Plan Review Notes
Plan Review Notes For Permit 06100522
Permit Number 06100522
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-24 08:17:04****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT YET
 BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED BEFORE DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE OLD CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE THE 2004 FBC FOR ALL
 TRADES AND THE 2002 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC
 2002 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
  
 ** PLEASE SEE SOME AREAS OF PLANS WHICH REFLECT THE
 2001 FBC AND THE 2005 NFPA-70.
  
 2) NOTE:PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF
 ALL FIXTURES AND CORRELATE WITH PLANS.
 PLEASE ALSO SEE THE 2004 FBC CHAPTER 13 FOR THE POWER
 ALLOWANCES PERMITTED AND PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW.
 PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND CONTROLS
 WHERE APPLICABLE. THE SECTION OF 13-415.1.ABC.1.1 DOES
 NOT SEEM TO APPLY AS THE SQ FT IS LESS THAN 5K SQ FT.
 PLEASE KNOW HOWEVER ENERGY CALCULATIONS PER 13-415.AB.1
 ARE REQUIRED TO VERIFY FOR NEW ELECTRICAL AND
 MECHANICAL BEING INSTALLED.
 FBC 106.1.2
  
 3) NOTE: PLEASE INCLUDE NEW LIGHTING FOR STAIR AREAS TO
 MEET NFPA-101 7.8 AND 7.9.
 PLEASE INCLUDE ANY EGRESS STAIR AREAS TO THE PUBLIC
 RIGHT OF WAY AND EGRESS PATHS.
 PLEASE KNOW THE STAIR AREAS ARE REQUIRED TO HAVE A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND ARE PERMITTED
 TO GO TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. PLEASE
 SUBMIT PHOTO-METRICS FOR REVIEW.
 NFPA-101 7.8.1.3, 7.9.2.2.
 FBC 106.1.2
  
 4) NOTE: PLEASE LABEL ALL PANELS AND SERVICE EQUIPMENT
 ON PLANS.
 THERE ARE SEVERAL NOTES ON PLANS WHICH MENTIONS
 EXISTING, HOWEVER THIS WORK WAS NOT DONE UNDER THE
 PRIOR PERMIT AS THE ELECTRICAL PERMIT FOR THIS SCOPE
 WAS NEVER ISSUED AND NO RECORD OF ANY INSPECTIONS WAS
 DONE.
 PLEASE INDICATE THIS ELECTRICAL WORK AS NEW UNLESS THIS
 WAS DONE BEFORE 02.?
 PLEASE SHOW AND LABEL ALL EQUIPMENT. PLEASE SEE SOME
 PANELS ARE SHOWN IN AREAS WHICH ARE CONSIDERED CLOSETS/
 STORAGE ROOM AREAS.
 PLEASE SEE 110.26, 408.7, 240.24 ETC
 PLEASE SEE SHOW WHERE THE *WIRE-WAY* IS LOCATED.?
 PLEASE SEE THE AREA OF STAIRS OUTSIDE APPEAR TO BE
 LOCATED IN FRONT OF THE METER AS NOTED ON PLANS. PLEASE
 COMPLETE THE RISER AS THE RISER DOES NOT INCLUDE THE
 METER.
 PLEASE SHOW THE LOCATION OF THE SERVICE MAIN. PLEASE
 SEE THERE IS A NOTE ON PLANS *NOTE A* WHICH MENTIONS TO
 SEE SHEET C-1 FOR THESE ITEMS YET THERE WAS NO SHEETS
 C-1 IN SET?
 PLEASE INCLUDE ALL TAPPED CONDUCTORS TO EQUIPMENT.
 PLEASE SHOW ALL EQUIPMENT FOR A/C UNITS. (NOTED AS
 EXISTING) HOWEVER AS PLANS SEEM TO INDICATE THE LEVEL
 OF REWIRED AND ALTERATION WHICH IS INCLUDING COMPLETE
 REWIRE FOR MOST, PLEASE INCLUDE WHAT IS EXISTING OF
 THIS SERVICE WHICH MEETS THE CURRENT CODE.
 240.4, 310.16, 110.26, 240.21, 440.11,ETC.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE VERIFY THE LOAD CALCULATIONS AS SHOWN
 AS THE NEW LOADS BEING ADDED ARE NOT SHOWN PER NEC FOR
 THE LOADS REQUIRED. CONTINUOUS LOADS AT 125%. PLEASE
 SEE LOADS ARE ONLY SHOWN AS CONNECTED LOADS ON PANEL
 SCHEDULE.
 PLEASE CLARIFY HOW LOADS ARE DERIVED.
 PLEASE SEE 220.10,220.11,220.3,220.13, ETC.
 215.3, 230.42.
 PLEASE SEE AS THE SERVICE SHOWN HAS LOAD AT 196+ AMPS,
 THERE IS NOT ROOM FOR FUTURE
 WIRING/EXPANSION/LOAD/PLANNING.
 PLEASE KNOW THAT AS THE LOAD IS BEING SHOWN SO CLOSE TO
 THE MAXIMUM LOAD ON SERVICE THE SERVICE WILL BE
 REQUIRED TO BE INCREASED TO A MINIMUM OF 225AMPS.
 PLEASE KNOW ONCE ALL LOADS ARE SHOWN AND DECLARED THE
 FINAL REVIEW OF THIS WILL BE DONE AT THAT TIME. 90.8,
 90.4.
  
 6) NOTE: PLEASE INCLUDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE SEE
 THERE ARE SEVERAL ITEMS ON PLANS WHICH DO NOT INDICATE
 ANY CIRCUITING. PLEASE EXPLAIN THE LOWER CASE *A*,*C*
 WHICH IS BEING SHOWN BEHIND SOME OF THE CIRCUITS?
 PLEASE SEE 408.4, 310.16, AND 240.4 AS MANY ITEMS NEED
 TO BE VERIFIED.
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 FBC 106.1.2
  
 7) NOTE: PLEASE ALSO INCLUDE HOW AND WHERE LIGHTING FOR
 SANCTUARY IS AND HOW MANY OF THE OTHER LIGHTS ARE GOING
 TO BE CONTROLLED. PLEASE SEE SOME AREAS WHICH DO NOT
 SHOW LIGHTS OR CONTROLS?
 PLEASE CLARIFY THE NUMERICAL DESIGNATIONS AND LETTERS
 AT SWITCH LOCATIONS?
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE BE SURE ALL BRANCH CIRCUIT CONDUCTORS
 ARE SHOWN AND MEET 310.16, 240.4
 FBC 106.3.5.1.2.
  
 9) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT HAS
 EXPIRED PER FS713.13(2). WILL ONLY NEED TO BE SUBMITTED
 ONCE PERMIT IS ISSUED.
  
 ** AS ELECTRICAL SCOPE OF WORK WAS NEVER COMPLETED,
 PERMITTED, OR INSPECTED UNDER PREVIOUS PLANS, CAN NOT
 REFERENCE BACK TO WORK NOT DONE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]