| 2008-08-29 13:57:45 | REVISIONS DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | NFPA-101 |
| | |
| | 1. SHTS P1-1.0 & P1-1.0U. REVISION 12A NOT FOUND, NOT |
| | CLOUDED. REVISION NUMBER SHALL BE LEGIBLE ON FLOOR |
| | PLAN. ALL REVISIONS SHALL BE CLOUDED. SEE COMMENT 3 |
| | FROM PREVIOUS REVIEW. SECTION 106.1.3. |
| | |
| | 2. SHTS P1-1.0U, P1-1.0 & P1-1.2. SUBMIT A DETAIL FOR |
| | THE PLANTER ON THE WEST SIDE OF THE COURTYARD. INDICATE |
| | HOW THE STORM WATER AND THE CONDENSATE WILL NOT DRAIN |
| | TO THE FOOTER AREA OF THE OUTSIDE WALL TO COMPLY WITH |
| | SECTION 1503.6. BY HAVING THE PLANTER OPEN AT THE |
| | BOTTOM, THE INTENT OF THE CODE IS NOT BEING MET. |
| | |
| | 3. SHTS P1-4.0, P1-4.2 & P3-7.0. PIPING FROM THE ROOF |
| | DRAIN, (6" RD 1865SF), NOT APPROVED IN THE EXIT |
| | STAIRWELL. NFPA 101 SECTION 7.1.3.2.1(6). |
| | |
| | 4. SHT P1-5.1. REVISION 193 SUBMITTED AND PLANS SIGNED, |
| | SEALED & DATED ON 05-09-08 NOT SHOWN ON REVISION |
| | SUBMITTED ON 08-21-08. ALSO CHANGES TO LATEST REVISION |
| | ARE NOT CLOUDED NOR NUMBERED WITH A REVISION NUMBER. |
| | (HUB DRAINS DELETED). SECTION 106.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |