| Notes |
| Date |
Text |
| 2006-10-25 15:49:27 | 1. STAIRWELL PRESSURIZATION SYSTEMS HAVE RECENTLY | | | EXPERIENCED PROBLEMS WORKING CORRECTLY OR WORKING AT | | | ALL. | | | 2. STAIRWELL PRESSURIZATION SYSTEMS SINCE INOPERATIVE | | | OR HAVING DIFFICULTY WORKING SHALL THEREBY COMPLY WITH | | | NFPA 101, THE LIFE SAFETY CODE, SECTION 7.2.3.9. 3. ALL | | | REQUIRED EQUIPMENT RELATED TO THE PRESSURIZATION SYSTEM | | | SHALL BE VERFIED TO BE INSTALLED PROPERLY. 4. ALL | | | SYSTEMS AFTER INSTALLATION SHALL BE PRE-TESTED PRIOR TO | | | CALLING IN FOR INSPECTION. | | | 5. ALL EQUIPMENT SHALL BE INSPECTED, TESTED, AND | | | APPROVED PRIOR TO APPROVAL WITH CITY MECHANICAL AND | | | FIRE PREVENTON BUREAU. | | | 6. ALL EXIT DOORS SHALL BE FISH-SCALED TO ENSURE THAT | | | ABOVE NORMAL OPERATING PRESSURE WILL NOT EXIST WHEN | | | THESE SYSTEMS ARE OPERATING. | | | 7. THESE CRITICAL LIFE SAFETY SYSTEMS SHALL BE VERIFIED | | | THAT THEY ARE CONNECTED TO EMERGENCY POWER. | | | 8. STACK EFFECTS SHALL BE CONSIDERED FOR HIGH-RISE | | | BUILDING. | | | 9. PLEASE ADD ALL OF THE APPROPRIATE NOTES TO THE | | | REVISED PLANS. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 |
|