| Plan Review Notes For Permit 06100522 |
| Permit Number |
06100522 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-05 17:24:14 | -----------------DENIED--------------------- | | | | | | 1. HVAC NOTE 1: PLEASE REFERENCE FBC,M 2004, NOT 2001. | | | | | | 2. HVAC NOTE 12: PLEASE SHOW ON PLAN THE LOCATION OF | | | FIRE DAMPERS IN RATED FLOOR/CEILING ASSEMBLIES PER | | | FBC,M 607.8 | | | | | | 3. PLAN INDICATES 15X10 DUCT UP TO 2ND FLOOR BUT SHEET | | | CVR STATES THAT THE 2ND FLOOR HAS BEEN DELETED. PLEASE | | | CLARIFY PER FBC,M 106.1.1. | | | | | | 4. BATHROOM WITH 3 STALLS: PLAN SHOWS 150 CFM EXHAUST | | | AND 175 CFM SUPPLY. ALL AIR SUPPLIED TO SUCH SPACES | | | SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT | | | REQUIRED BY TABLE 403.3 PER FBC,M 403.2.1. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|