Plan Review Notes
Plan Review Notes For Permit 06100199
Permit Number 06100199
Review Stop B
Sequence Number 3
Notes
Date Text
2007-01-22 18:57:43BUILDING REVIEW THIRD CHECKLIST:
 1- FLAT ROOF NOA 03-0501.02 SUBMITTED:
 A) THERE ARE TWO DIFFERENT APPROVED ASSEMBLIES THAT
 WERE HIGHLIGHTED. ONE IS ON PAGE 26 AND THE OTHER ONE
 IS ON PAGE28. THESE ARE 2 COMPLETELY DIFFERENT
 APPLICATIONS. NEED TO SELECT THE SPECIFIC ASSEMBLY THAT
 IS GOING TO BE INSTALLED.
  
 B) PROVIDE THE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7. SEE PAGE 32 ON NOA SUBMITTED.
  
 2- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED. SEE FLORIDA STATUTES
 713.13 FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 3- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORMS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. LETTER SUBMITTED BY ENGINEER
 SAYING THAT HE REVIEWED PRODUCT APPROVALS WITH
 CONTRACTOR IS TOO GENERAL. NEED TO IDENTIFY EACH
 PRODUCT APPROVAL WITH SPECIFIC INFORMATION LIKE
 MANUFACTURER, NOA NUMBER, ETC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712