| 2006-10-24 12:53:12 | *****UNSAT ******** |
| | |
| | 1) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE DONE ABY A |
| | LICENSED PROFESSIONAL UNDER FS 481 OR 471. PLEASE SEE |
| | HOME DESIGN COMPANY MAY NOT DESIGN SCOPE OF WORK PER |
| | 481.229(1)(C). |
| | |
| | PLEASE SEE PLANS ALSO CONTAIN A PHOTO-COPY OF WHAT |
| | APPEARS TO BE A SIGNATURE FROM AN ENGINEER AND ALSO |
| | CONTAINS A TITLE BLOCK FOR THE SAME SAID DESIGNER, |
| | HOWEVER PLANS ARE SIGNED, DATED OR SEALED BY THE SAID |
| | DESIGNER AS REQUIRED UDNER FS 471.025, FAC |
| | 61G15-23.002 |
| | |
| | 2) NOTE:PLEASE SEE NOW THAT THE SPACE IS BEING SLIT |
| | UP INTO TWO SEPARATE SPACES, PLEASE INDICATE THE |
| | CIRCUITINGS FOR THE NEW ELECTRICAL AS SHOWN AND HOW |
| | THESE WILL BE SEPARATED. |
| | ONE SPACE PANEL MAY NOT FEED ANOTHER. |
| | 210.25.408.4, 310.16 ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |