| 2008-07-18 08:54:08 | REVISIONS DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P1-1.0 REVISION 193R SHOWS A 2" CONDENSATE FROM |
| | AHU-1 CONNECTING TO A 1" CONDENSATE LINE THAT SNAKES |
| | OVER TO A PLANTER & DISCHARGES MINIMUM 12" AWAY FROM |
| | THE BUILDING WALL. FITTINGS SHOULD BE USED WHEN |
| | CHANGING DIRECTION ON DRAINAGE PIPE. SECTION 706.1.-- |
| | THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED IN |
| | SIZE IN THE DIRECTION OF FLOW. SECTION 704.2.--MORE |
| | INFORMATION IS REQUIRED. IF THE CONDENSATE WILL BE |
| | DRAINING 24 HOURS, 365 DAYS A YEAR, WHERE WILL THE |
| | CONDENSATE WATER DRAINING INTO THE PLANTER GO? IS THE |
| | PLANTER SEALED OFF FROM THE BUILDING WALL WITH A |
| | FLASHING OR SOME OTHER FORM OF WATER PROOFING?--IF |
| | THE EXCESS WATER REMAINS IN THE PLANTER, WILL THIS |
| | CAUSE ROOT ROT ON THE REQUIRED PLANTS?--ALSO ALL |
| | CHANGES TO THE CONDENSATE SYSTEM SHALL BE REFLECTED ON |
| | THE CONDENSATE RISER DIAGRAM. SECTIONS 106.1.1, 106.1.2 |
| | & 1503.6. |
| | |
| | 2. SHT P1-1.0 REVISIONS 193 & 193RSHOWS THE |
| | CONDENSATE LINE SNAKING TO 1" DC DOWN.FITTINGS SHOULD |
| | BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. |
| | SECTION 706.1. |
| | |
| | 3. SHT P1-1.01 PLANS STAMPED AND ISSUED 2-21-05 SHOW |
| | REVISIONS 1, 2, 4 & 5 IN THE REVISION INDEX. THE NEW |
| | REVISED SHEET SUBMITTED DOES NOT INDICATE REVISION 1 |
| | AND SHOWS REVISIONS 12A & 193R. REVISION 12A IS NOT |
| | CLOUDED AND THE NUMBER IS NOT LEGIBLE IN THE TRIANGLE |
| | WHICH MAY OR MAY NOT BE REVISION 12A. PLEASE CLOUD ALL |
| | REVISIONS TO BE SUBMITTED AND MAKE SURE THE REVISION |
| | NUMBERS IN THE TRIANGLES ARE LEGIBLE. ALSO MAKE SURE |
| | THE REVISION INDEX SHOWS ALL REVISIONS RELATED TO THE |
| | SHEET. SECTIONS 106.1.1, 106.1.2 & 106.1.3. |
| | |
| | 4. SHT P1-1.1 REVISIONS 193 & 193R FITTINGS SHOULD BE |
| | USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. SECTION |
| | 706.1. |
| | |
| | 5. SHT P1-1.1U REVISIONS 1 & 2 ARE NOT SHOWN ON THE |
| | REVISION INDEX AND REVISION 193R SHOWN ON THE FLOOR |
| | PLAN IS NOT SHOWN ON THE REVISION INDEX. PLEASE |
| | CORRELATE ALL REVISIONS AND THE REVISION INDEX. ALSO |
| | ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS SHALL |
| | REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE PLANS |
| | TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD. SECTION |
| | 1106.1.3. |
| | |
| | 6. SHT P1-1.2U REVISION 1 MISSING FROM THE REVISION |
| | INDEX. ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS |
| | SHALL REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE |
| | PLANS TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD. |
| | SECTION 1106.1.3. |
| | |
| | 7. SHT P1-1.2 REVISIONS 11, 12 & 193 SHOWN IN THE |
| | REVISION INDEX ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE |
| | CORRELATE. ALSO CLOUD AND NUMBER ALL REVISIONS |
| | SUBMITTED AFTER THE PREVIOUSLY REVIEWED SHEET. |
| | |
| | 8. SHT P1-3.1 NO REVISION SHOWN. NO CHANGE FROM |
| | PREVIOUSLY REVIEWED SHEET. SECTION 106.1.3. |
| | |
| | 9. SHT P1-4.0 REVISIONS NOT CLOUDED AT THE NEW ROOF |
| | DRAIN LOCATIONS.--ALSO THE RWL SIZE IS NOT LEGIBLE |
| | AT COLUUM LINES 8/L & 8/H. PLEASE CLARIFY. SECTION |
| | 106.1.1 & TABLE 1106.3. |
| | |
| | 10. SHT P1-4.1 REVISION 190 NOT FOUND ON THE FLOOR PLAN |
| | & REVISIONS 1 & 2 HAVE BEEN DELETED FROM THE REVISION |
| | INDEX. PLEASE CORRELATE AND ALL REVISIONS ON PREVIOUSLY |
| | REVIEWED SHEETS SHALL REMAIN ON THE REVISION INDEX THRU |
| | THE LIFE OF THE PLANS TO TRACK ALL REVISIONS AND FOR |
| | PUBLIC RECORD. SECTION 1106.1.3. |
| | |
| | 11. SHT P1-4.2 REVISIONS NOT CLOUDED IN MANY AREAS. BE |
| | SURE TO CLOUD ALL REVISIONS SUBMITTED AFTER THE LAST |
| | REVIEWED/STAMPED SET OF REVISIONS. SECTION 106.1.3. |
| | |
| | 12. SHT P1-5.0 NO REVISION NUMBER INDICATED FOR CLOUDED |
| | REVISIONS BETWEEN COLUUM LINES 1/H-L & 10/H-L. PLEASE |
| | NUMBER ALL REVISIONS. ALSO NO CHANGE NOTED FOR CLOUDED |
| | REVISION AT COLUUM LINES 6/C-D1 & B/6-8. PLEASE |
| | CORRELATE. SECTION 106.1.3.--PIPING FOR THE |
| | CONDENSATE SNAKING FROM RISER TO UNIT.FITTINGS SHOULD |
| | BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. |
| | SECTION 706.1. |
| | |
| | 13. SHTP3-7.0 REVISIONS SHOWN ON RWL'S 5, 6 & 7 WITH |
| | CLOUDS OR REVISIONS NUMBERS. PLEASE SHOW CLOUDS AND |
| | REVISION NUMBERS FOR EACH REVISIONS. SECTION 106.1.3. |
| | --REVISION NUMBER 11 DOES NOT INDICATE WHAT IS |
| | REVISED. PLEASE CLARIFY. SECTION 106.1.1.--THE |
| | ADDITION OF RWL'S 11& 14 ADD UP TO 10,420SF. 10" PIPE |
| | IS REQUIRED PER TABLE 1106.3. 8" IS SHOWN. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |