Plan Review Notes
Plan Review Notes For Permit 06100561
Permit Number 06100561
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-06 10:25:16******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
 PLEASE KNOW THAT AT THIS TIME DUE TO THE COMPLETELY
 REVISED RISER AND CHANGES, A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AS THERE ARE MANY ITEMS NOT
 SUBMITTED ON RISER ETC.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
 *** PREVIOUS REVIEW NOTES ***
  
 1) NOTE: NO, PLEASE SEE THE YEAR OF THE CODES IS NOT
 STATED ON PLANS. PLEASE KNOW THIS IS OF THE UTMOST
 IMPORTANCE AS THE 2005 NFPA-70 HAS BEEN ADOPTED AND
 THERE ARE SUBSTANTIAL DIFFERENCES.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 ** THE LATEST CODE IS NOTE YET ADOPTED BY THE STATE.
  
 2) NOTE: OK, HOWEVER SEE NOT FOR CIRCUITING.
  
 3) NOTE: NO, PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN
 COMPLETELY REVISED REMOVING MAIN WITH ANY OVER CURRENT
 PROTECTION DEVICES FOR SUB PANELS OR OTHER EQUIPMENT
 WHICH IS FED. PLEASE SEE THE RISER NOW SEEMS TO ONLY
 SHOW A METER TO SOME SORT OF GUTTER WITH NO MAINS ON
 THE RISER, OR ANY EQUIPMENT? PLEASE SEE 240.21 IF THE
 ATTEMPT IS TRYING TO USE SOME SORT OF TAP CONDUCTOR
 RULE. PLEASE SEE THAT ALL MAINS ARE REQUIRED TO BE
 GROUPED, ALL TAPS SHALL TERMINATE IN OVER CURRENT
 PROTECTION ETC.
 PLEASE SEE PANELS ARE SHOWN AS MLO (MAIN LUG ONLY)
 WITHOUT ANY MAINS.
 PLEASE SEE 230.70, 230.71, 230.72, 230.76, 230.79 ETC
 FOR REQUIRED MAINS ETC.
 PLEASE SEE THERE IS EQUIPMENT GROUNDING CONDUCTORS
 BEING SHOWN FROM THIS GUTTER OF SORTS TO THE MLO PANELS
 AND EQUIPMENT, WHICH IS OK AS LONG AS THERE ARE MAINS
 AHEAD OF THIS.
 PLEASE SEE THE PREVIOUS RISER WAS COMPLETELY
 DIFFERENT.
 PLEASE SHOW THE LOCATION OF SERVICE ON PLANS AND
 IDENTIFY ALL PANELS/MAINS AND THEIR LOCATIONS ON
 PLANS.110.26, 240.24 ETC.
 PLEASE SEE THE FEEDERS ON THE RISER DO NOT CORRELATE
 WITH THE FEEDERS ON THE PANEL SUBMITTED.
 FBC 106.1.2, 106.3.5.4
 NEC 2002 PLEASE ALSO SEE OTHER COMMENTS WHICH WILL
 AFFECT THE RISER AND PANELS AS SHOWN.
  
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE CORRELATE RISER AND PLANS, AS PLANS CALL FOR
 WHAT APPEARS TO BE A NEW METER/MAIN COMBO, YET RISER
 SHOWS NO MAIN? PLEASE INDICATE THE SIZE OF THE NEW
 MCB.
 230.70, 240.4, 310.15B6, 310.16, 230.71, ETC
  
 4) NOTE: OK, NOTE REMOVED.
  
 5) NOTE: NO, PLEASE SEE AS THE NOTE #3 STATES THAT
 THERE ARE NOT MAINS ETC, THE RATING CAN NOT BE
 VERIFIED.
 PLEASE SEE THE AVAILABLE FAULT CURRENT IS BEING STATED
 AND SHOWN FROM FPL AND THE MLO PANELS ARE SHOWING A 22K
 RATING FOR ALL BRANCH BREAKERS. SINCE THE MAINS ARE NOT
 SHOWN AT THIS TIME, THIS COMMENT HAS NOT BEEN
 ADDRESSED.
 ** PLEASE ALSO VERIFY THE INDICATION OF THE BRANCH
 BREAKERS BEING SHOWN AT 22K RATING AS THIS IS NOT
 COMMON AND WOULD BE EXTREMELY EXPENSIVE. HAVING THE
 BRANCH BREAKERS RATED AT 22K IS PERMITTED.
 PLEASE ADDRESS THE COMMENT FOR NEW MAINS ONCE RISER IS
 REVISED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE EQUIPMENT
 ALONG WITH SELECTIVE COORDINATION WHICH IS TO BE DONE.
 110.9, 240.12
  
 6) NOTE: NO, PLEASE SEE THE RISER WAS REVISED AND NOW
 SHOWS A NEW PANEL AND AN EXISTING PANEL, HOWEVER THE
 COMPETITION OF CIRCUITS ON PLANS AND COORDINATION WITH
 THE NEW PANEL SUBMITTED AHS NOT YET BEEN DONE.
 PLEASE SEE THE PREVIOUS COMMENT WAS TO SUBMIT A PANEL
 SCHEDULE WHICH WAS NOT SUBMITTED, NOW THAT ONE IS
 SUBMITTED, THERE ARE ITEMS WHICH DO NOT CORRELATE WITH
 LOAD CALCULATIONS AND PLANS.
 PLEASE SEE SOME ITEMS ON PLANS WHICH DO NOT CONTAIN THE
 CIRCUITING FOR WHAT THE EQUIPMENT IS. (OVEN, SA'S,
 FRIG, MICROWAVE ETC) ARE NOT CIRCUITED, EVEN THOUGH THE
 OVEN IS SHOWN IN LOAD CALCULATIONS?
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AND NEW FOR
 ITEMS ON PANEL SCHEDULE AND LOAD CALCULATIONS WHICH DO
 NOT MATCH.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT A PANEL SCHEDULE(S) INDICATING ALL
 MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE
 EXISTING.
 PLEASE BE SURE PANEL SCHEDULE(S)SHOW ALL OCP DEVICES
 AND CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS.
 PLEASE KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE
 AT THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: OK.
  
 8) NOTE:OK, HOWEVER PLEASE SEE A CIRCUIT ON PANEL
 SCHEDULE WHICH MENTIONS *WP BATH*PLEASE SEE MISSING
 DEDICATED BATH(S) CIRCUIT(S) PER 210.52D, 210.11C3
  
 9) NOTE: NO, PLEASE SEE THE CIRCUIT IS ON PANEL
 SCHEDULE HOWEVER THE LOAD IS NOT CORRECT AND THE LOAD
 WHICH IS TO BE CORRECTED NEEDS TO BE INCLUDED IN THE
 LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE MISSING DINING AREA/BREAKFAST AREA PER
 210.52B1, 210.11C1, 220.16
  
 10) NOTE: OK.
  
 11) NOTE: NO, PLEASE SEE A NOTE WAS ADDED ON THE PLANS
 AND SOME ELECTRICAL OUTLETS ARE SHOWN WITH AFCI
 PROTECTION; HOWEVER PLEASE SEE THAT THE SA'S ARE NOT
 CIRCUITED AND NOTE MENTIONS THESE ARE TO BE CIRCUITED
 TO THE KITCHEN/BATH LIGHTING CIRCUITS. THIS WOULD THEN
 REQUIRE ARC FAULT PROTECTION FOR THESE CIRCUIT(S)
 ALSO.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE WE ARE UNDER THE 2002 NEC AND REQUIRES AFCI
 PROTECTIONS FOR ALL "OUTLETS" IN BEDRM/SLEEPING AREAS.
 PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS,
 FANS, LTS, RECEPTS ETC.
  
 12) NOTE: OK, HOWEVER PLEASE KNOW AT THIS TIME DUE TO
 THE REVISIONS AND CHANGES IN RISER WHICH WILL BE
 FORTH-COMING THIS NOTE WILL REMAIN.
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR PER
 250.6, 250.24B, 250.110, 250.122
  
 13) NOTE: NO/OK, PLEASE SEE NEW GROUNDING DETAIL
 MENTIONS FOOTER STEEL WHERE AVAILABLE. PLEASE KNOW THIS
 IS REQUIRED. 250.50
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE NOTE AND VERIFY THE EXISTING/NEW GROUNDING
 ELECTRODE SYSTEM FOR THE NEW SERVICE. 250.50, CWP (IF
 METAL)
 PLEASE SEE 250.66, 310.15B16 FOR MIN SIZE SHALL BE
 1/0.
  
 14) NOTE: NO, PLEASE SEE THE HEAT FOR THE AHU HAS NOW
 BEEN COMPLETELY REVISED TO WHAT IS BEING SHOWN AS
 12.5KW. PLEASE VERIFY THIS. IF THIS IS INDEED THE CASE,
 PLEASE SEE THE SAME CODE SECTION AS PREVIOUSLY GIVEN
 FOR THE MINIMUM OVER CIURRENT PROTECTION TO BE SIZED AT
 125% PER 424.3B.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE VERIFY THE SIZE OF THE HEAT STRIPS AS SHOWN.
 5KW SEEMS LOW FOR THIS SIZE ADDITION. PLEASE KNOW THAT
 THIS IS ONLY A NOTE GIVEN. IF THIS CHANGES AND AS PANEL
 SCHEDULES ARE REQUIRED, PLEASE SEE 424.3B FOR MIN OCP.
  
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: OK.
  
 18) NOTE: OK, FOR THIS COMMENT, HOWEVER SEE #6 ABOVE.
  
 19) NOTE: NO, AS PREVIOUSLY NOTED AND THE NOTE # 3
 ABOVE.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE INDICATE THE NEW SERVICE LOCATION ON PLANS.
 PLEASE SEE 240.24, 230.70 ETC.
  
 20) NOTE: OK.
  
 21) NOTE: NO, PLEASE SEE THAT THE ENTIRE PACKAGE OF
 TRUSS PLANS AND LAYOUTS ARE THE SAME AS PREVIOUSLY
 SUBMITTED. PLEASE KNOW THAT THIS IS REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY THE OTHER TRADE(S).
 ** PLEASE KNOW THAT ONE SET WILL BE RETAINED ALONG WITH
 OTHER RETAINED PLANS. PLEASE CONTACT THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS IF THERE ARE ANY QUESTIONS ON
 THIS MATTER.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE BUILDING REVIEW NOTES, AS THE TRUSS
 ENGINEERING PLANS CONTAIN A RAISED SEAL OVER A "RUBBER
 STAMPED" SIGNATURE WHICH IS NOT PERMITTED UNDER FAC
 61G15-23.002, FS 471.025
  
 22) NOTE: OK.
  
 23) NOTE: OK.
  
 24) NOTE:NO, SAME COMMENT, PLEASE SEE THE SECTION
 GIVEN PREVIOUSLY AS THE AMOUNT OF THE RECESSED LIGHTING
 SHALL BE FIGURED INTO THE CALCULATIONS IN ADDITION TO
 THE LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON MAX WATTAGE FOR
 FIXTURE(S). THIS MAY NOTBE FIGURED IN W/ 3W/PER SQ
 FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND.
  
 25) NOTE: NO, PLEASE SEE THIS COMMENT REMAINS THE SAME
 AS THE LOAD ON THE PANEL SCHEDULE WHICH IS NOW
 SUBMITTED STILL EXCEEDS THAT FOR A SMALL APPLIANCE
 CIRCUIT.
 PLEASE SEE THE LOAD CALCULATIONS STILL INDICATE A LOAD
 OF 2500 VA???
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE SMALL APPL CIRCUITS ARE SHOWN AT 2500VA
 WHICH FAR EXCEEDS THE RATING OF A 20A CIRCUIT AND #12
 AWG.
 240.4,310.16, 220, ETC
  
 ***** NEW NOTES ***
  
 26) NOTE: PLEASE SEE THERE ARE SEVERAL ITEMS ON LOAD
 CALCULATIONS WHICH DO NOT CORRELATE WITH THE LOADS ON
 THE PANEL SCHEDULE SUBMITTED.
 PLEASE CORRELATE ALL.
 PLEASE ALSO SEE 408.4 AS THE PANEL SCHEDULE WHICH IS
 NOW SUBMITTED SHALL CONTAIN MORE DETAIL FOR THE
 CIRCUITS BEING SHOWN. PLEASE SEE THE FOLLOWING
 COMMENTARY WHICH IS BEING EXTRACTED DIRECTLY FROM THE
 CODE.
 PANEL SCHEDULES ARE *TO REQUIRE THAT THE IDENTIFICATION
 FOR EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR
 SWITCHBOARD BE LEGIBLE AND CLEARLY STATE THE SPECIFIC
 PURPOSE FOR WHICH THE CIRCUIT IS USED. CIRCUITS USED
 FOR THE SAME PURPOSE MUST BE IDENTIFIED AS TO THEIR
 LOCATION. FOR EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS
 CAN SUPPLY OUTLETS IN THE KITCHEN, DINING ROOM, AND
 KITCHEN COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS "KITCHEN WALL
 RECEPTACLES,'' DINING ROOM FLOOR RECEPTACLE,'' OR
 "KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' CIRCUIT
 DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH ONLY
 "LIGHTS'' OR "OUTLETS'' DO NOT PROVIDE THE SUFFICIENT
 DETAIL REQUIRED BY THIS SECTION.*
  
 27) NOTE: PLEASE SEE OTHER SHEETS INDICATE A
 RECIRCULATION PUMP FOR HOT WATER HOWEVER THE ELECTRICAL
 PLANS DO NOT SEEM TO INDICATE OR SHOW THIS.
 PLEASE COMPLETE AND CORRELATE WITH OTHER SHEETS FOR
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
 310.16, 240.4, ETC (NEC)
  
 28) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, THERE MAY BE FUTURE COMMENTS ON NEXT
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717