| Date |
Text |
| 2007-03-07 14:29:13 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE WPB |
| | |
| | |
| | 1. OK |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. THE EMBOSSED SEAL SHALL |
| | IMPART ALL REQUIRED INFORMATION ON EACH SHEET. PLEASE |
| | IMPRESS ALL INFORMATION REQUIRED BY FAC 61G1-16.002(1) |
| | & FS 481.2055. |
| | ****RESPONSE NOTED, BUT ALL THE INFORMATION REQUIRED IS |
| | NOT IMPRESSED ON EACH SHEET. THE SEAL APPEARS TO BE |
| | WORN OUT, AND MAYBE A NEW SEAL IS NEEDED. |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | |
| | 6. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT |
| | LMASSON, ENVIRONMENTAL COMPLIANCE MANAGER, (561) |
| | 822-2271, FAX (561) 822-2279, E-MAIL [email protected]. |
| | UTILITY ORD. 3434. |
| | ****RESPONSE NOTED, BUT NO REPLY FROM ENVIRONMENTAL |
| | COMPLIANCE AT THIS TIME. I WILL TRY TO GET THE FINAL |
| | DETERMINATION. |
| | |
| | 7. OK (DEPT. OF AGRICULTURE) |
| | 8. OK |
| | 9. OK (DELETED) |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHTS P2.1 AND P5.1 THE UNDERCOUNTER GREASE TRAP IS |
| | NOT APPROVED. A MINIMUM 750 GALLON GREASE INTERCEPTOR |
| | IS REQUIRED PER SECTION 90-124(7)(F) OF THE MUNICIPAL |
| | CODE AND THE UTILITY DEPT STANDARD GREASE INTERCEPTOR |
| | DETAIL. |
| | ****RESPONSE NOTED. WAITING FOR RESPONSE FROM |
| | ENVIRONMENTAL COMPLIANCE. |
| | |
| | 13. OK |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | F. OK |
| | G. OK |
| | H. N/A |
| | I. N/A |
| | J. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SHT P5.1 WATER ISOMETRIC, THE WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES, IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH |
| | 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |