Plan Review Notes
Plan Review Notes For Permit 06100214
Permit Number 06100214
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-04 11:44:50** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE THAT SOME NOTES ARE FROM THE PREVIOUS
 REVIEW STILL ARE IN NEED OF ADDRESSING.
 PLEASE SEE THERE ARE MANY NEW NOTES AS SCOPE OF WORK
 FOR ELECTRICAL HAS COMPLETELY CHANGED.
  
 1) NOTE: PLEASE SEE COMPLIANCE FOR CHAPTER 13 STILL
 NEEDS TO BE CLARIFIED. PLEASE SEE CALCULATIONS
 SUBMITTED DO NOT CORRELATE WITH LIGHTING AS SHOWN ON
 PLANS OR CONTROL FOR SUCH LIGHTING.
 PLEASE SEE PREVIOUS ENERGY CALCULATIONS SUBMITTED AS
 ONLY ONE FIXTURE IS BEING SHOWN AND *MANUAL ON/OFF *.
 PLEASE SEE NO MAXIMUM TIMES ARE SHOWN FOR DEVICES.
 PLEASE INDICATE MAXIMUM LIGHTING POWER ALLOWANCES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. 13-415.2.
 ETC
  
 2) NOTE: PLEASE SEE NEW SERVICE RISER AND PLEASE
 CORRELATE ALL EQUIPMENT. SOME SHOWN AS 2400AMPS,
 2500AMPS ETC?
 FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE THE MSBA AND RISER AS SHOWN COULD
 HAVE POWER FROM BOTH THE UTILITY AND BACK UP POWER
 SOURCE.
 PLEASE SEE PLANS NOW INDICATE A NEW SWITCH BOARD
 OUTSIDE WHICH DOES NOT PROVIDE THE INADVERTENT
 CONNECTION OF THE EQUIPMENT INSIDE.
 PLEASE KNOW THAT A KIRK KEY INTERLOCK WILL NOT PROVIDE
 A *FAIL SAFE/INADVERTENT* OPERATION. THIS OFFICE HAS
 REVIEWED DOCUMENTATION PROVIDED BY SQ *D* ON OTHER
 PROJECT(S) WHICH DOES NOT SEEM TO MEET CODE FOR THE
 INSTALLATION. PLEASE KNOW IT IS THE UNDERSTANDING OF
 THIS OFFICE THAT SOME EQUIPMENT IS BEING SUBMITTED FOR
 LISTINGS FOR INTENDED USE OF TRANSFER EQUIPMENT HOWEVER
 INFORMATION FOR THIS HAS NOT BEEN SUBMITTED AT THIS
 TIME FOR ALLOWANCE.
 PLEASE KNOW THAT THERE HAVE BEEN PREVIOUS PROJECTS
 WHICH MAY HAVE ALLOWED THESE TYPES OF DEVICES HOWEVER
 THIS WILL NOT BE PERMITTED BY THIS AHJ. PLEASE KNOW
 THIS AHJ ALONG WITH SEVERAL OTHER LOCAL JURISDICTIONS
 HAVE SEEN MULTIPLE KEYS ON-SITE WHICH WILL ALLOW BOTH
 SIDES TO BE CONNECTED. PLEASE KNOW THAT UNTIL PRODUCTS
 ARE LISTED AND PROVIDE THE OPERATION WHICH PROVIDES THE
 INADVERTENT CONNECTION FROM THE UTILITY AND THE BACK UP
 POWER SOURCE THIS IS A LIFE SAFETY AND PROPERTY HAZARD
 AND WILL NOT BE ACCEPTED BY THIS AHJ.
 THIS OFFICE HAS NOT MENTIONED THAT A *LISTED TRANSFER
 SWITCH* IS REQUIRED HOWEVER WE ARE REQUIRING THE DEVICE
 IS LISTED FOR USE AND THAT IT PROVIDES COMPLETE FAIL
 SAFE OPERATION.
 DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT.
 PLEASE SEE 110.3, 90.7, 702.6 ETC.
 PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS.
  
 4) NOTE: PLEASE SEE TAPPED CONDUCTORS ON GUTTER WOULD
 BE REQUIRED TO TERMINATE IN OCP PER 240.21. 408.16.
 PLEASE SEE THAT DISCONNECTS OF SOME KIND ARE BEING
 SHOWN HOWEVER PLEASE PROVIDE/SHOW THE OVER CURRENT AT
 EACH OF THESE.
  
 5) NOTE:PLEASE SEE THIS COMMENT FROM THE PREVIOUS
 REVIEW HAS NOT BEEN ADJUSTED. PLEASE KNOW THAT BASED ON
 THE ELECTRICAL SCOPE OF WORK ALONG, THE VALUE HAS
 SUBSTANTIALLY INCREASED AND NO ADJUSTMENTS TO THE
 PERMIT APPLICATION HAVE BEEN MADE. A VALUE WILL BE
 REVIEWED AND ADJUSTED BY THIS OFFICE AS NEEDED ON THE
 NEXT RE-SUBMITTAL.
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL
 INCLUDE ALL LABOR AND MATERIALS, EVEN IF ANY EQUIPMENT
 IS OWNER SUPPLIED.
 PLEASE KNOW IF AN APPROPRIATE VALUE IS NOT ADJUSTED,
 ONE WILL BE ADJUSTED BASED ON MARSHALL'S & SWIFT GUIDE
 AS ADOPTED INTO THE FBC 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 6) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE DIRECT
 ACCESS TO THE MAIN ELECTRICAL SWITCHGEAR FOR SHUT DOWN.
 DOORS, OPENINGS, TRAVEL DISTANCE, ETC. THE LOCATION
 NEEDS TO BE DETERMINED BY THIS OFFICE AND THE FIRE
 MARSHAL ONCE SHOWN ON PLANS.
 PLEASE SEE 230.70.
 PLEASE ALSO SEE THAT THE LOCATION FOR STORAGE/EASILY
 IGNITABLE ETC CAN NOT BE VERIFIED AT THIS TIME.
 PROTECTION OF THIS EQUIPMENT IS REQUIRED IN ANY OPEN
 AREAS AS THE OTHER EQUIPMENT ON PLANS OUTSIDE IS
 SHOWN.
 110.26, 408.7, 240.24 ETC.
  
 7) NOTE: PLEASE SEE THE NEW SWITCH GEAR SHOWS NEW OVER
 CURRENT PROTECTION TO ALL EXISTING PANELS; HOWEVER SIZE
 OF THOSE EXISTING PANELS HAS NOT BEEN SHOWN.
 PLEASE ALSO SEE PANELS *KB AND KC* WHICH DO NOT SHOW
 ANY ITEMS ON PANEL SCHEDULES, YET PANELS SHOW LOADS?
 PLEASE CLARIFY ALL PANELS, USE, LOADS ETC.
 215.5, 240, 220, 310.16 ETC
  
 FBC 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR INFORMATION
 NEEDED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717