| 2006-10-31 19:59:19 | ***** UNSAT **** |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING |
| | CODES AT A MINIMUM. |
| | 2002 NFPA-70 (NEC. |
| | 2002 NFPA-72 FAC. |
| | |
| | 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR |
| | SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE |
| | WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE |
| | IS A FIRE ALARM SYSTEM, THEN ONLY THENWOULD THEY BE |
| | SD. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS |
| | CALL FOR A NEW METER/MAIN COMBO, YET RISER SHOWS AND |
| | MAIN AND A NEW PANEL?? |
| | PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE |
| | CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS". |
| | PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE |
| | CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE |
| | MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO |
| | PANELS? |
| | PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC |
| | NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS |
| | TIME. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE |
| | AND CORRELATE WITH CONDUCTORS AND OCP. |
| | 240., 230.310 ETC. |
| | |
| | 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE |
| | EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO |
| | BE DONE. |
| | 110.9, 240.12 |
| | |
| | 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL |
| | MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE |
| | EXISTING. |
| | PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND |
| | CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE |
| | KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT |
| | THIS TIME. |
| | 240.4,310.16, 424.3B, 210.52, ETC. |
| | FBC ADMIN SECTION 106.3.5.4(8). |
| | |
| | 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE |
| | LOAD CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS |
| | ON PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED |
| | CIRCUITS WHICH ARE NOT FIGURED INTO THE LOAD CALCS. |
| | FRIG, GDO, OTHERS SHOWN ETC. |
| | 220.31B, 220.16, 210.11 |
| | |
| | 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S) |
| | CIRCUIT(S) PER 210.52D, 210.11C3 |
| | |
| | 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA |
| | PER 210.52B1, 210.11C1, 220.16 |
| | |
| | 10) NOTE: PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW |
| | LOAD. PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT |
| | AND 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE |
| | KNOW AS NO PANEL SCHEDULE WAS SUBMITTED, IT IS UNCLEAR |
| | OF THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED. |
| | 240.4, 310.16, ETC |
| | |
| | 11) NOTE: PLEASE SEE NOTE ON PLANS CALLS FOR AFCI |
| | PROTECTION FOR RECEPTS, WHEREAS THIS IS UNDER THE 1999 |
| | NEC REQUIREMENTS. PLEASE SEE WE ARE UNDER THE 2002 NEC |
| | AND REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN |
| | BEDRM/SLEEPING AREAS. |
| | PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS, |
| | FANS, LTS, RECEPTS ETC. |
| | |
| | 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122 |
| | |
| | 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING GROUNDING |
| | ELECTRODE SYSTEM FOR THE NEW SERVICE. |
| | 250.50 |
| | |
| | 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI |
| | PROTECTED. |
| | |
| | 15) NOTE: PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR |
| | TO CONTAIN NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT |
| | SPACING. |
| | PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR |
| | DO MEET ABOVE. |
| | |
| | 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA |
| | DESIGNATIONS ON ELECTRICAL PLANS. |
| | 106.1.2 |
| | |
| | 17) NOTE: PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND |
| | DISCONNECTS IF APPLICABLE. |
| | |
| | 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE |
| | SHOWN IN GARAGE BUT NOT IDENTIFIED? |
| | WASHER/ DRYER? |
| | |
| | ** PLEASE KNOW AT THIS TIME AS THERE ARE MANY ITEMS NOT |
| | YET SUBMITTED, THERE MAY BE NEW COMMENTS ON NEW PLANS |
| | SUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |