| Date |
Text |
| 2006-12-17 12:29:47 | *** UNSAT 2ND REVIEW*** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | STILL NEEDS TO BE CLARIFIED OR ADDRESSED. |
| | |
| | ** PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED PLANS |
| | FOR REVIEW FOR SCOPE OF WORK BEING PERFORMED. PLEASE |
| | SEE THE COMMENTS BELOW ARE BASED ON THE PLANS |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE PLANS MISSING CIRCUITING AS |
| | PREVIOUSLY REQUESTED. PLEASE SEE THAT THIS CIRCUITING |
| | SHALL CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S) |
| | PLEASE SEE SCOPE OF WORK PREVIOUSLY SUBMITTED INDICATED |
| | WALL BEING CLOSED IN TO CREATE SEPARATE SPACES, HOWEVER |
| | THESE PLANS SUBMITTED NOW INDICATE ANEW TENANT |
| | SEPARATION WALL AT A DIFFERENT LOCATION? |
| | PLEASE PROVIDE CIRCUITING ON HOW THE OTHER EXISTING |
| | SPACE IS BEING FED. |
| | PERMIT DESCRIPTION INDICATES INSTALLATION OF NEW WALL |
| | BETWEEN TWO SPACES. |
| | PLEASE SEE FBC CHAPTER 13 IF NEW TENANT SPACE IS BEING |
| | CREATED. |
| | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.2.1.ABC.1 |
| | 408.4, 310.16, |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 . |
| | PLEASE KNOW THERE IS MISSING INFORMATION WHICH CAN NOT |
| | DETERMINE CODE COMPLIANCE AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE SEE PANEL WHICH IS BEING SHOWN IN WHAT |
| | APPEARS TO BE A STORAGE CLOSET. |
| | PLEASE SEE 110.26,408.7, 240.24, AS THIS IS NOT |
| | PERMITTED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |