| 2006-10-27 11:30:01 | UNSAT |
| | REFERENCE: FBC-2004 SEC. 424.2 OR RFBC-2004 SEC. R4101 |
| | SWIMMING POOLS |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAIALS, OR SUBMITTALS TO |
| | REFLECT THE FOLLOWING INFOMATION REQUIRED FOR PLUMBING |
| | PLAN REVIEW: |
| | |
| | 1) COMPLY WITH FBC-2004 SEC 424.2, OR |
| | FBCR-2004 SEC R4101 PRIVATE SWIMMING |
| | POOLS. (ADD TO NOTES) |
| | |
| | 2) FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPER- ATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER.(DETAIL |
| | REQUIRED OR ADD MAKE AND MODEL NUMBER TO PRINTS) |
| | |
| | 3) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| | R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | |
| | 4) FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (ADD TO NOTES) |
| | |
| | 5) FBC-2004 SEC. 424.2.13.2, OR |
| | FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING.(ADD TO |
| | NOTES) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |