| Plan Review Notes For Permit 06100279 |
| Permit Number |
06100279 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-02 14:16:01 | DENIED; | | | NO INFORMATION FOR ROOF DRAINS OR SECONDARY EMERGENCY | | | DRAINS SHOWN ON PLANS; | | | THE FOLLOWING INFORMATION IS REQUIRED | | | SO A PLUMBING PLAN REVIEW CAN BE DONE. | | | A) TYPE OF MATERIAL TO BE USED. | | | B) LIST DRAINS TO BE USED. | | | C) SIZE THE RAIN DRAINS AND LEADERS. SHOW ROOF | | | AREA AND PARAPET AREA PER FBC-2004 PLUMBINGCHAPTER | | | 11. | | | D) SHOW CALCULATIONS FOR SECONDARY DRAINS. | | | HEIGHT ABOVE ROOF. | | | E)SECONDARY DRAINS SHALL TERMINATE IN A | | | VISIBLE LOCATION. PLAN SHOW DRAIN ENDS BEFORE THE EDGE | | | OF ROOF. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|