| 2008-05-29 15:05:51 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHTS P1-1.0 & P1-1.1 REVISION 193. SHOW THE 2" |
| | CONDENSATE RISER INDICATED ON THE REVISION. PLANS SHOW |
| | CONDENSATE CONNECTION TO THE 4" SANITARY LINE. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 2. SHTS P1-3.0 & P1-3.1 CONDENSATE SHALL NOT CONNECT TO |
| | THE RAIN WATER LEADER OTHER THAN AT THE ROOF DRAINS. |
| | THE CONDENSATE SHALL DRAIN SEPARATELY FROM THE BUILDING |
| | BY A DEDICATED CONDENSATE RISER AND CONNECT TO A |
| | DRYWELL, A CATCH BASIN, A STORM LINE OR INTO A PLANTED |
| | AREA. IF CONNECTING TO THE STORM DRAIN OUTSIDE THE |
| | BUILDING, A RELIEF VENT OR GOOSENECK IS REQUIRED AS THE |
| | CONDENSATE EXITS THE BUILDING. SECTION 314.2.1. |
| | |
| | 3. SHT P1-4.0 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES |
| | NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE |
| | 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS |
| | TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 4. SHT P1-4.2 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES |
| | NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE |
| | 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS |
| | TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE |
| | CLARIFY.--ALSO REVISION NUMBER 5 IS NOT INDICATED |
| | ON THE REVISION INDEX. PLEASE SHOW ALL REVISIONS ON THE |
| | INDEX. SECTIONS 106.1.2 & 106.1.3. |
| | |
| | 5. SHT P1-5.0 CHANGES TO THE ROOF DRAINS & OVERFLOW |
| | DRAIN ARE NOT INDICATED AS CHANGES. PLEASE CLOUD AND |
| | NUMBER ALL REVISIONS SUBMITTED. SECTION 106.1.3. |
| | |
| | 6. SHT P3-1.0 RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| | PLAN FOR THE NEW SINK AT THE CONNECTION AND ROUTING OF |
| | THE PIPING. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 7. SHT P3-7.0 RISER DOES NOT REFLECT THE FLOOR PLAN AT |
| | RWL'S 11 THRU 14. ALSO RECHECK THE SQUARE FOOTAGE AT |
| | EACH ROOF DRAIN AND THE TOTAL SQUARE FOOTAGE FOR EACH |
| | RWL. THIS INFORMATION SHALL REFLECT THE FLOOR PLAN. |
| | SECTION 106.1.1 & TABLE 1106.3.--ALSO CONDENSATE |
| | SHALL NOT CONNECT TO THE RAIN WATER LEADER OTHER THAN |
| | AT THE ROOF DRAINS. THE CONDENSATE SHALL DRAIN |
| | SEPARATELY FROM THE BUILDING BY A DEDICATED CONDENSATE |
| | RISER AND CONNECT TO A DRYWELL, A CATCH BASIN, A STORM |
| | LINE OR INTO A PLANTED AREA. IF CONNECTING TO THE STORM |
| | DRAIN OUTSIDE THE BUILDING, A RELIEF VENT OR GOOSENECK |
| | IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING. |
| | SECTION 313.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |