| 2006-10-28 18:15:35 | **** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES ARE |
| | STATED ON PLANS. 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72, 2004 NFPA-96 ETC. |
| | |
| | 2) NOTE: PLEASE SEE SPACE APPEARS TO BE PART OF A |
| | LARGER BUILDINGAND THE NEW SERVICE BEING REQUESTED IS |
| | NOT GRANTED AT THIS TIME. THIS BUILDING ALREADY |
| | CONTAINS NUMEROUS MAINS AND SERVICE EQUIPMENT. A |
| | SERVICE CHANGE/OVERHAUL WILL BE REQUIRED. AS SHOWN AND |
| | GIVEN THE SERVICE ON THE BUILDING THIS DOES NOT MEET |
| | 230.2. |
| | |
| | 3) NOTE: PLEASE SEE PLANS STATE A "TEST" KITCHEN |
| | HOWEVER THE SAME REQUIREMENTS FOR ANY COMMERCIAL |
| | KITCHEN WILL BE REQUIRED AS THESAME TASKS WILL BE AT |
| | HAND. |
| | PLEASE SEE 210.8B3 FOR ALL RECEPTS. PLEASE KNOW, EVEN |
| | ALL THE EXISTING. |
| | |
| | 4) NOTE: PLEASE SEE AS THIS APPEARS TO BE A CHANGE IN |
| | USE OR OCCUPANCY, PLEASE SEE CHAPTER 13 FOR |
| | COMPLIANCE. |
| | PLEASE SHOW ALL OTHER AREAS PART OF THIS BUILDING. |
| | |
| | 5) NOTE: PLEASE SEE ANY POSSIBLE FIRE REVIEW NOTES WITH |
| | RESPECT TO AN EXIT LT WHICH APPEARS TO GUIDE PERSON |
| | BACK INTO THE LARGER PORTION OF THE BUILDING. THIS IS |
| | NOT AN ELECTRICAL REVIEW NOTE , HOWEVER ANY CHANGES MAY |
| | AFFECT THE ELECTRICAL PLANS. |
| | LS 101 7.8, 7.9 |
| | |
| | 6) NOTE: PLEASE SEE TAPPED CONDUCTORS ON GUTTER WOULD |
| | BE REQUIRED TO TERMINATE IN OCP PER 240.21. |
| | 408.16HOWEVER PLEASE KNOW, AT THIS TIME, DUE TO THE |
| | UNKNOWN OF THE EXISTING SERVICE, BUILDING ETC, THIS |
| | COMMENT HAS NO AFFECT AS THE SERVICE AS SHOWN IS NOT |
| | PERMITTED. |
| | |
| | 7) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| | SHALL INCLUDE ALL LABOUR AND MATERIALS, EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | PLEASE KNOW IF AN APPROPRIATE VALUE IS NOT ADJUSTED, |
| | ONE WILL BE ADJUSTED BASED ON MARSHALL'S & SWIFT GUIDE |
| | AS ADOPTED INTOTHE FBC 108.3 ADMINISTRATIVE SECTION |
| | AS ADOPTED BY THE CITY OF WESTPALM BEACH. |
| | |
| | 8) NOTE: PLEASE SEE SOME SHEETS ARE MISSING FROM SETS |
| | WHICH ARE INDICATED ON COVER TITLE SHEET. |
| | |
| | 9) NOTE:** IMPORTANT** |
| | ** DO NOT IGNORE THIS COMMENT. |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT THE ELECTRICLA PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-10-22 09:16:29 | SEE UPDATED "I" NOTES, TO BE PLACED ON COMM BOARD. |