| 2006-10-16 16:17:59 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN |
| | REVIEW: |
| | |
| | 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING, ELECTRICAL, AND GAS |
| | FOR |
| | THE GENERATOR LOCATION. PLEASE SEE THE ATTACHED PERMIT |
| | INFORMATION INDICATING THAT A GEN/RES PERMIT HAS NOT |
| | BEEN APPLIED FOR. |
| | |
| | 2.THE WATER HEATER LOCATION AND THE TYPE ON THE |
| | APPROVED MASTER PERMIT #05070588 ON SHEET 2-5ARE |
| | DIFFERENT FROM THE GAS PERMIT APPLICATION. THE TYPE AND |
| | LOCATION ON THE APPROVED SET INDICATES A 60 GAL. WATER |
| | HEATER LOCATED OFF THE POWDER ROOM. THE GAS PERMIT |
| | APPLICATION INDICATES AN EXTERNAL TANKLESS WATER |
| | HEATER. PLEASE NOTE A REVISION FOR THE MASTER WILL BE |
| | REQUIRED IFDIFFERENT FROM APPROVED SET. |
| | |
| | 3.THE FIRE PLACE MANUFACTURER SHEETS SUBMITTED FOR THE |
| | GAS PERMIT APPLICATION ARE DIFFERENT FROM THE APPROVED |
| | MASTER PERMIT #05070588 ON SHEET 2-5.PLEASE REFERENCE |
| | THE ATTACHED APPROVED FIRE PLACE MANUFACTURER SHEET |
| | FROM THE MASTER PERMIT #05070588. PLEASE NOTE A |
| | REVISION FOR THE MASTER WILL BE REQUIRED IF FIRE PLACE |
| | IS DIFFERENT FROM THE APPROVED FIRE PLACE. |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR (COOK TOP) TO VERIFY |
| | COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. PLEASE SUBMIT |
| | MANUFACTURE SHEETS INDICATING APPLIANCE (COOK TOP) IS |
| | LISTED AND LABELED. |
| | |
| | END OF COMMENTS: |
| | |