| Date |
Text |
| 2006-11-14 17:40:40 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT P0-1.0 WATER HEATER SCHEDULE. TWH-1, TWH-2, |
| | TWH-3, SUBMIT MANUF. SPECIFICATION SHEETS THAT SHOW |
| | LISTING. SECTION 303.4. |
| | ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE. |
| | |
| | 2. SHT P0-1.0 PUMP SCHEDULE. SUBMIT MANUF. |
| | SPECIFICATION SHEETS THAT SHOW LISTING. SECTION 303.4. |
| | ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE. |
| | |
| | 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE |
| | INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR |
| | CERTIFICATION AND SERVICE. |
| | ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE |
| | BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. |
| | |
| | 4. SHTS P1-1.1 THRU P1-5.1 INDICATE RISER NUMBER FOR |
| | THE SANITARY, STORM, AND WATER RISERS TO TRACK RISERS |
| | THRU THE BUILDING. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SOME RISERS INDICATED ON THE |
| | UPPER FLOORS ARE NOT INDICATED ON THE FIRST FLOOR. |
| | EXAMPLE P/6 STARTS ON THE FIRST FLOOR, BUT P/8 ALSO |
| | DRAINS THRU P/6. LABEL P/8 WITH P/6 ON THE FIRST FLOOR. |
| | ALSO WHY DOES P5 TURN INTO P9? |
| | |
| | 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY |
| | SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1 |
| | (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE |
| | NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS |
| | REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE |
| | NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE |
| | INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK. |
| | ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER |
| | DIAGRAMS. |
| | |
| | 6.OK |
| | 7.OK |
| | 8.OK |
| | 9.OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | |
| | 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| | AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS, |
| | INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS |
| | DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS. |
| | SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY |
| | OVERFLOW SCUPPERS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE |
| | SUBMITTED. |
| | |
| | 15. OK |
| | 16. OK (SHOWN ON SHT P2-1.0U) |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | |
| | 21. SHT P2-2.0 ALL DETAILS, SHOW ALL PIPE SIZES FOR ALL |
| | SYSTEMS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR |
| | MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) & |
| | 710.1(2). |
| | |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | |
| | 33. SHT P2-3.0 ALL DETAILS, SHOW ALL PIPE SIZES IN ALL |
| | SYSTEMS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR |
| | MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) & |
| | 710.1(2). |
| | |
| | 34. SHT P4-1.0 DETAIL #12 CONDENSATE DRAIN, DETAIL NOT |
| | APPROVED AS SHOWN. CLARIFY OPEN NIPPLE. CLARIFY GAP |
| | BETWEEN PIPE AND FLOOR. WHY USE A TEE AT THE BOTTOM OF |
| | THE TRAP? SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT DETAIL NOT EXPLAINED OR REVISED |
| | AS NOTED. COMMENT NOT ADDRESSED. |
| | |
| | 35. SHT P4-1.0 DETAIL #13 WATER HEATER DETAIL. PLEASE |
| | SHOW COMPLIANCE WITH SECTION 607.3.2, THERMAL EXPANSION |
| | CONTROL. - A SHUT OFF VALVE IS REQUIRED ON EACH SIDE OF |
| | THE CIRCULATING PUMP. - SUBMIT PUMP MANUF. |
| | SPECIFICATIONS SHEETS. PUMP SHALL BE LISTED. SECTION |
| | 303.4. |
| | ****RESPONSE NOTED, BUT THERMAL EXPANSION CONTROL HAS |
| | NOT BEEN ADDRESSED. CIRCULATION PUMP SPECIFICATIONS |
| | SHALL BE SUBMITTED WITH SUBMITTAL PACKAGE. |
| | |
| | 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND |
| | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, |
| | VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS |
| | THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT |
| | SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE |
| | ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE |
| | SYSTEM. |
| | |
| | 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM & |
| | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS, |
| | & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE |
| | SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION |
| | 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE |
| | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT |
| | INDICATED. |
| | |
| | 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL |
| | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW |
| | PROTECTION ETC. SECTION 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN, |
| | NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS, |
| | DISHWASHERS, & WASH MACHINES IF FIXTURES ARE |
| | PROVIDED). |
| | |
| | 39. SUBMIT A CONDENSATE RISER ISOMETRIC DIAGRAM. SHOW |
| | ALL PIPE SIZES, VENTS, TERMINATION POINTS ETC. SECTION |
| | 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT NO CONDENSATE RISER DIAGRAM |
| | SUBMITTED AS REQUESTED. |
| | |
| | 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE |
| | SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE |
| | BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS |
| | 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE |
| | NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS |
| | SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE |
| | ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS). |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES |
| | NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM |
| | OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & |
| | ROOF PLAN. SECTION 106.1.1. |
| | |
| | 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO |
| | RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID |
| | IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY |
| | PIPE SIZES. SECTION 106.1.1. |
| | |
| | 3B. SHTS P1-1.1U & P2-1.01 DETAIL #6 THE SINK SHALL NOT |
| | DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE |
| | DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE |
| | TOILET ROOM FIXTURES. SECTION 909.1. |
| | |
| | 4B. SHT P1-1.2U FD-2 IN D1.106 LOADING REQUIRES A VENT. |
| | THIS DOES NOT REFLECT THE RISER DIAGRAM PIPING. THE |
| | FLOOR IS SLOPING AWAY FROM THE TRENCH DRAIN. PLEASE |
| | CLARIFY. SECTIONS 901.2.1, 106.1.1. |
| | |
| | 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 & |
| | P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN |
| | AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION |
| | OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS. |
| | 708.3.3, 708.3.4, 708.3.5. |
| | |
| | 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND |
| | ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & |
| | P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. |
| | SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" |
| | CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE |
| | Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. |
| | WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE |
| | SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD |
| | CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD |
| | CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN |
| | THRU THE MIDDLE OF THE FIXTURE GROUP). |
| | |
| | 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 |
| | RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| | RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE |
| | INFORMATION. SECTION 106.1.1 & TABLE 1106.3. |
| | |
| | 8B. SHT P1-1.3 THE WATER SUPPLY TO THE ICE MAKER SHALL |
| | CONNECT UPSTREAM OF THE MAKE-UP WATER FOR THE COOLING |
| | TOWERS. - SHOW THE LOCATIONS FOR RWL-6 & RWL-7. SECTION |
| | 106.1.1 & 608.1. |
| | |
| | 9B. SHT P1-2.1 RISER P/8 NOT INDICATED ON THE 1ST |
| | FLOOR. PLEASE SHOW WHERE RISERS START ON THE FIRST |
| | FLOOR. SECTION 106.1.1. |
| | |
| | 10B. SHT P1-3.2 RISER P/4 SHOWN AT COL. LINE H/2 WAS |
| | RISER P/2 ON THE FLOOR BELOW. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 11B. SHT P1-4.1 C/O FOR S-1 SINK PIPING CONNECTING TO |
| | RISER P/7 IS NOT APPROVED AS INDICATED. SECTION 706.3. |
| | - RISER P/9 IS NOT INDICATED ON PREVIOUS LEVELS. PLEASE |
| | CLARIFY. - RISER P/5 SHOWN ON PREVIOUS LEVEL IS NOT |
| | INDICATED. PLEASE CLARIFY. |
| | |
| | 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE |
| | 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL |
| | 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE |
| | FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4" |
| | SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN |
| | OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR |
| | PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1. |
| | |
| | 13B. SHT P1-4.2 SANT. RISER P/2 VTR NOT SHOWN. SECTION |
| | 106.1.1. |
| | |
| | 14B. SHOW ALL PIPE SIZES PER TABLE 1106.3. |
| | |
| | 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - |
| | INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. |
| | SECTION 106.1.1. |
| | |
| | 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE |
| | NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS |
| | IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM. |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING |
| | LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE |
| | SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS, |
| | SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE |
| | D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING |
| | ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO |
| | THE BLDG. DRAIN. SECTION 106.1.1. |
| | |
| | 18B. SHT P2-1.0U DETAILS 3 & 4, SUBMIT A DETAIL FOR THE |
| | PIPING ARRANGEMENT FOR THE D.F.'S. SECTION 106.1.1. |
| | |
| | 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT |
| | DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET |
| | ROOM. SECTION 909.1. |
| | |
| | 20B. SHT P2-1.0 DETAIL 1 DOES NOT REFLECT THE FLOOR |
| | PLAN OR RISER DIAGRAM. NO WATER PIPING TO WH'S SHOWN. |
| | SECTION 106.1.1. |
| | |
| | 21B. SHT P2-1.0 DETAIL 2 DOES NOT REFLECT THE FLOOR |
| | PLAN. SHOWS 2" WATER SUPPLY. SECTION 106.1.1. |
| | |
| | 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR |
| | PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION |
| | 106.1.1. |
| | |
| | 23B. SHT P2-1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR |
| | PLAN FOR SANT. TO LAVS. FLOOR DRAINS NOT VENTED. |
| | SECTIONS 106.1.1 & 901.2.1. |
| | |
| | 24B. SHT P2-2.0 DETAIL 1, INDICATE RISER NUMBERS. |
| | SECTION 106.1.1. |
| | |
| | 25B. SHT P2-2.0 DETAIL 2, SUBMIT A DETAIL FOR SANT. |
| | PIPING TO D.F'S. - DOES NOT REFLECT THE RISER DIAGRAM. |
| | SECTION 106.1.1. |
| | |
| | 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT. |
| | PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER |
| | DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU |
| | BATHROOM FIXTURES. SECTION 106.1.1. |
| | |
| | 27B. SHT P2-2.0 DETAIL 4, NO PIPING TO FLOOR DRAINS |
| | SHOWN. SECTION 106.1.1. |
| | |
| | 28B. SHT P2-2.0 DETAIL 5, SUBMIT A DETAIL FOR SANT. |
| | PIPING TO D.F.'S. SECTION 106.1.1. |
| | |
| | 29B. SHT P2-2.0 DETAIL 6, SUBMIT A DETAIL FOR SANT. |
| | PIPING TO D.F.'S. SECTION 106.1.1. - SANT. RISER |
| | UPSTREAM OF JANITOR SINK NOT SHOWN. (SEE RISER |
| | DIAGRAM). SECTION 106.1.1. |
| | |
| | 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH |
| | LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS |
| | NO PIPING. SECTION 106.1.1. |
| | |
| | 31B. SHT P2-3.0 DETAIL 2, NO PIPING SHOWN TO FLOOR |
| | DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. |
| | SECTION 106.1.1. |
| | |
| | 32B. SHT P2-3.0 DETAIL 3, NO PIPING SHOWN TO FLOOR |
| | DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. |
| | SECTION 106.1.1. |
| | |
| | 33B. SHT P2-3.0 DETAIL 4, NO PIPING SHOWN TO FLOOR |
| | DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. |
| | SECTION 106.1.1. |
| | |
| | 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED |
| | ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR |
| | LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR |
| | DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION |
| | 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 |
| | SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE |
| | BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND |
| | 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C |
| | STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. |
| | SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. |
| | SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION |
| | 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR |
| | DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & |
| | 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS |
| | SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES |
| | NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR |
| | FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE |
| | FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL |
| | SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. |
| | |
| | 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT |
| | THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING |
| | FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE |
| | BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN |
| | SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - |
| | PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE |
| | FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES |
| | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| | INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL |
| | 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS |
| | INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE |
| | INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE |
| | FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT |
| | REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF |
| | C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - |
| | PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN |
| | UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT |
| | VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT |
| | BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. |
| | - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO |
| | F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A |
| | DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN |
| | AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. |
| | - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO |
| | BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION |
| | 106.1.1. |
| | |
| | 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| | TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION |
| | 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF |
| | THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM |
| | OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH |
| | P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING |
| | TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. |
| | FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & |
| | P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON |
| | RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT |
| | REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE |
| | OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS |
| | A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE |
| | OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE |
| | LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & |
| | A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - |
| | PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR |
| | PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 38B. SHT P3-4.0 GARAGE WATER RISER DIAGRAM SHOWS WH'S |
| | BELOW GRADE. PLEASE CLARIFY. - SHUT OFF VALVE REQUIRED |
| | ON WH SHOWN BELOW GRADE. SECTION 606.2(2). - A WATER |
| | HAMMER ARRESTOR IS REQUIRED AT THE ICE MACHINE. SECTION |
| | 604.9. - SHUT OFF VALVES ARE REQUIRED FOR THE HOSE |
| | BIBBS ON THE ROOF. SECTION 606.2(2). - SANITARY RISER |
| | DIAGRAM, FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT |
| | WASTE. A FLOOR SINK OR HUB DRAIN IS REQUIRED FOR THE |
| | ICE MACHINE. SECTIONS 802.3 & 802.3.2. - SECTION |
| | 106.1.1. |
| | |
| | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. OFFSETS BETWEEN THE |
| | METER AND THE RISER ARE NOT SHOWN. - |
| | INDICATE WHAT THE RISERS ABOVE THE TEE |
| | AT THE TOP OF THE RISER AND AT THE |
| | GENERATOR ARE FOR. FUTURE BTU LOAD AND |
| | DISTANCE MAY REQUIRE CHANGES IN THE |
| | GAS SYSTEM WHEN ADDED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD- |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH |
| | FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER |
| | DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL |
| | OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. |
| | SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR |
| | PLAN AT ROOMS C2.104/C2.103. (2 LAVS SHOWN EACH TOILET |
| | ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, |
| | JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - |
| | INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH |
| | RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. |
| | |
| | 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON |
| | THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN |
| | ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, |
| | AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 |
| | TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO |
| | TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & |
| | RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT |
| | FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION |
| | 106.1.1. |
| | |
| | 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND |
| | SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT |
| | REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - |
| | RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT |
| | SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO |
| | FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF |
| | LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET |
| | PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT |
| | INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE |
| | CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, |
| | 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES |
| | PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE |
| | ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT |
| | REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT |
| | THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE |
| | 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS |
| | REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES |
| | "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL |
| | AND SIGNATURE" |
| | |
| | 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF |
| | AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. |
| | 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS |
| | REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. |
| | UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. |
| | PLEASE RESEAL PLANS. |
| | |
| | 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK. |
| | 61G1-16.004(1) & FS 481.319. |
| | |
| | 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION |
| | REQUIRED IN 61G1-16.004. |
| | |
| | 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE |
| | REQUIRED ON PLANS. SECTION 106.1.1. |
| | |
| | 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND |
| | FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3 |
| | ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES |
| | ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF |
| | DRINKING FOUNTAINS. |
| | |
| | 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD |
| | FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER |
| | TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE |
| | UPDATE FIXTURE COUNT. |
| | |
| | 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH |
| | FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY |
| | 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS. |
| | TABLE 403.1. |
| | |
| | 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST |
| | FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, |
| | BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| | REQUIRED. |
| | |
| | 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD |
| | FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, |
| | BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| | REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. |
| | PLEASE CORRECT INFORMATION. |
| | |
| | 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH |
| | FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT |
| | THE FIXTURE COUNT. TABLE 403.1. |
| | |
| | 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN |
| | OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE |
| | POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT |
| | LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR |
| | E-MAIL [email protected]. |
| | |
| | 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE |
| | CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED |
| | PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% |
| | REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. |
| | PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. |
| | |
| | 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS |
| | ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE |
| | SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT |
| | IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN, |
| | BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF |
| | DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE |
| | RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO |
| | ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT |
| | COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4 |
| | - 5/E THRU H). |
| | |
| | 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE |
| | CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS, |
| | INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO |
| | THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF |
| | LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS |
| | WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS |
| | IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR |
| | TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS |
| | 1106.1, 1106.2, 1106.3, 1106.4. |
| | |
| | 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL |
| | INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND |
| | INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE |
| | OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. |
| | |
| | 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA |
| | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | |
| | 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE |
| | FOR THE URINAL. SECTION 11-4.18.3. |
| | |
| | 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| | 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE). |
| | |
| | 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| | 11-28. (SHOWS 2'2"). |
| | |
| | 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA |
| | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | |
| | 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| | 11-28. |
| | |
| | 66B. SHT A6-3.1 DETAIL 1, SHOW THE TURNING AREA IN THE |
| | LOCKER ROOM AREA. SECTION 11-4.2.3. |
| | |
| | 67B. SHT A6-3.1 DETAILS 2, 3, 4 & 6, SHOW THE TURNING |
| | AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | |
| | 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA |
| | IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| | SECTION 11-4.22.3. |
| | |
| | 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE |
| | TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE |
| | URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3. |
| | |
| | 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS |
| | C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, |
| | A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE |
| | PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE |
| | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS |
| | REQUIRED IN SECTION 1210.2. |
| | |
| | 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10 |
| | & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE |
| | INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS |
| | COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS |
| | REQUIRED IN SECTION 1210.1. |
| | |
| | 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE |
| | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | |
| | 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE |
| | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | DETAIL #1 |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | |
| | DETAIL #2 |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | |
| | 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE |
| | DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | DETAILS #1 - #2 - #3 |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | |
| | 75B. SHT A9-4.4 SHOW THE FOLLOWING FOR COMPLIANCE:A. |
| | 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.7 CURBS |
| | |
| | 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, |
| | A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH |
| | THE FOLLOWING |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| | REQUIRED) |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED |
| | LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR |
| | REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6721 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |