2006-11-02 14:16:01DENIED;
 NO INFORMATION FOR ROOF DRAINS OR SECONDARY EMERGENCY
 DRAINS SHOWN ON PLANS;
 THE FOLLOWING INFORMATION IS REQUIRED
 SO A PLUMBING PLAN REVIEW CAN BE DONE.
 A) TYPE OF MATERIAL TO BE USED.
 B) LIST DRAINS TO BE USED.
 C) SIZE THE RAIN DRAINS AND LEADERS. SHOW ROOF
 AREA AND PARAPET AREA PER FBC-2004 PLUMBINGCHAPTER
 11.
 D) SHOW CALCULATIONS FOR SECONDARY DRAINS.
 HEIGHT ABOVE ROOF.
 E)SECONDARY DRAINS SHALL TERMINATE IN A
 VISIBLE LOCATION. PLAN SHOW DRAIN ENDS BEFORE THE EDGE
 OF ROOF.