| 2007-06-20 12:01:37 | *** UNSAT 3RDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | NEED TO COORDINATE WITH THE PLANS FOR THE NUMBER OF |
| | FIXTURES, THE WATTAGE FOR FIXTURES. PLEASE SEE THE |
| | PLANS DO NOT INDICATE ANY FIXTURE LEGEND FOR THE |
| | FIXTURES AND WATTAGE FOR EACH. PLEASE SEE FIXTURES ON |
| | ENERGY CALCULATIONS INDICATE COMPACT FLUORESCENT WHICH |
| | IS NOT CLEAR WHEN THE MAJORITY OF THE FIXTURES ON PLANS |
| | ARE 2X4 LAY-IN FIXTURES. |
| | PLEASE PROVIDE INFORMATION FOR THESE FIXTURE TYPES AND |
| | BE SURE TO COORDINATE WITH CALCULATIONS. |
| | PLEASE BE SURE THE OWNER AGENT IS ISGNED ON SHEETS FOR |
| | VERIFICATION.13-103.1, 13-415.1.AB.1.1 |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK WAS NOT ADJUSTED BY THE CONTRACTOR. PLEASE SEE FBC |
| | 108.3 AS ALL EQUIPMENT, LABOR, MATERIALS, DESIGN COST |
| | FOR ARCHITECTURAL AND ENGINEERING ETC. |
| | THE VALUE AS SUBMITTED IS TOO LOW AND IF AN APPROPRIATE |
| | VALUE IS NOT INDICATE, ONE WILL BE ASSESSED BY GUIDES |
| | ADOPTED BY THE FBC. |
| | |
| | 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE NOT SIGNED |
| | WITH SIGNATURE ON FILE AND RECOGNIZED BY THIS OFFICE. |
| | FS 471.025 |
| | |
| | 4) NOTE: PLEASE SEE THAT SETS NEED TO BE SUBMITTED WITH |
| | ALL SHEETS ATTACHED INTO SETS FOR REVIEW AND STAMPING |
| | AS PREVIOUSLY STATED IN EACH OF THE PREVIOUS REVIEWS. |
| | PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE BE SURE THESE |
| | ARE BOUND IN SOME MANOR. |
| | SETS WERE PLACED AND ATTACHED TOGETHER BY THIS REVIEWER |
| | HOWEVER WILL NOT BE DONE IF PLANS ARE SUBMITTED THE |
| | SAME WAY FOR THE NEXT REVIEW. |
| | FBC 106.1 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |