| 2006-10-26 07:15:57 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE INCLUDE THE FOLLOWING MIN CODES WHICH |
| | ARE RELEVANT TO DESIGNA DN SCOPE PF WORK ON PLANS. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASEINDICATE THE "EQUIPMENT GROUNDING |
| | CONDUCTOR: FOR THE NEW FEEDERS BEING PULLED FROM |
| | EXISTING MAIN AT SERVICE. |
| | 250.110,250.24B , 250.122 ETC |
| | |
| | 3) NOTE: PLEASE SEE THAT THE ROOMS/OFFICE WHERE NEW |
| | ELECTRICAL LIGHTING CONTROLS/LAYOUTS WORK IS BEING WILL |
| | BE REQUIRED TO HAVE OCCUPANT SENSOR TYPE DEVICES TO BE |
| | INSTALLED. 13-415.1.ABC.1.2 2004 FBC. |
| | |
| | 4) NOTE: PLEASE VERIFY THE VOLTAGE COMING INTO SPACES ? |
| | IT WAS THOUGHT THE VOLTAGE WAS 277/480 COMING INTO |
| | SPACES ? PLEASE ONLY VERIFY. IF INDEED 120/208V THIS IS |
| | OK. |
| | |
| | 5) NOTE: PLEASE CORRELATE CIRCUITS ON PANEL SCHEDULE |
| | WIHT ROOMS /AREAS ON PLANS,. IE: OFFICE 102 RECEPT, LT |
| | RECEPTION AREA ,, ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |