| Plan Review Notes For Permit 06100279 |
| Permit Number |
06100279 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-16 14:38:39 | DENIED; | | | | | | 1.(SECOND REQUEST) SECONDARY ROOF DRAINS SHALL | | | DISCHARGE IN A LOCATION WHICH WOULD NORMALLY BE | | | OBSERVED BY THE BUILDING OCCUPANTS | | | OR MAINTENANCE PERSONNEL. SEE FBC-2004 PLUMBING | | | SECTION 1107.2. (NOT VISIBLE AS DRAWN) | | | 2. DETAIL "B" ON SHT. A3.0; | | | A. SHOW SIZE AND MATERIAL TYPE | | | OF PIPE, SECONDARY DRAIN. | | | B. SIZE EMERGENCYSCUPPER | | | PER TABLE 1106.7 PLBG. | | | C. SHOW HIGHT ABOVE ROOF DRAIN | | | TO COMPLY WITH FBC-2004 BUILDING | | | SECTION 1503.4.3. | | | ALL COMMENTS ARE SECOND REQUESTS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|