| 2006-10-25 08:49:46 | *** PROVISO *** | | | 1) IF NO FIRE DAMPERS ARE LOCATED IN THE TWO HEAT DUCTS | | | WERE PENETRATING THE FIRE WALLS, THEN FIRE DAMPERS NEED | | | TO BE INSTALLED, PER 2004 FBC/M 607.5.3, OR COMPLY WITH | | | 2004 FBC/M | | | 607.5.3 EXCEPTIONS. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|