Plan Review Notes
Plan Review Notes For Permit 06100214
Permit Number 06100214
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-06 17:42:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS NUMBER IS
 REQUIRED IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS
 481.219. PLEASE PROVIDE REQUIRED INFORMATION ON EACH
 SEET.
  
 2. ALL ARCHITECTURAL SHEETS. THE EMBOSSED SEAL SHALL
 IMPART ALL REQUIRED INFORMATION ON EACH SHEET. PLEASE
 IMPRESS ALL INFORMATION REQUIRED BY FAC 61G1-16.002(1)
 & FS 481.2055.
  
 3. SHT A-0.0 CODES IN EFFECT ARE FBC-2004. PLEASE
 DESIGN TO THIS CODE AND CHANGE CODE REFERENCES TO
 REFLECT THIS REQUIREMENT.
  
 4. PLEASE INDICATE THE SPACE NUMBER ON THE APPLICATION
 AND ON THE PLANS. THE PLANS INDICATE THAT THIS IS A
 SPACE WITHIN THE BUILDING. SECTION 106.1.2.
  
 5. SHT A-0.1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A
 SERVICE SINK ARE REQUIRED. PLEASE INDICATE THE LOCATION
 OF EACH.
  
 6. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LMASSON, ENVIRONMENTAL COMPLIANCE MANAGER, (561)
 822-2271, FAX (561) 822-2279, E-MAIL [email protected].
 UTILITY ORD. 3434.
  
 7. MORE INFORMATION IS REQUIRED. WILL THERE BE SALES OF
 FOOD AND WILL THIS BE CONSIDERED A RESTURANT? IF SO THE
 PLANS WILL HAVE TO BE ROUTED TO DBPR HOTEL & RESTURANT
 DIVISION FOR REVIEW, AND A MINIMUM OF TWO SETS OF
 STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" WILL BE
 REQUIRED TO BE SUBMITTED TO WEST PALM BEACH FOR REVIEW
 PRIOR TO ISSUING A PERMIT. SECTION 102.2.1.
  
 8. SHT KE-2.1 DETAIL 15 INDICATES PLUMBING EQUIPMENT
 SCHEDULE. DETAIL 5 DOES NOT REFLECT THE ITEM NUMBERS.
 PLEASE CORRELATE SCHEDULE AND ITEM NUMBERS ON THE FLOOR
 PLAN. SECTION 106.1.1.
  
 9. SHT KE-2.1 DETAIL 15, ITEM 34 INDICATES A WATER
 FILTER. THE FILTER SHALL COMPLY WITH NSF-42. PLEASE
 SUBMIT MANUF. SPECIFICATIONS FOR THE FILTER SHOWING
 COMPLIANCE WITH THE NSF STANDARD. SECTION 611.1.
  
 10. SHT P.1 WATER SERVICE. AN RPZV BACKFLOW IS REQUIRED
 ON THE WATER SERVICE TO THE SPACE. SECTION 608.13.2.
 PLEASE INDICATE ON THE RISER DIAGRAM AND ON THE FLOOR
 PLAN.
  
 11. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED. SECTION
 607.3.2.
  
 12. SHTS P2.1 AND P5.1 THE UNDERCOUNTER GREASE TRAP IS
 NOT APPROVED. A MINIMUM 750 GALLON GREASE INTERCEPTOR
 IS REQUIRED PER SECTION 90-124(7)(F) OF THE MUNICIPAL
 CODE AND THE UTILITY DEPT STANDARD GREASE INTERCEPTOR
 DETAIL.
  
 13. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NO CORRESPONDING LENGTHS SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - THIS WILL BE VERIFIED
 WHEN ALL LENGTHS OF PIPE ARE SHOWN ON THE RISER
 DIAGRAM.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. - INDICATE IF WATER HEATER ROOM
 IS A CONFINED SPACE OR NOT. SHOW CUBIC FEET OF HEATER
 ROOM.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. SHOW THE MODEL NUMBER
 AND BTU LOAD FOR EACH PIECE OF EQUIPMENT TO REFLECT THE
 GAS RISER DIAGRAM.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]