| Date |
Text |
| 2006-11-02 15:35:37 | UNSAT |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE DOUBLE-BOWL ISLAND KITCHEN SINK INDICATED ON |
| | SHEET P-1 SANITARY RISER DIAGRAM IS NOT CODE COMPLIANT |
| | PER FBC-2004 PLUMBING, SECTION 913.2 VENT CONNECTIONS: |
| | PLEASE NOTE THE DETAIL IN RED INK ON SHEET P-1 ADDING |
| | AN AIR ADMITTANCE VALVE PER FBC-2004 PLUMBING, SEC. 917 |
| | TO MEET CODE COMPLIANCE. |
| | |
| | 2. THE WASHING MACHINE PIPING INDICATED ON SHEET P-1 |
| | SANITARY RISER DIAGRAM IS NOT CODE COMPLIANT PER |
| | FBC-2004 PLUMBING, SECTIONS 406.3 , 802.4, 708.9: (A) |
| | 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE STANPIPE ON RESUBMITTAL. |
| | (C) 708.9 ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS. |
| | PLEASE INSTALL CLEANOUT FOR WASING MACHINE AT FOUR FEET |
| | ABOVE FINNISH FLOOR, 4' A.F.F. PLEASE INDICATE THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 3. PLEASE NOTE THAT THE LAUNDRYROOM PLUMBING TO THE |
| | WASHING MACHINE,SINK AND THE PLUMBING TO THE NEW |
| | KITCHEN AND SECOND FLOOR MASTER BATH MUST BE PIPED TO |
| | THE FOLLOWING TO MEET CODE COMPLIANCE AND BE INDICATED |
| | ON THE SANITARY PLUMBING RISER DIAGRAM AND FIRST FLOOR |
| | PLUMBING PLAN ON SHEET P-1. |
| | PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |