Plan Review Notes
Plan Review Notes For Permit 06100547
Permit Number 06100547
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-26 13:49:21 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} LOCATE THE NEW PANEL ON THE DRAWING FLOOR PLAN SO
 THAT COMPLIANCE WITH 230.70(A)(1) CAN BE REVIEWED. A
 DISCONNECT MAY BE NEEDED AT THE METER FOR COMPLIANCE.
  
 2} THE AIR HANDLER CIRCUIT IN THE PANEL SCHEDULE DOES
 NOT INDICATE THE WATTAGE OF THE UNIT, BUT THE
 CALCULATION INDICATES 7500 WATTS, IN WHICH CASE THE 80
 AMP BREAKER IS TOO LARGE PER 240.4, 310.16.
  
 3} THE SPECS ON SHEET H1 INDICATE 10K HEAT , THE CALCS
 HAVE 7500 LISTED. PLEASE CORRELATE AND ADJUST
 CALCULATIONS AS NEEDED.
  
 4}} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 5} THE RECEPTACLE SPACING IN THE BATHROOMS MUST COMPLY
 WITH 210.52(D).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.