| Date |
Text |
| 2007-09-19 11:17:05 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P1-1.3U MANY REVISIONS #11 SHOWN. THE PREVIOUS |
| | REVISION NUMBER REVIEWED WAS REVISION #4. NO REVISIONS |
| | SUBMITTED OR APPROVED AFTER THAT. CLOUD AND NUMBER ALL |
| | REVISIONS AFTER REVISION #4. REVISIONS #10 & #11 ARE |
| | NOT INDICATED ON THE REVISION INDEX, BUT ARE INDICATED |
| | ON THE PLANS. THESE REVISIONS ARE NOT CLOUDED.FOR |
| | EXAMPLE SEE CHANGES IN THE TOILET ROOM B1.108 NOT |
| | INDICATED AS A REVISION AS WELL AS CHANGES IN THE |
| | SANITARY AND CHANGES IN THE STORM AND CHANGES IN THE |
| | LOCATION OF THE FLOOR DRAINS IN THE PUMP ROOMS. THE |
| | COLUMN LINES HAVE BEEN CHANGED ALSO, (DELETED SOME). |
| | THESE HAVE NOT BEEN INDICATED AS REVISIONS.--ALL |
| | CHANGES IN THE SYSTEMS SHALL BE REFLECTED ON THE RISER |
| | DIAGRAMS TO REFLECT THESE CHANGES. SECTION 106.1.1. |
| | |
| | 2. SHT P1-5.0 MANY CHANGES ARE NOT INDICATED BY CLOUDS |
| | OR REVISION NUMBERS. THE LAST REVISION #5, SIGNED, |
| | SEALED & DATED 2-5-7. ALL CHANGES FROM THE STAMPED |
| | PLANS SHALL BE CLOUDED AND INDICATED WITH A REVISION |
| | NUMBER. (PLEASE TURN OFF ALL PREVIOUS CLOUDS AND |
| | REVISION NUMBERS FROM SHEETS THAT HAVE BEEN APPROVED |
| | PRIOR TO SUBMITTING NEW REVISIONS. -- LEAVING ON |
| | PREAPPROVED REVISION CLOUDS AND REVISION NUMBERS ADDS |
| | TIME TO EACH REVIEW). |
| | |
| | 3. SHT P1-5.1 REVISION #12 HAS NOT BEEN FOUND. PLEASE |
| | INDICATE WITH A CLOUD AND A REVISION NUMBER AND PLEASE |
| | TURN OFF THE CLOUDS AND REVISION NUMBERS FROM |
| | PREVIOUSLY APPROVED REVISIONS. |
| | |
| | 4. SHT P3-7.0 ISOMETRIC RISER DIAGRAM FOR RWL-7 DOES |
| | NOT REFLECT THE FLOOR PLAN. CLEANOUT NOT SHOWN ON THE |
| | FLOOR PLAN. CLEANOUTS TO BE INSTALLED PER SECTION |
| | 1101.8. SECTION 106.1.1. |
| | |