| Date |
Text |
| 2006-11-02 10:16:09 | UNSAT |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW ON THE RESUBMITTAL TO MEET CODE COMPLIANCE: |
| | |
| | 1. NOTE THE SUBMITTED PLANS REFERENCE FBC-2001 FUEL |
| | GAS, TABLE 402(2), THIS IS WRONG THEY SHOULD REFERENCE |
| | FBC-2004 FUEL GAS TABLE 402.4 (2). |
| | |
| | 2. THEGAS PIPING INDICATED ON SHEET P1 FLOOR PLAN AND |
| | P2 GAS RISER MATERIAL IS INDICATED AS BEING 3/4" |
| | SCHEDULE 40 BLACK STEEL BEING INSTALLED IN A SLEEVE |
| | WITH THREE (3) 90 DEGREE TURNS.IT IS RECOMMENDED THAT |
| | THE GAS PIPE MATERIAL IN THE SLEEVE BE CHANGED TO 3/4" |
| | CSST {FBC-2004 FUEL GAS TABLE 404.4(14)} AND THAT THE |
| | SLEEVE BE INSTALLED WITH TWO (2) 90 DEGREE TURNS. |
| | PLEASE REFERENCE SHEETS P1 AND P2 INDICATING THESE |
| | CHANGES. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | 4. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |