Plan Review Notes
Plan Review Notes For Permit 06100214
Permit Number 06100214
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-13 12:04:04*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
 AMEND SHEET A 0.0 UNDER BUILDING CODES.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY TEREOF.
  
 4.INTERIOR FINISH IN AN UNSPRINKLERED BUILDING SHALL
 BE CLASS "A" OR CLASS "B" , NO CLASS "C".
  
 5.THERE APPEARS TO BE A DISCREPANCY IN THE SWING OF
 THE DOUBLE EXIT DOORS.FOR EXAMPLE, SHEET KE-1.0 HAS
 THE DOORS SWINGING INTO THE EGRESS PATH, WHEREAS SHEET
 P2.1 HAS THE DOORSPROPERLY SWINGING OUT TOWARDS THE
 DIRECTION OF EGRESS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722