2006-11-01 15:09:17BUILDING PLAN REVIEW
 PERMIT:06100279
 ADD:319 CLEMATIS ST.
 CONT:
 TEL: (561)638-4993
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
  
 1)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R. .
  
 2)F.S489.113(3)A GENERAL CONTRACTOR SHALL
 SUB-CONTRACT ALLELECTRICAL, MECHANICAL, PLUMBING,
 ROOFING
 SHEET METAL,SWIMMING POOL, AND AIR-CONDITIONING WORK,
 UNLESS SUCH CONTRACTOR HOLDS A STATE CERTIFICATE OR
 REGISTRATION IN THE RESPECTIVE TRADE CATEGORY.
 A LICENSE ROOFING CONTRACTOR WILL HAVE TO DO ALL THE
 ROOFING WORK AT THIS PROJECT.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE.OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3FBC*.
  
 4)1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
  
 5)703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 "NONCOMBUSTIBLE" DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
  
 6)602.2 TYPES I AND II.
 TYPE I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS.
  
 7)THE NAIL SPACING FOR THE ROOF SHALL BE IN
 ACCORDANCE WITH TABLE2304.9.1 (Q).
  
 8)61G15-23.001.(1)THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AMENDED IT SEALS RULE EFFECTIVE FEBRUARY5,
 2004 TO ALLOW EMBOSSING SEALS MADE OF MATERIALS OTHER
 THAN METAL AND THE SAME TIME CLEAND UP THE APPERANCE OF
 THE SEAL BY ELEMITATINS OBLOLETE CONTENT AND CHANGING
 THE "CERTIFICATE" TO "LICENSE.
 NOTE: SHEET S1. THE SEALSTILL HAS THE WORD
 "CERTIFICATE" .THIS TYPE OF SEAL EXPIRED DECEMBER 31,
 2005. THE NEW SEAL SHALL HAVE THE WORD "LICENSE".
  
 9) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITTING
 BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 SUBMIT THE MATCHING STATE COVER SHEET WITH THE FL# FOR
 EACH PRODUCT APPROVAL. SEE FLORIDABUILDING.ORG FOR
 ADDITIONAL INFORMATION.
  
 10) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _XX__ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _XX__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 11)SHEET A2.0INDICATE THE SCUTTLE HATCHES DETAILS
 IS ON SHEET S-2, HOWEVER, THERE IS NO SHEET S-2. EITHER
 SUBMIT SHEET S-2 OR REVISED THE DRAWINGS TO REFLECT THE
 CORRECT INFORMATION.
  
 12)WHAT IS THE SLOPE OF THE NEW ROOF OVERHANG.
 INDICATE ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  