| Plan Review Notes For Permit 06100385 |
| Permit Number |
06100385 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-04 15:43:58 | NOTE REFERENCE GEN/RES PERMIT #06061608 | | | | | | | | | ****************PROVISO**************** | | | A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATORS: | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. | | | B} PER FBC-2004 FUEL GAS, SECTION 408.4 SEDIMENT TRAP | | | SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT SHUTOFF | | | VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS | | | PRACTICAL. |
|