | COPY OF RESPONSE LETTERS AND ONE COPY OF SUBMITTIALS |
| | FOR REVIEW. |
| | REVIEW IN PROGRESS. |