| Plan Review Notes For Permit 06100214 |
| Permit Number |
06100214 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-13 12:04:04 | *****DENIED***** | | | | | | | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | AMEND SHEET A 0.0 UNDER BUILDING CODES. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY TEREOF. | | | | | | 4.INTERIOR FINISH IN AN UNSPRINKLERED BUILDING SHALL | | | BE CLASS "A" OR CLASS "B" , NO CLASS "C". | | | | | | 5.THERE APPEARS TO BE A DISCREPANCY IN THE SWING OF | | | THE DOUBLE EXIT DOORS.FOR EXAMPLE, SHEET KE-1.0 HAS | | | THE DOORS SWINGING INTO THE EGRESS PATH, WHEREAS SHEET | | | P2.1 HAS THE DOORSPROPERLY SWINGING OUT TOWARDS THE | | | DIRECTION OF EGRESS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|