| 2006-11-01 15:09:17 | BUILDING PLAN REVIEW |
| | PERMIT:06100279 |
| | ADD:319 CLEMATIS ST. |
| | CONT: |
| | TEL: (561)638-4993 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW1ST |
| | ACTION: DENIED |
| | |
| | |
| | 1)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) OCCUPANT LOAD |
| | ) FLOOD ZONE |
| | ) FLOOD ELEVATION |
| | )L.O.M.R. . |
| | |
| | 2)F.S489.113(3)A GENERAL CONTRACTOR SHALL |
| | SUB-CONTRACT ALLELECTRICAL, MECHANICAL, PLUMBING, |
| | ROOFING |
| | SHEET METAL,SWIMMING POOL, AND AIR-CONDITIONING WORK, |
| | UNLESS SUCH CONTRACTOR HOLDS A STATE CERTIFICATE OR |
| | REGISTRATION IN THE RESPECTIVE TRADE CATEGORY. |
| | A LICENSE ROOFING CONTRACTOR WILL HAVE TO DO ALL THE |
| | ROOFING WORK AT THIS PROJECT. |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE.OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3FBC*. |
| | |
| | 4)1406.2.2 ARCHITECTURAL TRIM. |
| | IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION |
| | THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM) |
| | IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS |
| | SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE |
| | PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT |
| | COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL |
| | COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD |
| | COMPLYING WITH SECTION 2303.2 FOR EXTERIOR |
| | INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN |
| | EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION |
| | DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL |
| | TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE |
| | GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED |
| | NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE |
| | WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE |
| | BRACKETS. |
| | |
| | 5)703.4 NONCOMBUSTIBILITY TESTS. |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | "NONCOMBUSTIBLE" DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | |
| | 6)602.2 TYPES I AND II. |
| | TYPE I AND II CONSTRUCTION ARE THOSE TYPES OF |
| | CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN |
| | TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS. |
| | |
| | 7)THE NAIL SPACING FOR THE ROOF SHALL BE IN |
| | ACCORDANCE WITH TABLE2304.9.1 (Q). |
| | |
| | 8)61G15-23.001.(1)THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS AMENDED IT SEALS RULE EFFECTIVE FEBRUARY5, |
| | 2004 TO ALLOW EMBOSSING SEALS MADE OF MATERIALS OTHER |
| | THAN METAL AND THE SAME TIME CLEAND UP THE APPERANCE OF |
| | THE SEAL BY ELEMITATINS OBLOLETE CONTENT AND CHANGING |
| | THE "CERTIFICATE" TO "LICENSE. |
| | NOTE: SHEET S1. THE SEALSTILL HAS THE WORD |
| | "CERTIFICATE" .THIS TYPE OF SEAL EXPIRED DECEMBER 31, |
| | 2005. THE NEW SEAL SHALL HAVE THE WORD "LICENSE". |
| | |
| | 9) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITTING |
| | BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | SUBMIT THE MATCHING STATE COVER SHEET WITH THE FL# FOR |
| | EACH PRODUCT APPROVAL. SEE FLORIDABUILDING.ORG FOR |
| | ADDITIONAL INFORMATION. |
| | |
| | 10) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _XX__ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _XX__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | _XX__THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 11)SHEET A2.0INDICATE THE SCUTTLE HATCHES DETAILS |
| | IS ON SHEET S-2, HOWEVER, THERE IS NO SHEET S-2. EITHER |
| | SUBMIT SHEET S-2 OR REVISED THE DRAWINGS TO REFLECT THE |
| | CORRECT INFORMATION. |
| | |
| | 12)WHAT IS THE SLOPE OF THE NEW ROOF OVERHANG. |
| | INDICATE ON THE DRAWINGS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |