| Plan Review Notes For Permit 06100522 |
| Permit Number |
06100522 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-06 14:43:57 | ***DENIED*** | | | | | | 1) BASED ON OCCUPANT LOAD CALCULATIONS FOR SOUTH | | | CHAPEL, PLEASE CLARIFY IF ALL AREAS INCLUDING THE NORTH | | | CHAPEL UNDER ROOF ARE DEFINED AS (1) BUILDING. | | | | | | 2) PLEASE ADD NOTE TO PLANS THAT OCCUPANT LOAD WILL | | | REMAIN AS DOCUMENTED, THEREBY NOT INITIATING ANY | | | REQUIREMENTS FOR FIRE ALARM AND FIRE SPRINKLER SYSTEMS, | | | AS WELL AS INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 3) PLEASE SHOW REQUIRED LOCATION OF 2A-10B,C RATED FIRE | | | EXTINGUISHERS THAT SHALL BE MOUNTED SO AS NOT TO EXCEED | | | 75' TRAVEL DISTANCE. | | | | | | 4) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|