| 2006-10-26 15:51:00 | *** DENIED *** |
| | 1) PLEASE SUBMIT TWO COPYS OF THE ENERGY CAL'S. AND |
| | MANUAL J CAL'S. |
| | |
| | 2) 24X24 RETURN AIR GRILL IN LIVING ROOM IS SHOWN AS A |
| | SUPPLY AIR GRILL, PLEASE CORRECT. |
| | |
| | 3) RETURN AIR TRANSFER DUCT IN MASTER SUITE NEEDS TO BE |
| | 14", PLEASE CORRECT, SEE NOTE #4. |
| | |
| | 4) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |