2006-10-25 15:49:271. STAIRWELL PRESSURIZATION SYSTEMS HAVE RECENTLY
 EXPERIENCED PROBLEMS WORKING CORRECTLY OR WORKING AT
 ALL.
 2. STAIRWELL PRESSURIZATION SYSTEMS SINCE INOPERATIVE
 OR HAVING DIFFICULTY WORKING SHALL THEREBY COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, SECTION 7.2.3.9. 3. ALL
 REQUIRED EQUIPMENT RELATED TO THE PRESSURIZATION SYSTEM
 SHALL BE VERFIED TO BE INSTALLED PROPERLY. 4. ALL
 SYSTEMS AFTER INSTALLATION SHALL BE PRE-TESTED PRIOR TO
 CALLING IN FOR INSPECTION.
 5. ALL EQUIPMENT SHALL BE INSPECTED, TESTED, AND
 APPROVED PRIOR TO APPROVAL WITH CITY MECHANICAL AND
 FIRE PREVENTON BUREAU.
 6. ALL EXIT DOORS SHALL BE FISH-SCALED TO ENSURE THAT
 ABOVE NORMAL OPERATING PRESSURE WILL NOT EXIST WHEN
 THESE SYSTEMS ARE OPERATING.
 7. THESE CRITICAL LIFE SAFETY SYSTEMS SHALL BE VERIFIED
 THAT THEY ARE CONNECTED TO EMERGENCY POWER.
 8. STACK EFFECTS SHALL BE CONSIDERED FOR HIGH-RISE
 BUILDING.
 9. PLEASE ADD ALL OF THE APPROPRIATE NOTES TO THE
 REVISED PLANS.
  
 APPROVED PROVISO
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709