| 2006-10-31 20:43:13 | ***** UNSAT **** |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING |
| | CODES AT A MINIMUM. |
| | 2002 NFPA-70 (NEC. |
| | 2002 NFPA-72 FAC. |
| | |
| | ** THE LATEST CODE IS NOTE YET ADOPTED BY THE STATE. |
| | |
| | 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR |
| | SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE |
| | WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE |
| | IS A FIRE ALARM SYSTEM, THEN THEY WOULD BE SD. PLEASE |
| | ALSO SEE LOCATIONS SHALL BE INSTALLED PER 11.5.1.1, AND |
| | 11.8.3. |
| | PLEASE SEE AREAS WHICH CONTAIN A TRAY/VAULTED CEILING , |
| | THE SA SHALL BE INSTALLED WITHIN 12" OF THE HIGHEST |
| | POINT OF A FLAT CEILING AND WITHIN 3' OF THE PEAK ON A |
| | SLOPED/VAULTED CEILING. |
| | PLEASE INCLUDE COMPLETE LAYOUT FOR THE EXISTING |
| | DWELLING FOR SMOKE ALARM?S EITHER EXISTING MEETING THE |
| | CURRENT CODE OR NEW TO BE INSTALLED. PLEASE SEE FBC |
| | 2004 R313 WHICH REQUIRES ALL TO BROUGHT UP TO CODE. |
| | PLEASE ADJUST PLANS. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS |
| | CALL FOR WHAT APPEARS TO BE A NEW METER/MAIN COMBO, YET |
| | RISER SHOWS NO MAIN? PLEASE INDICATE THE SIZE OF THE |
| | NEW MCB. |
| | 230.70, 240.4,310.15B6,310.16,230.71, ETC |
| | |
| | 4) NOTE: PLEASE SEE NOTE ON THE BOTTOM OF LOAD |
| | CALCULATIONS INDICATE EXISTING 200A SERVICE TO REMAIN, |
| | HOWEVER RISER SHOWS A NEW 400A SERVICE?? |
| | PLEASE CORRELATE. |
| | FBC ADMIN SECT 106.1.2, 106.3.5.4(8) |
| | |
| | |
| | 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE |
| | EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO |
| | BE DONE. |
| | 110.9, 240.12 |
| | |
| | 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE(S) INDICATING |
| | ALL MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE |
| | EXISTING. |
| | PLEASE BE SURE PANEL SCHEDULE(S)SHOW ALL OCP DEVICES |
| | AND CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. |
| | PLEASE KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE |
| | AT THIS TIME. |
| | 240.4,310.16, 424.3B, 210.52, ETC. |
| | FBC ADMIN SECTION 106.3.5.4(8). |
| | |
| | 7) NOTE: PLEASE SEE MISSING GARAGE GFI PER 210.52G, |
| | 210.8A |
| | |
| | 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S) |
| | CIRCUIT(S) PER 210.52D, 210.11C3 |
| | |
| | 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA |
| | PER 210.52B1, 210.11C1, 220.16 |
| | |
| | 10) NOTE: PLEASE SEE 110.26 FOR ANY NEW DISCONNECTING |
| | MEANS FOR MIN CLEARANCES. |
| | PLEASE SEE UPSTAIRS CLOSET WHICH SHOWS A DISC , YET NO |
| | EQUIPMENT IS SHOWN. |
| | 440.11,110.26 |
| | |
| | 11) NOTE:. PLEASE SEE WE ARE UNDER THE 2002 NEC AND |
| | REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN |
| | BEDRM/SLEEPING AREAS. |
| | PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS, |
| | FANS, LTS, RECEPTS ETC. |
| | |
| | 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122 |
| | |
| | 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING/NEW |
| | GROUNDING ELECTRODE SYSTEM FOR THE NEW SERVICE. 250.50, |
| | CWP (IF METAL) |
| | PLEASE SEE 250.66, 310.15B16 FOR MIN SIZE SHALL BE |
| | 1/0. |
| | |
| | 14) NOTE: PLEASE VERIFY THE SIZE OF THE HEAT STRIPS AS |
| | SHOWN. 5KW SEEMS LOW FOR THIS SIZE ADDITION. PLEASE |
| | KNOW THAT THIS IS ONLY A NOTE GIVEN. IF THIS CHANGES |
| | AND AS PANEL SCHEDULES ARE REQUIRED, PLEASE SEE 424.3B |
| | FOR MIN OCP. |
| | |
| | |
| | 15) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI |
| | PROTECTED. |
| | |
| | 16) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHICH |
| | APPEAR TO CONTAIN NEW WALLS SPACE, YET DO NOT MEET |
| | 210.52 FOR RECEPT SPACING. |
| | PLEASE ALSO KNOW, RAIL AREAS ARE ALSO CONSIDERED WALL |
| | SPACE. PLEASE SEE 2FT OR MORE, WITHIN 6FT OF A DOOR |
| | ETC. |
| | |
| | 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA |
| | DESIGNATIONS ON ELECTRICAL PLANS. |
| | 106.1.2 |
| | |
| | 17) NOTE: PLEASE SEE EXISTING DWELLING LA |
| | |
| | 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE |
| | SHOWN BUT NOT IDENTIFIED? |
| | WASHER/ DRYER? |
| | |
| | 19) NOTE: PLEASE INDICATE THE NEW SERVICE LOCATION ON |
| | PLANS. |
| | PLEASE SEE 240.24, 230.70 ETC. |
| | |
| | 20) NOTE: PLEASE BE SURE TO SEE 410.8 FOR POSSIBLE |
| | CONFLICT WITH THE CODE FOR RECESSED LIGHTS IN CLOSET. |
| | |
| | 21) NOTE: PLEASE SEE BUILDING REVIEW NOTES, AS THE |
| | TRUSS ENGINEERING PLANS CONTAIN A RAISED SEAL OVER A |
| | "RUBBER STAMPED" SIGNATURE WHICH IS NOT PERMITTED UNDER |
| | FAC 61G15-23.002, FS 471.025 |
| | |
| | 22) NOTE: PLEASE SEE COVER SHEET MENTIONS "PALM BEACH |
| | COUNTY", HOWEVER SCOPE OF WORK IS LOCATED IN THE CITY |
| | OF WEST PALM BEACH. |
| | |
| | 23) NOTE: PLEASE SEE VALUATIONS ARE BASED ON MINIMUM |
| | TABLES BASED IN THE FBC AND ADMINISTRATIVE SECTION. |
| | 108.3 |
| | PLEASE SEE POSSIBLE ADJUSTMENT MAY BE MADE. |
| | |
| | 24) NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 25) NOTE: PLEASE SEE SMALL APPL CIRCUITS ARE SHOWN AT |
| | 2500VA WHICH FAR EXCEEDS THE RATING OF A 20A CIRCUIT |
| | AND #12 AWG. |
| | 240.4,310.16, 220, ETC |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED |
| | FOR REVIEW, THERE MAY BE FUTURE COMMENTS ON NEXT |
| | REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-10-31 20:03:18 | IN ELEC ON 10/31 |