| 2007-07-27 14:59:35 | *** UNSAT 4TH REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW, |
| | PLEASE CORRELATE THE LIGHTING AND METHODS OF CONTROLS |
| | FOR LIGHTING ON THE ENERGY CALCULATIONS WITH PLANS. |
| | PLEASE SEE THE PLANS SHOW AUTOMATED CONTROLS FOR ALL |
| | LIGHTING, HOWEVER THE INPUT DATA REPORT SHOWS *MANUAL |
| | ON/OFF* FOR TWO OF THE FIXTURES FOR BATHROOMS? THIS IS |
| | NOT POSSIBLE. |
| | PLEASE ALSO SEE THE NEW ENERGY CALCULATIONS SUBMITTED |
| | ARE UNDER THE NEW CODE DATED AS OF DECEMBER 8TH, 2006. |
| | THIS PROJECT IS UNDER THE PREVIOUS CODE REVISIONS TO |
| | THE 2004 FBC WHICH REQUIRES THE RELEVANT ENERGY |
| | CALCULATIONS AT THE TIME OF PERMIT APPLICATION. |
| | PLEASE SEE THIS WOULD BE VERSION 2.11AS ADOPTED BY THE |
| | 2004 FBC W/2005 REVISIONS. |
| | PLEASE KNOW THIS WAS CONFIRMED WITH THE STATE AND |
| | BUILDING OFFICIAL. MAY NOT SUBMIT ENERGY CALCULATIONS |
| | FROM ONE CODE AND PLANS FROM ANOTHER CODE EVEN IF THE |
| | NEW ENERGY CODE IS MORE RESTRICTIVE. |
| | 13-415.1.A |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES |
| | SPECIFICALLY NOTED FOR ELECTRICAL PLANS TO BE SIGNED BY |
| | THE ENGINEER OF RECORD AS ON FILE. PLEASE SEE ONLY THE |
| | NEW REVISED SHEET E2.1 CONTAINS THE SIGNATURE AS |
| | RECOGNIZED AND AS ON-FILE WITH THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |