| 2006-10-27 11:07:29 | 1. STAIR SUMMARY CHART NEEDED ON PAGE LS0.0. THIS CHART |
| | SHALL IDENTIFY ALL STAIRS, WIDTHS, AND EXIT |
| | CAPACITIES. |
| | 2. STAIRWELL IDENTIFICATION SIGNS SHALL BE PROVIDED ON |
| | THE SIGNAGE LEGEND DISPLAYED ON PAGE LS0.0. THESE |
| | STAIRWELL IDENTIFICATION SIGNS SHALL IDENTIFY THE |
| | STAIR, TERMINUS, TOP AND BOTTOM, FLOOR NUMBER, ETC. |
| | 3. STAIR # 5 ON PAGE LS1-1.0 HAS STILL NOT BEEN |
| | CORRECTED. PLEASE MOVE OR REMOVE WALL SECTION DIRECTLY |
| | IN FRONT OF EXIT STAIR DOOR TO ALLOW FOR PROPER EXIT |
| | DISCHARGE. |
| | 4. EXIT SIGNS APPEAR TO BE MISSING FROM SHEET LS1-1.1. |
| | PLEASE SEE BACK OF HOUSE AREA IN COMMISSION CHAMBERS. |
| | OTHER AREAS ALSO ABSENT OF SIGNS. CONFLICTS APPEAR TO |
| | EXIST BETWEEN LS1-1.1 AND E2-1.1. |
| | 5. EXIT SIGN NOTED DIRECTLY INFRONT OF ELECTRICAL ROOM |
| | DOOR ON PAGE E2-1.2. |
| | 6. EXIT SIGN IN CENTER OF STAIR # 9 ON PAGE E2-1.2. |
| | 7. EXIT SIGN WITH DIRECTIONAL ARROWS DIRECTS PERSONS TO |
| | GRAND STAIR ON PAGE E2-2.1. |
| | 8. EXIT SIGN MISSING IN FRONT OF STAIR DOOR # 7 ON PAGE |
| | E2-2.2. |
| | 9. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF |
| | STAIR DOOR ON PAGE E2-2.2. |
| | 10. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF |
| | STAIR DOOR ON PAGE E2-3.2. |
| | 11. EXIT SIGN INSTALLED NEAR WALL OF STAIR # 9 NOT NEAR |
| | DOUBLE DOORS ON PAGE E2-3.2. |
| | 12. NO EXIT MARKINGS COULD NOT BE LOCATED ON PAGES |
| | E2-4.0 AND E2-4.1. |
| | 13. EXIT SIGN MARKINGS MISSING FROM PAGE E2-4.2. |
| | 14. SAME CONDITION EXISTS ON PAGE E2-5.1. |
| | 15. PLEASE EXPLAIN FACP CALL OUT IN VOICE DATA ROOM ON |
| | PAGE E3-1.0. |
| | 16. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE FIRE ALARM SYSTEM. FIRE ALARM |
| | SYSTEM SHALL BE UL LISTED FOR CENTRAL STATION SERVICE. |
| | PLEASE EXPLAIN "PROVIDE ZONED EMERGENCY VOICE |
| | EVACUATION"ON PAGE FA1-1. SYSTEM TO COMPLY WITH NFPA |
| | 72, THE NATIONAL FIRE ALARM CODE, 2002 EDITION. |
| | 17. EXIT SIGN MISSING NEAR STAIR # 2 ON PAGE E1-6.1. |
| | 18. TRAINING ROOM AT A 4 AND 5 MISSING FIRE ALARM |
| | NOTIFICATION APPLIANCES ON PAGE FA1-4. |
| | 19. PLEASE EXPLAIN NOTE # 3 FIRE PROTECTION DESIGN |
| | CRITERIA INFORMATION BOX ON PAGE FP0-1.0. |
| | 20. ON PAGE FP1-1.0 AT LEAST FIVE FIRE DEPARTMENT |
| | CONNECTIONS ARE SHOWN. AGAIN ALL OF THESE ARE NOT |
| | NECESSARY. |
| | 21. SOME FIRE SPRINKLER DRAWINGS ARE ABSENT OF FIRE |
| | SPRINKLER HEADS. IT IS DIFFICULT TO DETERMINE IF 100 % |
| | COVERAGE IS PROVIDED DUE TO INSUFFICIENT INFORMATION. |
| | 22. ON PAGE FP1-2.1 KEY NOTE # 5 "PROVIDE WATER CURTAIN |
| | FOR GLASS AREAS LOCATE SPRINKLERS 6'-0 ON CENTER". |
| | PLEASE ILLUSTRATE WATER CURTAIN ARRANGEMENT. |
| | 23. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM 200 |
| | FIRE SUPPRESSION SYSTEM PLANNED FOR THE SERVER ROOM ON |
| | PAGE FP1-4.0. |
| | 24. DOUBLE DETECTOR CHECK VALVE ASSEMBLY DETAIL SHOWN |
| | ON PAGE FP2-1.0 DOES NOT INDICATE TAMPER SWITCHES, |
| | CHAIN AND LOCK. |
| | 25. FLOOR CONTROL VALVE ASSEMBLY DETAIL SHOWN ON PAGE |
| | FP3-1.0 SHALL BE EQUIPPED WITH 2 1/2 TO 1 1/2 |
| | REDUCERS. |
| | 26. PLEASE DISPLAY HEIGHT DIMENSIONS FROM ROOF TO |
| | EXHAUST FAN ON PAGE M502.0. |
| | 27. COULD NOT LOCATE WHAT THE FIREFIGHTERS SMOKE |
| | CONTROL PANEL FOR THE ATRIUM SYSTEM LOOKS LIKE WITH THE |
| | MECHANICAL DRAWINGS. |
| | 28. ALSO COULD NOT LOCATE A SEQUENCE OF OPERATIONS |
| | MATRIX FOR THE ATRIUM MECHANICAL SYSTEM IN THE |
| | MECHANICAL DRAWINGS. |
| | 29. NO EXIT SIGN NOTED AT THE BACK LOADING DOCK DOUBLE |
| | DOORS ON PAGE LS1-1.2. |
| | 30. ALL MECHANICAL, ELECTRICAL, AND STORAGE ROOM DOORS |
| | ARE TO BE SMOKE RESISTANT. PLEASE ESNURE THAT THE PLANS |
| | ARE REVISED TO REFLECT THIS CHANGE. |
| | 31. OCCUPANT LOAD TAG FOR GROUP B BUSINESS ON PAGE |
| | LS1-2.0 SHOULD READ 25 OCCUPANTS INSTEAD OF 40 |
| | OCCUPANTS. |
| | 32. PROGRAM MEETING ROOM ON PAGE LS1-3.2 THAT CONTAINS |
| | 50 SEATS DOES NOT CONTAIN ANY EXIT SIGNS. |
| | 33. OCCUPANT LOAD TAG FOR GROUP B BUSINESS OCCUPANCY ON |
| | PAGE LS1-4.0 SHOULD READ 270 PERSONS NOT 278 |
| | OCCUPANTS. |
| | 34. ILLUMINATED EXIT SIGN IN SERVER ROOM LOCATED ON |
| | PAGE LS1-4.1 IS NOT LOCATED INFRONT OF ANY EXIT DOOR. |
| | 35. EXIT SEPARATION LINE IN TRAINING ROOM ON PAGE |
| | LS1-4.1 IS DRAWN TO A DOOR ABSENT OF AN EXIT SIGN. |
| | 36. A FIRE EXTINGUISHER CABINET IS LOCATED ON PAGE |
| | LS1-4.1 NEAR MEN'S ROOM BUT DOES NOT APPEAR TO BE |
| | AFFIXED TO ANYTHING. |
| | 37. IT APPEAR THAT A FIRE EXTINGUISHER CABINET IS |
| | MOUNTED ON A DOOR TO THE SERVER ROOM ON PAGE LS1-4.1. |
| | 38. EXIT SIGN ON PAGE LS1.6.1 IS NOT LOCATED NEAR STAIR |
| | DOOR. |
| | 39. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL HANDRAILS, GUARDRAILS, TEMPERED GLASS WALLS |
| | CABLE RAILINGS, AND PRE-ENGINEERED RAILINGS. |
| | 40. ON PAGE ID2-4.2 A SOLID WALL EXISTS WHERE A DOOR |
| | EXISTS FOR THE STAIRWELL. |
| | 41. SEVERAL BUILDING ADDRESSES NOTED ON TWO DIFFFERENT |
| | ELEVATIONS ON PAGE A4-1.0. THE ADDRESSES SHALL ONLY BE |
| | LISTED ON THE PROPER ELEVATION. |
| | 42.ALL PROPOSED WORK STATIONS IN OPEN WORK AREAS |
| | SHALL PROVIDE FOR A MINIMUM OF AT LEAST 44" INCHES. |
| | 43. ALL FIRE DAMPERS WILL BE REQUIRED TO BE DROP TESTED |
| | AFTER INSTALLATION TO ENSURE PROPER OPERATION. |
| | 44. CHAIRS LOCATED IN ENTRY/WAITING A2.009 MAY |
| | INTERFERE WITH DOORS ON PAGE ID2-2.0. |
| | 45. PLEASE EXPLAIN EXIT ACCESS FOR MEETING ROOM ON PAGE |
| | ID2-3.2 ESPECIALLY NEAR THE FOUR COLUMNS. |
| | 46. PLEASE PROVIDE A STAIR SECTION FOR THE PROPOSED |
| | ALTERNATING TREAD STAIRS SHOWN ON THE DRAWINGS. |
| | 47. PLEASE DISPLAY THE REQUIRED 1/2 MAXIMUM AT ALL EXIT |
| | DOOR LOCATIONS. |
| | 48. THE SERVER ROOM SHALL COMPLY WITH NFPA 75, THE |
| | STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY |
| | EQUIPMENT. |
| | 49. SOME OF THE ITEMS IDENTIFIED AT THE PREVIOUS |
| | REVIEWS STILL SEEM TO EXIST AT THIS PERMIT REVIEW. |
| | PLEASE REVIEW ALL PREVIOUS COMMENTS PROVIDED BY CITY |
| | STAFF AND ESNURE THAT PREVIOUS ITEMS IDENTIFIED HAVE |
| | BEEN CORRECTED AND PROPERLY COORDINATED ON THE |
| | APPROPRIATE SHEETS. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER |
| | 804-4709 PHONE |
| | 804-4774 FAX |