Plan Review Notes
Plan Review Notes For Permit 06100473
Permit Number 06100473
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-27 20:28:58*** UNSAT ***
  
  
 *** PLEASE SEE PLANS CALL FOR SUITE #100 , YET PERMIT
 APPLICATION HAS SUITE #200. PLEASE CORRELATE AND
 CONTACT THE ADDRESSING REVIEWER AS THESE DO NOT
 CORRELATE AND THIS REVIEWER HAS GRANTED AN EXTENSIONOF
 #200. IF INDEED SUITE #200, PLEASE ADJUST ALL TITLE
 BLOCKS AS REQUIRED PER FAC 61G16, 61G15
  
 1) NOTE: PLEASE BE SURE PLANS LIST THE CURRENT RELEVANT
 CODES ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101.
 PLEASE ALSO LIST THE 2004 FBC.
  
 2) NOTE: PLEASE CLARIFY THE LOADS AS SHOWN AND ANY
 CONTINUOUS LOADS ARE ALREADY FIGURED AT 125% OR ADJUST
 AND SHOW AS NEEDED.
 215.3,230.42 ETC.
  
 3) NOTE: PLEASE SEE NEC 605.
 PLEASE STATE THE FOLLOWING ON PLANS.
 (C) RECEPTACLE OUTLETS, MAXIMUM. INDIVIDUAL PARTITIONS
 OR GROUPS OF INTERCONNECTED INDIVIDUAL PARTITIONS SHALL
 NOT CONTAIN MORE THAN THIRTEEN 15-AMPERE, 125-VOLT
 RECEPTACLE OUTLETS.
 (D) MULTIWIRE CIRCUITS, NOT PERMITTED. INDIVIDUAL
 PARTITIONS OR GROUPS OF INTERCONNECTED INDIVIDUAL
 PARTITIONS SHALL NOT CONTAIN MULTIWIRE CIRCUITS. PLEASE
 ALSO STATE ALL FURNITURE SHALL BE IN PLACE OR WILL BE
 REQUIRED TO BE DONE UNDER A SEPARATE PERMIT . PERMIT
 MUST BE APPLIED FOR BEFORE FINAL OF UNIT ONLY IF
 FURNITURE IS NOT INSTALLED BEFORE FINAL AND DURING THIS
 CONSTRUCTION.
  
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
 ** PLEASE ALSO KNOW, DU E TO SCOPE OF WORK AT THIS
 TIME, FBC 2004 CHAPTER 13 DOES NOT APPLY BASED ON
 FACTORS AS SHOWN, HOWEVER IF SCOPE DOES INCREASE,
 CHAPTER 13 REQUIREMENTS MAY BE REQUIRED.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]