| 2007-09-02 08:48:58 | BUILDING PLAN REVIEW |
| | PERMIT: 06100574 |
| | ADD: 401 CLEMATIS ST |
| | CONT: CATALFUMO |
| | TEL: (561)307-4746 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION # 11-12REVIEW |
| | ACTION: DENIED |
| | |
| | 1) GARAGE MAIN ELECTRIC ROOM B1.103THE FLOOR IS NOW |
| | DROPPED DOOR B1-103-AIS INDICATED WITH A PAIR OF 3'-0" |
| | OUTSWING DOORS AND A LANDING AND STAIR THAT IS ONLY |
| | 3'-0" WIDE. |
| | THE PLAN DOESN'T INDICATE THE PRESENCE OF A HANDRAIL |
| | SYSTEM OR NOTE AS SUCH. THE PLAN ALSO INDICATES THE (2) |
| | RISERS TO BE 6 7/16" INCHES AND TREAD DEPTH OF 11". |
| | 1003.5.1 |
| | WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING |
| | 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM |
| | TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM) |
| | AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE |
| | READILY APPARENT. |
| | |
| | 2)BOTH THE ELECTRIC ROOM AND MECHANICAL ROOM INDICATE |
| | THE FLOOR SLAB IS NOW RECESSED 6" PLEASE PROVIDE THE |
| | INFORMATION HOW **READILY APPARENT** WILL BE |
| | ACCOMPLISHED IN SECTION 1003.5.1. |
| | |
| | 3) GARAGE MAIN ELECTRIC ROOM B1.103 DOOR B1-103-B IS AN |
| | OUTSWING DOOR WITH AUTOMATIC CLOSER WITH LATCHSEE |
| | A8-0.1 NOTES D & E AND SEE A8-0.2DOOR SCHEDULE. WITH |
| | THE DOOR |
| | HAVING A CLOSER AND LATCH THE LANDING ON THE INTERIOR |
| | OF THE ROOM SHOULD EXTEND A MINIMUM OF 12" SEE |
| | MANEUVERING CLEARENCE AT DOORS FIGURE 25(A) THE LANDING |
| | WOULD NEED TO BE A MINIMUM OF 48" DEEP.11-4.13.6 |
| | MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| | CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | 4) SHEET S1-1.0THE EXTERIOR OF THE MAIN ELECTRIC ROOM |
| | IN THE GARAGE PORTION OF THE PLAN INDICATES A SINGLE |
| | 3'-0" DOORWAY WHERE AS THE ARCHITECTURAL SHEETS |
| | INDICATE A PAIR OF DOORS. |
| | PLEASE CORRELATE PLAN DETAILS.106.1.2*ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 5) ONE SET OF PLANS IS MISSING SHEET A1-GA.1 THERE ARE |
| | (2) A1-GA.3 IN SET. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |