| 2007-10-29 15:33:58 | REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE |
| | REVISED PLANS: |
| | |
| | 1. SHEET P1 SANITARY FLOOR PLAN DOES NOT REFLECT THE |
| | SANITARY ISOMETRIC ON SHEET P2: THE TRAP FOR THE MOP |
| | SINK IS MISSING. PER *701.1, SCOPE. |
| | |
| | 2. SHEET P2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN ON SHEET P1: THE WYE FITTING IS |
| | NOT INDICATED FOR THE WASHING MACHINE. PER *701.1, |
| | SCOPE. |
| | |
| | 3. SHEET P2 SANITARY ISOMETRIC RISER DIAGRAM: THE |
| | FOLLOWING NEEDS TO BE INDICATED FOR THE WASHING |
| | MACHINE. |
| | |
| | (A) PER *708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE |
| | INCH (3"). |
| | |
| | (B) PER *708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |