2006-12-08 12:22:25*****DENIED*****
  
  
  
 1.THE SUITE NUMBER LOCATED IN THE TITLE BLOCK OF THE
 SUBMITTED PLAN IS INCORRECT.SUITE 200 SHOULD BE USED
 NOT 100.
  
 2.NFPA 101 - 2003 EDITION - AND THE FLORIDA FIRE
 PREVENTION CODE -2004 EDITION- SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION ACTIVITIES SHALL COMPLY WITH NFPA 241.
  
 4.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, DUST,
 AND DEBRIS SHALL BE REMOVED FROM THE STRUCTURE DAILY
 AND ITS IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 5.INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS AND
 EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 6.IF THE SCOPE OF THE WORK REQUIRES MODIFICATION OF
 THE SPRINKLER SYSTEM, SEPARATE PLANS AND PERMIT ARE
 REQUIRED.
  
 7.THE SUITE NUMBER IS MISSING IN THE TITLE BLOCK ON
 DRAWING FA 0.1 AND FA 1.0.
  
 8.ALL PLANS SUBMITTED UNDER THE MASTER SHALL HAVE THE
 PROPER SEAL AND SIGN AS PER FLORIDA ADMISTRATIVE
 CODES.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  