Plan Review Notes
Plan Review Notes For Permit 06100214
Permit Number 06100214
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-28 18:15:35**** UNSAT ******
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES ARE
 STATED ON PLANS. 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72, 2004 NFPA-96 ETC.
  
 2) NOTE: PLEASE SEE SPACE APPEARS TO BE PART OF A
 LARGER BUILDINGAND THE NEW SERVICE BEING REQUESTED IS
 NOT GRANTED AT THIS TIME. THIS BUILDING ALREADY
 CONTAINS NUMEROUS MAINS AND SERVICE EQUIPMENT. A
 SERVICE CHANGE/OVERHAUL WILL BE REQUIRED. AS SHOWN AND
 GIVEN THE SERVICE ON THE BUILDING THIS DOES NOT MEET
 230.2.
  
 3) NOTE: PLEASE SEE PLANS STATE A "TEST" KITCHEN
 HOWEVER THE SAME REQUIREMENTS FOR ANY COMMERCIAL
 KITCHEN WILL BE REQUIRED AS THESAME TASKS WILL BE AT
 HAND.
 PLEASE SEE 210.8B3 FOR ALL RECEPTS. PLEASE KNOW, EVEN
 ALL THE EXISTING.
  
 4) NOTE: PLEASE SEE AS THIS APPEARS TO BE A CHANGE IN
 USE OR OCCUPANCY, PLEASE SEE CHAPTER 13 FOR
 COMPLIANCE.
 PLEASE SHOW ALL OTHER AREAS PART OF THIS BUILDING.
  
 5) NOTE: PLEASE SEE ANY POSSIBLE FIRE REVIEW NOTES WITH
 RESPECT TO AN EXIT LT WHICH APPEARS TO GUIDE PERSON
 BACK INTO THE LARGER PORTION OF THE BUILDING. THIS IS
 NOT AN ELECTRICAL REVIEW NOTE , HOWEVER ANY CHANGES MAY
 AFFECT THE ELECTRICAL PLANS.
 LS 101 7.8, 7.9
  
 6) NOTE: PLEASE SEE TAPPED CONDUCTORS ON GUTTER WOULD
 BE REQUIRED TO TERMINATE IN OCP PER 240.21.
 408.16HOWEVER PLEASE KNOW, AT THIS TIME, DUE TO THE
 UNKNOWN OF THE EXISTING SERVICE, BUILDING ETC, THIS
 COMMENT HAS NO AFFECT AS THE SERVICE AS SHOWN IS NOT
 PERMITTED.
  
 7) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOUR AND MATERIALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE KNOW IF AN APPROPRIATE VALUE IS NOT ADJUSTED,
 ONE WILL BE ADJUSTED BASED ON MARSHALL'S & SWIFT GUIDE
 AS ADOPTED INTOTHE FBC 108.3 ADMINISTRATIVE SECTION
 AS ADOPTED BY THE CITY OF WESTPALM BEACH.
  
 8) NOTE: PLEASE SEE SOME SHEETS ARE MISSING FROM SETS
 WHICH ARE INDICATED ON COVER TITLE SHEET.
  
 9) NOTE:** IMPORTANT**
 ** DO NOT IGNORE THIS COMMENT.
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICLA PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-22 09:16:29SEE UPDATED "I" NOTES, TO BE PLACED ON COMM BOARD.