| Date |
Text |
| 2006-11-07 08:20:49 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY |
| | SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF |
| | THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT |
| | COMMENCED WITHIN 90 DAYS OF RECORDING. |
| | |
| | 2.CODE SECTION SHOWS PALM BEACH COUNTY.CODE SHOULD |
| | REFLECT WEST PALM BEACH AMMENDMENTS TO THE 2004 FBC. |
| | |
| | 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT |
| | VALUE HAS BEEN REVISED TO $241,573.00.ADDITIONAL |
| | PERMIT FEES ARE DUE. |
| | |
| | 4."R" VALUES DO NOT MACH PLANS ON THE ENERGY CALCS. |
| | |
| | 5.PRODUCT APPROVALS REQUIRED FOR GLASS BLOCK, LINTELS |
| | AND STRAPS AND TIE-DOWNS. |
| | |
| | 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY |
| | ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL |
| | ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF |
| | THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN |
| | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC |
| | FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3. |
| | |
| | |
| | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER |
| | 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE |
| | APPROVED PRIOR TO INSTALLATION. |
| | |
| | 9.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR |
| | A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS |
| | WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC |
| | EXISTING BUILDING 301.5 |
| | |
| | 10.R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| | OF 6 INCHESWITHIN THE FIRST 10 FEET. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE |
| | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | 561-805-6672 |
| | |
| | |
| | |
| | |