| 2008-04-08 16:00:16 | REVIEW #: REV.14B AND 14C |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PG M1-1.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| | REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| | PLAN. |
| | ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE |
| | REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS |
| | INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO |
| | A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV |
| | 14B. |
| | |
| | 2. PG M1-1.2: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| | REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| | PLAN. |
| | ALSO, REVISION WHICH WAS PART OF THE REVISION HISTORY |
| | IS NOW MISSING FROM PLANS. THIS INDICATES IT IS LIKELY |
| | THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE BEFORE |
| | BEING REVISED AS PART OF REV 14B AND 14C. |
| | |
| | 3. PG M1-1.2: THERE IS A 10 INCH ROUND DUCT PENETRATING |
| | A 2-HOUR RATED WALL BETWEEN LOADING D1.106 AND CORRIDOR |
| | D1.006. SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN |
| | ACCORDANCE WITH FBCM 607.5. |
| | |
| | 4. PG M1-2.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| | REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| | PLAN. |
| | ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE |
| | REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS |
| | INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO |
| | A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV |
| | 14B. |
| | |
| | 5. PG M1-2.2: THIS PAGE IS NOT ABLE TO BE REVIEWED. |
| | THERE ARE MULTIPLE LAYERS IN MULTIPLE SCALES ON THE |
| | SAME PAGE. PLEASE CORRECT THE PAGE AND RESUBMIT. |
| | |
| | 6. PG M1-3.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| | REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| | PLAN. |
| | |
| | 7. PG M1-3.1: THIS PAGE HAS BEEN MODIFIED BY HAND WITH |
| | A PEN. THERE IS NO INDICATION ON PLANS THAT THESE |
| | MODIFICATIONS WERE MADE BY THE DESIGN PROFESSIONAL OF |
| | RECORD. SIGNED AND SEALED DRAWINGS SHALL NOT BE |
| | MODIFIED ONCE SIGNED AND SEALED UNLESS THE |
| | MODIFICATIONS ARE SIGNED AND DATED BY THE DESIGNER OF |
| | RECORD. OTHERWISE, IT SHALL BE ASSUMED THAT THE |
| | DRAWINGS WERE MODIFIED BY SOMEONE NOT AUTHORIZED TO DO |
| | SO. |
| | |
| | 8. PG M1-3.1: PLAN SHOWS TWO FIRE DAMPERS IN THE WALL |
| | AT VOICE/DATA A3.116. THIS WALL IS NOT SHOWN AS HAVING |
| | A FIRE RESISTANCE RATING ON ARCHITECTURAL OR LIFE |
| | SAFETY PLANS. THERE IS ALSO A 60X26 UNPROTECTED DUCT |
| | PENETRATION SHOWN IN THE SAME ROOM. PLEASE COORDINATE |
| | MECH. PLANS WITH ARCH. PLANS AND LS PLANS, SHOWING |
| | PROTECTION OF PENETRATIONS WHERE NEEDED IN ACCORDANCE |
| | WIT FBCM 607.5. |
| | |
| | 9. PG M1-3.2: THERE ARE AT LEAST FIVE DUCT PENETRATIONS |
| | OF FIRE RATED WALL ASSEMBLIES WITHOUT PROTECTION AT |
| | CORRIDORS C3.011 AND C3.012. SHOW HOW THESE |
| | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH |
| | FBCM 607.5 AND 607.5.4. |
| | |
| | 10. PG M1-3.2: THIS SHEET CONTAINS CHANGES WHICH ARE |
| | NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. |
| | PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED |
| | SINCE REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED |
| | ON PLAN. |
| | ALSO, REVISION 12B WHICH WAS PART OF THE REVISION |
| | HISTORY IS NOW MISSING FROM PLANS. THIS INDICATES IT IS |
| | LIKELY THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE |
| | BEFORE BEING REVISED AS PART OF REV 14B AND 14C. |
| | |
| | 11. PG M1-3.2: PLEASE SHOW SIZE OF DUCT FOR EF-3 ABOVE |
| | STAIR 10 RISER BETWEEN TRANSITIONS. ALSO, SHOW SIZE OF |
| | TAP AT 40X44 RETURN DUCT FOR RTU-2 NEAR STAIR 7. |
| | |
| | 12. THIS SHEET CONTAINS CHANGES WHICH ARE NOT MARKED OR |
| | CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE MARK OR |
| | CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE REV. 12A. |
| | ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON PLAN. |
| | |
| | 13. PG M1-4.1: THE DUCT FEEDING A VAV FROM SOUTH END OF |
| | SERVER ROOM IS PENETRATING A 2-HOUR RATED WALL ASSEMBLY |
| | AS SHOWN ON ARCHITECTURAL AND LIFE SAFETY PLANS. PLEASE |
| | COORDINATE PLANS AND SHOW PENETRATIONS TO BE PROTECTED |
| | IN ACCORDANCE WITH FBCM 607.5. |
| | |
| | 14. PG M1-4.1: THERE IS A DELTA-13 REVISION MARK IN THE |
| | RISER FOR CAHU-1. THERE IS NO REVISION 13 SHOWN ON THE |
| | REVISION HISTORY FOR THIS PAGE. PLEASE CLARIFY. |
| | |
| | 15. PG M1-4.2: RETURN DUCT SIZE FOR AHU-3 HAS BEEN |
| | REVISED ON THIS PAGE BUT THE CORRESPONDING DUCT HAS NOT |
| | BEEN REVISED ON PAGE M2-2.0. PLEASE COORDINATE PLANS |
| | AND RESUBMIT. |
| | |
| | 16. SUPPLY AND RETURN DUCT RISER SIZES FOR RTU-1 AND |
| | RTU-2 HAVE BEEN REVISED ON THIS PAGE BUT HAVE NOT BEEN |
| | REVISED ON PAGE M1-5.2. PLEASE COORDINATE PLANS AND |
| | RESUBMIT. |
| | |
| | 17. PG M1-5.1: THIS SHEET CONTAINS CHANGES WHICH ARE |
| | NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. |
| | PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED |
| | SINCE REV. 12A. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED |
| | ON PLAN. |
| | |
| | 18. PG M2-1.0, M3-1.0, M6-1.0: THESE PAGES ARE OK BUT |
| | ARE BEING RETURNED TO CONTRACTOR PER THEIR REQUEST. |
| | |
| | 19. PG M2-3.0: THIS SHEET CONTAINS CHANGES WHICH ARE |
| | NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. |
| | PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED |
| | SINCE REV. 12A. |
| | |