| 2006-11-02 10:08:52 | UNSAT |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE |
| | COMPLIANCE: |
| | |
| | 1. NOTE: THE SUBMITTED PLANS REFERENCE FBC-2001 |
| | PLUMBING, THIS IS WRONG THEY SHOULD REFERENCE FBC-2004 |
| | PLUMBING. |
| | |
| | 2.THE SANITARY RISER DIAGRAM ON SHEET P2 DOES NOT |
| | REFLECT THE FLOOR PLAN ON SHEETS A-1 AND P1. NOT ALL OF |
| | THE PLUMBING FIXTURES ARE INDICATED ON THE SANTARY |
| | RISER DIAGRAM. PLEASE REFERNCE SHEET A-1 IN THE |
| | GARAGE-6 WHERE THE 24" MOP SINK IS INDICATED. |
| | |
| | 3. 1. PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. (NOTE: PLEASE |
| | REFERENCE THE CORRECTED SHEETS P1 AND P2 WHERE THE MOP |
| | SINK ON SHEET A-1 IS ADDED TO SHEET P1 FLOOR PLAN AND |
| | SHEET P2 SANITARY RISER FOR THE RESUBMITTAL.) |
| | |
| | 4. THE BRANCH DRAIN PIPING TO THE WASHING MACHINE IS |
| | SIZED WRONG PER FBC-2004 PLUMBING SEC. 406.3. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. (NOTE: PLEASE REFERENCE THE CORRECTED SHEETS |
| | P1 AND P2 FOR THE RESUBMITTAL.) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |