| 2006-12-06 17:42:18 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE WPB |
| | |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS NUMBER IS |
| | REQUIRED IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS |
| | 481.219. PLEASE PROVIDE REQUIRED INFORMATION ON EACH |
| | SEET. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. THE EMBOSSED SEAL SHALL |
| | IMPART ALL REQUIRED INFORMATION ON EACH SHEET. PLEASE |
| | IMPRESS ALL INFORMATION REQUIRED BY FAC 61G1-16.002(1) |
| | & FS 481.2055. |
| | |
| | 3. SHT A-0.0 CODES IN EFFECT ARE FBC-2004. PLEASE |
| | DESIGN TO THIS CODE AND CHANGE CODE REFERENCES TO |
| | REFLECT THIS REQUIREMENT. |
| | |
| | 4. PLEASE INDICATE THE SPACE NUMBER ON THE APPLICATION |
| | AND ON THE PLANS. THE PLANS INDICATE THAT THIS IS A |
| | SPACE WITHIN THE BUILDING. SECTION 106.1.2. |
| | |
| | 5. SHT A-0.1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A |
| | SERVICE SINK ARE REQUIRED. PLEASE INDICATE THE LOCATION |
| | OF EACH. |
| | |
| | 6. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT |
| | LMASSON, ENVIRONMENTAL COMPLIANCE MANAGER, (561) |
| | 822-2271, FAX (561) 822-2279, E-MAIL [email protected]. |
| | UTILITY ORD. 3434. |
| | |
| | 7. MORE INFORMATION IS REQUIRED. WILL THERE BE SALES OF |
| | FOOD AND WILL THIS BE CONSIDERED A RESTURANT? IF SO THE |
| | PLANS WILL HAVE TO BE ROUTED TO DBPR HOTEL & RESTURANT |
| | DIVISION FOR REVIEW, AND A MINIMUM OF TWO SETS OF |
| | STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" WILL BE |
| | REQUIRED TO BE SUBMITTED TO WEST PALM BEACH FOR REVIEW |
| | PRIOR TO ISSUING A PERMIT. SECTION 102.2.1. |
| | |
| | 8. SHT KE-2.1 DETAIL 15 INDICATES PLUMBING EQUIPMENT |
| | SCHEDULE. DETAIL 5 DOES NOT REFLECT THE ITEM NUMBERS. |
| | PLEASE CORRELATE SCHEDULE AND ITEM NUMBERS ON THE FLOOR |
| | PLAN. SECTION 106.1.1. |
| | |
| | 9. SHT KE-2.1 DETAIL 15, ITEM 34 INDICATES A WATER |
| | FILTER. THE FILTER SHALL COMPLY WITH NSF-42. PLEASE |
| | SUBMIT MANUF. SPECIFICATIONS FOR THE FILTER SHOWING |
| | COMPLIANCE WITH THE NSF STANDARD. SECTION 611.1. |
| | |
| | 10. SHT P.1 WATER SERVICE. AN RPZV BACKFLOW IS REQUIRED |
| | ON THE WATER SERVICE TO THE SPACE. SECTION 608.13.2. |
| | PLEASE INDICATE ON THE RISER DIAGRAM AND ON THE FLOOR |
| | PLAN. |
| | |
| | 11. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE |
| | INDICATE HOW THIS WILL BE ACCOMPLISHED. SECTION |
| | 607.3.2. |
| | |
| | 12. SHTS P2.1 AND P5.1 THE UNDERCOUNTER GREASE TRAP IS |
| | NOT APPROVED. A MINIMUM 750 GALLON GREASE INTERCEPTOR |
| | IS REQUIRED PER SECTION 90-124(7)(F) OF THE MUNICIPAL |
| | CODE AND THE UTILITY DEPT STANDARD GREASE INTERCEPTOR |
| | DETAIL. |
| | |
| | 13. THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | SEPARATE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - NO CORRESPONDING LENGTHS SHOWN. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - THIS WILL BE VERIFIED |
| | WHEN ALL LENGTHS OF PIPE ARE SHOWN ON THE RISER |
| | DIAGRAM. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. - INDICATE IF WATER HEATER ROOM |
| | IS A CONFINED SPACE OR NOT. SHOW CUBIC FEET OF HEATER |
| | ROOM. |
| | |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. SHOW THE MODEL NUMBER |
| | AND BTU LOAD FOR EACH PIECE OF EQUIPMENT TO REFLECT THE |
| | GAS RISER DIAGRAM. |
| | |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |