Plan Review Notes
Plan Review Notes For Permit 06100214
Permit Number 06100214
Review Stop E
Sequence Number 3
Notes
Date Text
2007-06-20 12:01:37*** UNSAT 3RDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 NEED TO COORDINATE WITH THE PLANS FOR THE NUMBER OF
 FIXTURES, THE WATTAGE FOR FIXTURES. PLEASE SEE THE
 PLANS DO NOT INDICATE ANY FIXTURE LEGEND FOR THE
 FIXTURES AND WATTAGE FOR EACH. PLEASE SEE FIXTURES ON
 ENERGY CALCULATIONS INDICATE COMPACT FLUORESCENT WHICH
 IS NOT CLEAR WHEN THE MAJORITY OF THE FIXTURES ON PLANS
 ARE 2X4 LAY-IN FIXTURES.
 PLEASE PROVIDE INFORMATION FOR THESE FIXTURE TYPES AND
 BE SURE TO COORDINATE WITH CALCULATIONS.
 PLEASE BE SURE THE OWNER AGENT IS ISGNED ON SHEETS FOR
 VERIFICATION.13-103.1, 13-415.1.AB.1.1
  
 2) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK WAS NOT ADJUSTED BY THE CONTRACTOR. PLEASE SEE FBC
 108.3 AS ALL EQUIPMENT, LABOR, MATERIALS, DESIGN COST
 FOR ARCHITECTURAL AND ENGINEERING ETC.
 THE VALUE AS SUBMITTED IS TOO LOW AND IF AN APPROPRIATE
 VALUE IS NOT INDICATE, ONE WILL BE ASSESSED BY GUIDES
 ADOPTED BY THE FBC.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE NOT SIGNED
 WITH SIGNATURE ON FILE AND RECOGNIZED BY THIS OFFICE.
 FS 471.025
  
 4) NOTE: PLEASE SEE THAT SETS NEED TO BE SUBMITTED WITH
 ALL SHEETS ATTACHED INTO SETS FOR REVIEW AND STAMPING
 AS PREVIOUSLY STATED IN EACH OF THE PREVIOUS REVIEWS.
 PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE BE SURE THESE
 ARE BOUND IN SOME MANOR.
 SETS WERE PLACED AND ATTACHED TOGETHER BY THIS REVIEWER
 HOWEVER WILL NOT BE DONE IF PLANS ARE SUBMITTED THE
 SAME WAY FOR THE NEXT REVIEW.
 FBC 106.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]