| 2006-10-27 15:16:54 | UNSAT |
| | REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED FOR PLUMBING PLAN |
| | REVIEW ON THE SANITARY PLUMBING RISER DIAGRAM ON SHEET |
| | PR-1. PLEASE REFERENCE THE CORRECTED SANITARY PLUMBING |
| | RISER DIAGRAM IN RED INK ON SHEET PR-1 FOR THE |
| | RESUBMITTAL: |
| | |
| | 1. THE MASTER BATH INDICATED ON SHEET PR-1 IS WRONG |
| | PER THE FOLLOWING. |
| | A. PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SEC. 106.3.5.4 RESIDENTIAL |
| | (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL |
| | WASTE, VENTS, TRAPS WITH SIZES, AND |
| | CLEANOUT LOCATIONS. (NOTE: NOT ALL TRAPS ARE SIZED ON |
| | SHEET PR-1) |
| | |
| | 3. THE DOUBLE BOWL KITCHEN SINK WITH DISHWASHER IS |
| | INDICATED ON SHEET PR-1 WRONG, AND DOES NOT REFLECT THE |
| | FLOOR PLAN. PLEASE REFERENCE THE CORRECTED DRAWING IN |
| | RED INK FOR THE RESUBMITTAL. |
| | |
| | 4. THE WASHING MACHINE ON SHEET PR-1 IS NOT INDICATED |
| | ON THE EXISTING FLOOR PLAN, THEREFORE IT IS ASSUMED THE |
| | WASHING MACHINE IS NEW. PER FBC-2004 PLUMBING, SECTIONS |
| | 406.3 AND 802.4 THE FOLLOWING IS REQUIRED. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE |
| | RESUBMITTAL. |
| | (C)708.9 ACCESS SHALL BE PROVIDED FOR ALL CLEANOUTS. |
| | PLEASE INDICATE THE WASHING MACHINE CLEANOUT FOUR FEET |
| | ABOVE FINNISH FLOOR (4' AFF). |
| | (D)PER FBC-2004 PLUMBING, SECTION |
| | 901.2.1 VENTING REQUIRED: EVERY TRAP AND |
| | TRAPPED FIXTURE SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING |
| | METHODS SPECIFIED IN THIS CHAPTER. (NOTE: THE WASHING |
| | MACHINE NEEDS A VENT.) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |