| Plan Review Notes For Permit 06100547 |
| Permit Number |
06100547 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-26 13:49:21 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} LOCATE THE NEW PANEL ON THE DRAWING FLOOR PLAN SO | | | THAT COMPLIANCE WITH 230.70(A)(1) CAN BE REVIEWED. A | | | DISCONNECT MAY BE NEEDED AT THE METER FOR COMPLIANCE. | | | | | | 2} THE AIR HANDLER CIRCUIT IN THE PANEL SCHEDULE DOES | | | NOT INDICATE THE WATTAGE OF THE UNIT, BUT THE | | | CALCULATION INDICATES 7500 WATTS, IN WHICH CASE THE 80 | | | AMP BREAKER IS TOO LARGE PER 240.4, 310.16. | | | | | | 3} THE SPECS ON SHEET H1 INDICATE 10K HEAT , THE CALCS | | | HAVE 7500 LISTED. PLEASE CORRELATE AND ADJUST | | | CALCULATIONS AS NEEDED. | | | | | | 4}} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | | | 5} THE RECEPTACLE SPACING IN THE BATHROOMS MUST COMPLY | | | WITH 210.52(D). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|