| 2007-03-04 11:44:50 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THAT SOME NOTES ARE FROM THE PREVIOUS |
| | REVIEW STILL ARE IN NEED OF ADDRESSING. |
| | PLEASE SEE THERE ARE MANY NEW NOTES AS SCOPE OF WORK |
| | FOR ELECTRICAL HAS COMPLETELY CHANGED. |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE FOR CHAPTER 13 STILL |
| | NEEDS TO BE CLARIFIED. PLEASE SEE CALCULATIONS |
| | SUBMITTED DO NOT CORRELATE WITH LIGHTING AS SHOWN ON |
| | PLANS OR CONTROL FOR SUCH LIGHTING. |
| | PLEASE SEE PREVIOUS ENERGY CALCULATIONS SUBMITTED AS |
| | ONLY ONE FIXTURE IS BEING SHOWN AND *MANUAL ON/OFF *. |
| | PLEASE SEE NO MAXIMUM TIMES ARE SHOWN FOR DEVICES. |
| | PLEASE INDICATE MAXIMUM LIGHTING POWER ALLOWANCES. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. 13-415.2. |
| | ETC |
| | |
| | 2) NOTE: PLEASE SEE NEW SERVICE RISER AND PLEASE |
| | CORRELATE ALL EQUIPMENT. SOME SHOWN AS 2400AMPS, |
| | 2500AMPS ETC? |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 3) NOTE: PLEASE SEE THE MSBA AND RISER AS SHOWN COULD |
| | HAVE POWER FROM BOTH THE UTILITY AND BACK UP POWER |
| | SOURCE. |
| | PLEASE SEE PLANS NOW INDICATE A NEW SWITCH BOARD |
| | OUTSIDE WHICH DOES NOT PROVIDE THE INADVERTENT |
| | CONNECTION OF THE EQUIPMENT INSIDE. |
| | PLEASE KNOW THAT A KIRK KEY INTERLOCK WILL NOT PROVIDE |
| | A *FAIL SAFE/INADVERTENT* OPERATION. THIS OFFICE HAS |
| | REVIEWED DOCUMENTATION PROVIDED BY SQ *D* ON OTHER |
| | PROJECT(S) WHICH DOES NOT SEEM TO MEET CODE FOR THE |
| | INSTALLATION. PLEASE KNOW IT IS THE UNDERSTANDING OF |
| | THIS OFFICE THAT SOME EQUIPMENT IS BEING SUBMITTED FOR |
| | LISTINGS FOR INTENDED USE OF TRANSFER EQUIPMENT HOWEVER |
| | INFORMATION FOR THIS HAS NOT BEEN SUBMITTED AT THIS |
| | TIME FOR ALLOWANCE. |
| | PLEASE KNOW THAT THERE HAVE BEEN PREVIOUS PROJECTS |
| | WHICH MAY HAVE ALLOWED THESE TYPES OF DEVICES HOWEVER |
| | THIS WILL NOT BE PERMITTED BY THIS AHJ. PLEASE KNOW |
| | THIS AHJ ALONG WITH SEVERAL OTHER LOCAL JURISDICTIONS |
| | HAVE SEEN MULTIPLE KEYS ON-SITE WHICH WILL ALLOW BOTH |
| | SIDES TO BE CONNECTED. PLEASE KNOW THAT UNTIL PRODUCTS |
| | ARE LISTED AND PROVIDE THE OPERATION WHICH PROVIDES THE |
| | INADVERTENT CONNECTION FROM THE UTILITY AND THE BACK UP |
| | POWER SOURCE THIS IS A LIFE SAFETY AND PROPERTY HAZARD |
| | AND WILL NOT BE ACCEPTED BY THIS AHJ. |
| | THIS OFFICE HAS NOT MENTIONED THAT A *LISTED TRANSFER |
| | SWITCH* IS REQUIRED HOWEVER WE ARE REQUIRING THE DEVICE |
| | IS LISTED FOR USE AND THAT IT PROVIDES COMPLETE FAIL |
| | SAFE OPERATION. |
| | DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT. |
| | PLEASE SEE 110.3, 90.7, 702.6 ETC. |
| | PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS. |
| | |
| | 4) NOTE: PLEASE SEE TAPPED CONDUCTORS ON GUTTER WOULD |
| | BE REQUIRED TO TERMINATE IN OCP PER 240.21. 408.16. |
| | PLEASE SEE THAT DISCONNECTS OF SOME KIND ARE BEING |
| | SHOWN HOWEVER PLEASE PROVIDE/SHOW THE OVER CURRENT AT |
| | EACH OF THESE. |
| | |
| | 5) NOTE:PLEASE SEE THIS COMMENT FROM THE PREVIOUS |
| | REVIEW HAS NOT BEEN ADJUSTED. PLEASE KNOW THAT BASED ON |
| | THE ELECTRICAL SCOPE OF WORK ALONG, THE VALUE HAS |
| | SUBSTANTIALLY INCREASED AND NO ADJUSTMENTS TO THE |
| | PERMIT APPLICATION HAVE BEEN MADE. A VALUE WILL BE |
| | REVIEWED AND ADJUSTED BY THIS OFFICE AS NEEDED ON THE |
| | NEXT RE-SUBMITTAL. |
| | PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL |
| | INCLUDE ALL LABOR AND MATERIALS, EVEN IF ANY EQUIPMENT |
| | IS OWNER SUPPLIED. |
| | PLEASE KNOW IF AN APPROPRIATE VALUE IS NOT ADJUSTED, |
| | ONE WILL BE ADJUSTED BASED ON MARSHALL'S & SWIFT GUIDE |
| | AS ADOPTED INTO THE FBC 108.3 ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 6) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE DIRECT |
| | ACCESS TO THE MAIN ELECTRICAL SWITCHGEAR FOR SHUT DOWN. |
| | DOORS, OPENINGS, TRAVEL DISTANCE, ETC. THE LOCATION |
| | NEEDS TO BE DETERMINED BY THIS OFFICE AND THE FIRE |
| | MARSHAL ONCE SHOWN ON PLANS. |
| | PLEASE SEE 230.70. |
| | PLEASE ALSO SEE THAT THE LOCATION FOR STORAGE/EASILY |
| | IGNITABLE ETC CAN NOT BE VERIFIED AT THIS TIME. |
| | PROTECTION OF THIS EQUIPMENT IS REQUIRED IN ANY OPEN |
| | AREAS AS THE OTHER EQUIPMENT ON PLANS OUTSIDE IS |
| | SHOWN. |
| | 110.26, 408.7, 240.24 ETC. |
| | |
| | 7) NOTE: PLEASE SEE THE NEW SWITCH GEAR SHOWS NEW OVER |
| | CURRENT PROTECTION TO ALL EXISTING PANELS; HOWEVER SIZE |
| | OF THOSE EXISTING PANELS HAS NOT BEEN SHOWN. |
| | PLEASE ALSO SEE PANELS *KB AND KC* WHICH DO NOT SHOW |
| | ANY ITEMS ON PANEL SCHEDULES, YET PANELS SHOW LOADS? |
| | PLEASE CLARIFY ALL PANELS, USE, LOADS ETC. |
| | 215.5, 240, 220, 310.16 ETC |
| | |
| | FBC 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR INFORMATION |
| | NEEDED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |