Plan Review Notes
Plan Review Notes For Permit 06100489
Permit Number 06100489
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-24 12:53:12*****UNSAT ********
  
 1) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE DONE ABY A
 LICENSED PROFESSIONAL UNDER FS 481 OR 471. PLEASE SEE
 HOME DESIGN COMPANY MAY NOT DESIGN SCOPE OF WORK PER
 481.229(1)(C).
  
 PLEASE SEE PLANS ALSO CONTAIN A PHOTO-COPY OF WHAT
 APPEARS TO BE A SIGNATURE FROM AN ENGINEER AND ALSO
 CONTAINS A TITLE BLOCK FOR THE SAME SAID DESIGNER,
 HOWEVER PLANS ARE SIGNED, DATED OR SEALED BY THE SAID
 DESIGNER AS REQUIRED UDNER FS 471.025, FAC
 61G15-23.002
  
 2) NOTE:PLEASE SEE NOW THAT THE SPACE IS BEING SLIT
 UP INTO TWO SEPARATE SPACES, PLEASE INDICATE THE
 CIRCUITINGS FOR THE NEW ELECTRICAL AS SHOWN AND HOW
 THESE WILL BE SEPARATED.
 ONE SPACE PANEL MAY NOT FEED ANOTHER.
 210.25.408.4, 310.16 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  