| Date |
Text |
| 2007-10-29 16:06:47 | REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REVISED |
| | PLANS: |
| | |
| | 1. SHEET P1 THE 1/2" GAS AND BTU LOAD FOR THE ADDED |
| | DRYER IS MISSING AND NEEDS TO BE INDICATED IN THE |
| | CLOUDED REVISION ON THE RESUBMITTED REVISION. PER |
| | *106.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS AND |
| | *401.1, SCOPE. |
| | |
| | 2. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: THE DRYER AND |
| | ITS BUT LOAD ARE MISSING FROM THE REVISION CLOUD. PER |
| | *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND |
| | *401.1, SCOPE. |
| | |
| | 3. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: THE GAS METER |
| | IS MISSING FROM THE GAS ISOMETRIC. PER *401.1, SCPOE. |
| | |
| | 4. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: THE TOTAL BTU |
| | LOAD NEEDS TO REVISED WITH THE ADDITION OF THE DRYER. |
| | PER *401.1, SCOPE. |
| | |
| | 5. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: PLEASE |
| | CLARIFY WHAT "PIPING MATERIALIS WARFLEX" IS. SHOULD IT |
| | READ AS "PIPING MATERIAL IS WARDFLEX"? AND PLEASE |
| | CLARIFY IF ALL PIPING MATERIAL IS BEING CHANGED TO |
| | WARDFLEX C.S.S.T. ON THE REVISION RESUBMITTAL. PLEASE |
| | CLEARLY IDENTIFY ALL PIPING MATERIALS BEING USED FOR |
| | EACH CUT SECTION OF PIPE. PER *106.1.1, INFORMATION ON |
| | COSTRUCTION DOCUMENTS AND *401.1, SCOPE. |
| | |
| | 6. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: PLEASE |
| | CORRELATE THE GAS ISOMETRIC, WHICH HAS THE ADDED SUM OF |
| | THE INDICATED CUT SECTIONS OF PIPE OF FIFTY EIGHT FEET |
| | (58') AND HAS THE REMOTE OUTLET BEING INDICATED AS |
| | SIXTYFIVE FEET (65'). PER *106.1.1, INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND *401.1, SCOPE. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |