| Plan Review Notes For Permit 06100546 |
| Permit Number |
06100546 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-25 13:27:37 | BUILDING REVIEW CHECKLIST: | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 2- ACCORDING TO KEY PLAN SUBMITTED ALL OPENINGS WILL | | | HAVE ACCORDION SHUTTERS.PLEASE, IDENTIFY WHICH ONE IS | | | THE MEANS OF ESCAPE WHEN SHUTTERS ARE UP IN ORDER TO | | | COMPLY WITH SEC. R310.4 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 3- PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE FOR | | | PRODUCT APPROVAL SUBMITTED.GO TO | | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION. | | | | | | 4- PROVIDE COMPLETE INFORMATION IN THE INSTALLATION | | | SCHEDULE. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. SEE | | | ATTACHED SAMPLE COPY OF INSTALLATION SCHEDULE. COMPLETE | | | ALL INFORMATION THAT APPLIES. | | | | | | 5- CHECK PRODUCT APPROVAL FOR PROPER WAY OF MEASURING | | | SHUTTER SPAN. SHUTTER SPAN AND OPENING HEIGHT IS NOT | | | THE SAME DIMENSION.REVISE AS REQUIRED. | | | | | | 6-IF EDGE DISTANCE IS LESS THAN 3 1/2", THEN | | | CALCULATE ANCHOR SPACING ACCORDING TO CHART SHOWN AT | | | BOTTOM OFSHEET11 OF 14 OFACCORDION SHUTTERS | | | #05-195. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|