| Notes |
| Date |
Text |
| 2007-10-23 12:31:09 | 1. SOME SUGGESTED IMPROVED WORDING IS PROVIDED FOR NOTE | | | # 26 ON PAGE FAO.1. "THE FIRE ALARM SYSTEM SHALL BE | | | ABLE TO TRANSMIT THE FOLLOWING ALARMS TO THE UL LISTED | | | CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE. | | | | | | A) WATERFLOW | | | B) GENERAL ALARM | | | C) SUPERVISORY SIGNAL | | | D) TROUBLE SIGNAL | | | | | | 2. ANY SPECIAL LOCKING ARRANGEMENTS ON EXIT DOORS SHALL | | | COMPLY WITH WITH CHAPTER 7 OF THE LIFE SAFETY CODE, | | | 101. | | | | | | 3. THE PLANS SEEM TO SUGGEST "PROVIDE AND INSTALL SMOKE | | | DETECTORS PER FLORIDA MECHANICAL CODE (FMC) 607.5.4.1 | | | AT EACH SMOKE DAMPER. SINCE NO FIRE ALARM SYSTEM SHOP | | | DRAWINGS HAVE BEEN SUBMITTED IT IS UNKNOWN IF A | | | COMPLETE SMOKE DETECTION SYSTEM IS TO BE INSTALLED | | | WITHIN THE BUILDING. IN FMC 607.3.2.1 PROVIDES | | | INFORMATION ON HOW SMOKE DAMPER ACTUATION METHODS CAN | | | BE PERFORMED USING 1-5. PLEASE ADVISE THE MECHANICAL | | | SECTION OF THE CONSTRUCTION SERVICES DEPARTMENT AND | | | THIS OFFICE IF A COMPLETE SMOKE DETECTION SYSTEM IS | | | PLANNED FOR THE BUILDING AND IT THIS SYSTEM IS PLANNED | | | TO ACTUATE THE SMOKE DAMPERS. PLEASE COORDINATE ALL | | | FIRE/ SMOKE DAMPERS AND FIRE DAMPERS WITH THE | | | MECHANICAL DIVISION OF THE CONSTRUCTION SERVICES | | | DEPARTMENT. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 FAX |
|