Plan Review Notes
Plan Review Notes For Permit 06100561
Permit Number 06100561
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-31 20:43:13***** UNSAT ****
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 ** THE LATEST CODE IS NOTE YET ADOPTED BY THE STATE.
  
 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR
 SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE
 WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE
 IS A FIRE ALARM SYSTEM, THEN THEY WOULD BE SD. PLEASE
 ALSO SEE LOCATIONS SHALL BE INSTALLED PER 11.5.1.1, AND
 11.8.3.
 PLEASE SEE AREAS WHICH CONTAIN A TRAY/VAULTED CEILING ,
 THE SA SHALL BE INSTALLED WITHIN 12" OF THE HIGHEST
 POINT OF A FLAT CEILING AND WITHIN 3' OF THE PEAK ON A
 SLOPED/VAULTED CEILING.
 PLEASE INCLUDE COMPLETE LAYOUT FOR THE EXISTING
 DWELLING FOR SMOKE ALARM?S EITHER EXISTING MEETING THE
 CURRENT CODE OR NEW TO BE INSTALLED. PLEASE SEE FBC
 2004 R313 WHICH REQUIRES ALL TO BROUGHT UP TO CODE.
 PLEASE ADJUST PLANS.
  
 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS
 CALL FOR WHAT APPEARS TO BE A NEW METER/MAIN COMBO, YET
 RISER SHOWS NO MAIN? PLEASE INDICATE THE SIZE OF THE
 NEW MCB.
 230.70, 240.4,310.15B6,310.16,230.71, ETC
  
 4) NOTE: PLEASE SEE NOTE ON THE BOTTOM OF LOAD
 CALCULATIONS INDICATE EXISTING 200A SERVICE TO REMAIN,
 HOWEVER RISER SHOWS A NEW 400A SERVICE??
 PLEASE CORRELATE.
 FBC ADMIN SECT 106.1.2, 106.3.5.4(8)
  
  
 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE
 EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO
 BE DONE.
 110.9, 240.12
  
 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE(S) INDICATING
 ALL MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE
 EXISTING.
 PLEASE BE SURE PANEL SCHEDULE(S)SHOW ALL OCP DEVICES
 AND CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS.
 PLEASE KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE
 AT THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: PLEASE SEE MISSING GARAGE GFI PER 210.52G,
 210.8A
  
 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3
  
 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA
 PER 210.52B1, 210.11C1, 220.16
  
 10) NOTE: PLEASE SEE 110.26 FOR ANY NEW DISCONNECTING
 MEANS FOR MIN CLEARANCES.
 PLEASE SEE UPSTAIRS CLOSET WHICH SHOWS A DISC , YET NO
 EQUIPMENT IS SHOWN.
 440.11,110.26
  
 11) NOTE:. PLEASE SEE WE ARE UNDER THE 2002 NEC AND
 REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN
 BEDRM/SLEEPING AREAS.
 PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS,
 FANS, LTS, RECEPTS ETC.
  
 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122
  
 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING/NEW
 GROUNDING ELECTRODE SYSTEM FOR THE NEW SERVICE. 250.50,
 CWP (IF METAL)
 PLEASE SEE 250.66, 310.15B16 FOR MIN SIZE SHALL BE
 1/0.
  
 14) NOTE: PLEASE VERIFY THE SIZE OF THE HEAT STRIPS AS
 SHOWN. 5KW SEEMS LOW FOR THIS SIZE ADDITION. PLEASE
 KNOW THAT THIS IS ONLY A NOTE GIVEN. IF THIS CHANGES
 AND AS PANEL SCHEDULES ARE REQUIRED, PLEASE SEE 424.3B
 FOR MIN OCP.
  
  
 15) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI
 PROTECTED.
  
 16) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHICH
 APPEAR TO CONTAIN NEW WALLS SPACE, YET DO NOT MEET
 210.52 FOR RECEPT SPACING.
 PLEASE ALSO KNOW, RAIL AREAS ARE ALSO CONSIDERED WALL
 SPACE. PLEASE SEE 2FT OR MORE, WITHIN 6FT OF A DOOR
 ETC.
  
 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
 106.1.2
  
 17) NOTE: PLEASE SEE EXISTING DWELLING LA
  
 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE
 SHOWN BUT NOT IDENTIFIED?
 WASHER/ DRYER?
  
 19) NOTE: PLEASE INDICATE THE NEW SERVICE LOCATION ON
 PLANS.
 PLEASE SEE 240.24, 230.70 ETC.
  
 20) NOTE: PLEASE BE SURE TO SEE 410.8 FOR POSSIBLE
 CONFLICT WITH THE CODE FOR RECESSED LIGHTS IN CLOSET.
  
 21) NOTE: PLEASE SEE BUILDING REVIEW NOTES, AS THE
 TRUSS ENGINEERING PLANS CONTAIN A RAISED SEAL OVER A
 "RUBBER STAMPED" SIGNATURE WHICH IS NOT PERMITTED UNDER
 FAC 61G15-23.002, FS 471.025
  
 22) NOTE: PLEASE SEE COVER SHEET MENTIONS "PALM BEACH
 COUNTY", HOWEVER SCOPE OF WORK IS LOCATED IN THE CITY
 OF WEST PALM BEACH.
  
 23) NOTE: PLEASE SEE VALUATIONS ARE BASED ON MINIMUM
 TABLES BASED IN THE FBC AND ADMINISTRATIVE SECTION.
 108.3
 PLEASE SEE POSSIBLE ADJUSTMENT MAY BE MADE.
  
 24) NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 25) NOTE: PLEASE SEE SMALL APPL CIRCUITS ARE SHOWN AT
 2500VA WHICH FAR EXCEEDS THE RATING OF A 20A CIRCUIT
 AND #12 AWG.
 240.4,310.16, 220, ETC
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, THERE MAY BE FUTURE COMMENTS ON NEXT
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]