| Plan Review Notes For Permit 06100563 |
| Permit Number |
06100563 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-27 07:46:43 | | | | NONCOMPLIANT | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | | | 3} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT | | | ON THE PLAN. 215.5. | | | | | | 4} 225.32 LOCATION. | | | THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER | | | INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED | | | OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR | | | STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A | | | READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | | ENTRANCE OF THE CONDUCTOR | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 |
|