| 2006-11-29 15:51:31 | BUILDING PLAN REVIEW |
| | PERMIT:06100279 |
| | ADD:319 CLEMATIS ST. |
| | CONT: ANDOVER CONSTRUCTION |
| | TEL: (561)638-4993 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | |
| | 1)THE VALUE ON THE PERMIT HAS NOT BEING CHANGED. IF A |
| | FAIR MARKET VALUE IS NOT APPLIED, WE WILL CALCULATE THE |
| | VALUE USING MARSHALL-SWIFT. ICC (BVD), AND MEANS COST |
| | ANALYSIS SERVICES PER 108.3 FBC*. |
| | |
| | 2)WHAT TYPE OF MATERIAL WILL BE USED TO INSTALL THE |
| | ROOF TILES? IF POLYFOAM WILL BE USED SUBMIT THE PRODUCT |
| | APPROVAL FOR THE POLYFOAM AND MARK CLEARLY ON THE |
| | PRODUCT APPROVAL THE TABLE WHICH WILL BE USED. THE |
| | PRODUCT APPROVAL FOR THE MODIFIED BITUMEN ROOF NEEDS TO |
| | INCICATE WHICH SYSTEM WILL BE USED. EITHER CIRCLE OR |
| | HI-LIGHT THE APPLICATION TO BE USED. |
| | |
| | 3)FBC 703.4THE TESTS INDICATED IN SECTIONS 703.4.1 |
| | AND 703.4.2 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF |
| | BUILDING MATERIALS AS SET FORTH IN SECTIONS 602.2 , |
| | 602.3 AND 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. |
| | THE TERM ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME |
| | SPREAD CHARACTERISTICS OF INTERIOR FINISH OR TRIM |
| | MATERIALS. A MATERIAL SHALL NOT BE CLASSIFIED AS A |
| | NONCOMBUSTIBLE BUILDING CONSTRUCTION MATERIAL IF IT IS |
| | SUBJECT TO AN INCREASE IN COMBUSTIBILITY OR FLAME |
| | SPREAD BEYOND THE LIMITATIONS HEREIN ESTABLISHED |
| | THROUGH THE EFFECTS OF AGE, MOISTURE OR OTHER |
| | ATMOSPHERIC CONDITIONS. A DIFFERENT TYPE OF MATERIAL |
| | WILL HAVE TO BE USED INSTEAD OF THE |
| | FIRE-RETARDANT-TREATED PLYWOOD. |
| | |
| | 4) 704.2.1 TYPE I AND II CONSTRUCTION. |
| | PROJECTIONS FROM WALLS OF TYPE I OR II CONSTRUCTION |
| | SHALL BE OF NONCOMBUSTIBLE MATERIALS OR COMBUSTIBLE |
| | MATERIALS AS ALLOWED BY SECTIONS 1406.3 AND 1406.4 . |
| | |
| | 5)704.11.1 PARAPET CONSTRUCTION. |
| | PARAPETS SHALL HAVE THE SAME FIRE-RESISTANCE RATING AS |
| | THAT REQUIRED FOR THE SUPPORTING WALL, AND ON ANY SIDE |
| | ADJACENT TO A ROOF SURFACE, SHALL HAVE NONCOMBUSTIBLE |
| | FACES FOR THE UPPERMOST 18 INCHES (457 MM), INCLUDING |
| | COUNTERFLASHING AND COPING MATERIALS.THE TREATED |
| | PLYWOOD IS CONSIDERED COMBUSTIBLE UNDER CERTAIN |
| | CONDITIONS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |