2007-07-27 14:59:35*** UNSAT 4TH REVIEW ***
  
 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW,
 PLEASE CORRELATE THE LIGHTING AND METHODS OF CONTROLS
 FOR LIGHTING ON THE ENERGY CALCULATIONS WITH PLANS.
 PLEASE SEE THE PLANS SHOW AUTOMATED CONTROLS FOR ALL
 LIGHTING, HOWEVER THE INPUT DATA REPORT SHOWS *MANUAL
 ON/OFF* FOR TWO OF THE FIXTURES FOR BATHROOMS? THIS IS
 NOT POSSIBLE.
 PLEASE ALSO SEE THE NEW ENERGY CALCULATIONS SUBMITTED
 ARE UNDER THE NEW CODE DATED AS OF DECEMBER 8TH, 2006.
 THIS PROJECT IS UNDER THE PREVIOUS CODE REVISIONS TO
 THE 2004 FBC WHICH REQUIRES THE RELEVANT ENERGY
 CALCULATIONS AT THE TIME OF PERMIT APPLICATION.
 PLEASE SEE THIS WOULD BE VERSION 2.11AS ADOPTED BY THE
 2004 FBC W/2005 REVISIONS.
 PLEASE KNOW THIS WAS CONFIRMED WITH THE STATE AND
 BUILDING OFFICIAL. MAY NOT SUBMIT ENERGY CALCULATIONS
 FROM ONE CODE AND PLANS FROM ANOTHER CODE EVEN IF THE
 NEW ENERGY CODE IS MORE RESTRICTIVE.
 13-415.1.A
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES
 SPECIFICALLY NOTED FOR ELECTRICAL PLANS TO BE SIGNED BY
 THE ENGINEER OF RECORD AS ON FILE. PLEASE SEE ONLY THE
 NEW REVISED SHEET E2.1 CONTAINS THE SIGNATURE AS
 RECOGNIZED AND AS ON-FILE WITH THE CITY OF WEST PALM
 BEACH.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717